ABB HD4 Series Guida rapida

Medium voltage products
HD4
Installation and service instructions
Index
1. Packing and transport 5
2. Checking on receipt 6
3. Storage 7
4. Handling 8
5. Description 10
6. Instructions for circuit-breaker operation 12
7. Installation 13
8. Putting into service 32
9. Periodical checking 34
10. Maintenance operations 34
11. Indications for handling apparatus with SF6 35
12. Spare parts and accessories 36
12-40.5 kV – 630-3600 A – 16-50 kA


3
• Make sure that the installation room (spaces, divisions
and ambient) are suitable for the electrical apparatus.
•Check that all the installation, putting into service and
maintenance operations are carried out by qualified
personnel with in-depth knowledge of the apparatus.
•Make sure that the standard and legal prescriptions
are complied with during installation, putting into
service and maintenance, so that installations
according to the rules of good working practice and
safety in the work place are constructed.
•Strictly follow the information given in this instruction
manual.
•Check that the rated performance of the apparatus is
not exceeded during service.
•Pay special attention to the danger notes indicated in
the manual by the following symbol:
•Check that the personnel operating the apparatus
have this instruction manual to hand as well as the
necessary information for correct intervention.
Responsible behaviour safeguards your own
and others’ safety!
For any requests, place contact the
ABB Assistance Service.
For your safety!

4
I. Introduction
This publication contains the information necessary for
installation and putting into service of HD4 medium voltage
circuit-breakers.
For correct usage of the product, please read this manual
carefully.
For correct mounting of accessories and/or spare parts
please refer to the relevant instructions.
Like all the apparatus manufactured by us, the HD4 circuit-
breakers are designed for different installation configurations.
They do, however, allow further technical-constructional
variations (at the customer’s request) to suit special
installation requirements.
For this reason, the information given below does not always
cover special configurations.
Apart from this booklet, it is therefore always necessary to
refer to the latest technical documentation available (circuit
diagram, wiring diagrams, assembly and installation drawings,
any studies of protection co-ordination, etc.), especially with
regard to any variations from standardized configurations
requested.
All the operations regarding installation, putting
into service, operation and maintenance must be
carried out by suitably qualified personnel with in-
depth knowledge of the apparatus.
Only use original spare parts for maintenance operations.
For further information, also see the technical catalogue of the
circuit-breaker and the spare parts catalogue.
II. Programme for the environmental
protection
The HD4 circuit-breakers comply with ISO 14000 Standards
(Guidelines for the Environmental Management).
The production system of the Medium Voltage factories
complies for the environmental protection in terms of energy
consumption, raw materials and waste.
The environmental impact of the product life cycle is assessed
by the LCA - Life Cycle Assessment procedure, which is also
the result of a well-focused project phase in the selection of
materials, processes and packaging.
The Product environmental declaration is available for the
HD4 circuit-breakers
Production techniques are carried out in order to achieve
an easy dismantling and separation of the components at
the end of the circuit-breaker life cycle, while optimizing the
recycling process.

5
1. Packing and transport
The circuit-breaker is shipped in special packing in the open
position with the springs discharged and with absolute pole
pressure corresponding with the service value.
Each piece of apparatus is protected by a plastic film to
prevent any infiltration of water during the loading and
unloading stages and to keep the dust off during storage.
Handling and transport must only be carried out by expert
and properly trained personnel.
Do not remove or alter the switch identification contents and
labels.
Switches subject to UN3164 standards for transportation by
air and / or sea.
Safety data sheet: 1VCD850182

6
Caption
A Circuit-breaker nameplate
B Operating mechanism nameplate
1 Type of apparatus
2 Symbols and compliance with Standards
3 Serial number
4 Circuit-breaker characteristics
5 Characteristics of the operating auxiliaries
Nameplate
Fig. 1
A
B
3
4
2
CIRCUIT-BREAKER IEC 62271-100
HD4 ... ... ... CEI 17-1
CLASSIFICATION ... ... ...
SN ... ... ... PR. YEAR ......
M MASS ... Kg
Ur
m SF6 mass for circuit-breaker .... Kg
ELECTRIC DIAGRAM ... ... ... ...
FIG. ... ...
.. ... ... ... OPERATING MECHANISM
-MO1 ... ... ... V
Made by ABB
1
5
Before carrying out any operation, always make
sure that the operating mechanism dprings are
discharged and that the apparatus is in the open
position.
On receipt, check the state of the apparatus, that the packing
is undamaged and that the nameplate data corresponds (see
fig. 1) with that specified in the order acknowledgement and
in the delivery note.
Also make sure that all the materials described in the shipping
note are included in the supply.
If any damage or irregularity is discovered on unpacking,
notify ABB (directly or through the agent or supplier) as soon
as possible and in any case within five days of receipt.
The apparatus is only supplied with the accessories
specified at the time of order and confirmed in the order
acknowledgement sent by ABB.
The following accompanying documents are inserted in the
shipping packing:
– Instruction manual (this document)
– Test certificate
– Identification tag
– Fiscal copy of shipping note
– Electrical diagram
These other documents are sent prior to shipment:
– Order acknowledgement
– Original copy of shipping note
– Any drawings or documents regarding special
configurations/conditions.
2. Checking on receipt

7
3. Storage
In case a storage period is foreseen, on request our
workshops will provide a suitable packing to the specified
storage conditions.
On receipt, the apparatus must be carefully unpacked and
checked as described in chapter 2: Checkink on receipt.
If immediate installation is not possible and the circuit breaker
has to be re-stored again, it is necessary to restore the
packaging at least suitable for protection against dust.
Insert hygroscopic substances in the packaging in the
quantity of at least one standard pack per apparatus.
Therefore, store in a sheltered, well-ventilated area with a
dry, non-dusty, non-corrosive atmosphere away from highly
flammable materials, with a temperature between -5 °C and
+45 °C.
In any case, avoid accidental shocks or accommodations that
stress the structure of the circuit breaker.

8
1
2
2
2
1
3
4. Handling
Before carrying out any operation, always check that the
operating mechanism springs are discharged and that the
apparatus is in the open position.
Circuit-breakers up to 24 kV
– To lift and handle the circuit-breaker, use the tool (1) (fig. 2a:
shortest hooks for circuit-breakers up to 17.5 kV; all hooks
for 24 kV circuit-breakers).
– Put the hooks (2) in the holes prepared in the circuit-breaker
frame and lift.
– On completion of the operation (and in any case before
putting into service) unhook the lifting tool (1) (fig. 2b) and
dismantle the crosspiece (2) by unscrewing the screws (3).
Fig. 2a
36 kV circuit-breakers
– Attach the tools (1) to lift and handle the circuit-breaker
(fig. 2c);
–Attach the hooks (2) as illustrated in fig. 2d and lift;
– On completion of the operation, remove the tools (1).
Always take great care during handling not to stress the
insulating parts and the circuit-breaker terminals.
The apparatus must not be handled by inserting
lifting devices directly under the apparatus itself.
Should it be necessary to use this method, place
the circuit-breaker on a sturdy supporting surface
(see fig. 3).
Fig. 2b

9
1
2
Fig. 2c
Fig. 3Fig. 2d

10
Fig. 4
Caption
1 Signalling device for state of SF6 pressure (on request)
2 Opening push button
3 Closing push button
4 Operator counter
5 Signalling device for circuit-breaker open/closed
6 Shaft for manual closing spring charging
5. Description
5.1. General features
The HD4 series are sulphur hexafluoride circuit-breakers for
indoor installation. For the electrical performance, please refer
to the corresponding technical catalogue code 1VCP000004.
For special installation conditions please ask ABB.
The following versions are available:
– fixed
– withdrawable for CBE, PowerCube enclosures and CBF
fixed parts
– withdrawable for switchgear: UniGear type ZS1, UniGear
type ZS2, UniGear type ZS3.2
– withdrawable for switchgear: UniSwitch, UniMix and
UniSec.
5.2. Reference Standards
The HD4 series circuit-breakers comply with the following
Standards:
– IEC 62271-100.
5.3. Fixed circuit-breaker
The fixed circuit-breaker (see fig. 4) corresponds to the basic
version complete with a front protection shield and frame.
The anchoring holes are drilled in the lower part of the frame.
The terminal box, fixed on the upper protection, is available
for connection of the circuit-breaker auxiliary circuits.
The earthing screw is located on the circuit-breaker side.
For further details, refer to the caption of fig. 4.
5.4. Withdrawable circuit-breaker
The withdrawable circuit-breakers (see fig. 5) are consist
of a truck on which the supporting structure of the circuit-
breaker itself is fixed. The cord with the connector (plug) for
connection of the operating mechanism electrical accessories
comes out of the front protection of the circuit-breaker.
Fixed circuit-breaker
7 Signalling device for closing springs charged/discharged
8 Characteristics nameplate
9 Terminals (only available for certain versions)
10 Pressure switch (on request)
11 Valve for checking the SF6 gas pressure
12 Resetting button for protection circuit-breaker of geared motor (on request)
10 - 11 (36 kV)
Altri manuali per HD4 Series
1
Indice
Altri manuali ABB Utensili elettrici

ABB
ABB VD4 Series Manuale utente

ABB
ABB SACE Emax 2 Manuale

ABB
ABB T&B Tools TBM12PCR-LI Manuale utente

ABB
ABB ACS560 Manuale utente

ABB
ABB GSec/T1 Manuale di programmazione

ABB
ABB SF6 Manuale utente

ABB
ABB Thomas&Betts BAT22-6NV2 Manuale utente

ABB
ABB B-CK 240 Manuale utente

ABB
ABB REX 521 Manuale utente

ABB
ABB AMVAC Guida rapida