ABLELink ABLELink MB5000 Series Manuale utente

ABLELink®
Modbus Gateway
MB5000 Series
User’s Manual
Version 1.1
Updated in March, 2010
TEL: 886-3-5508137
FAX: 886-3-5508131
http://www.atop.com.tw

User manual Version 1.0
Modbus Gateway
Table of Contents
Table of Contents...................................................................................................................................... 2
Introduction .............................................................................................................................................. 4
Features .................................................................................................................................................... 5
Specifications ........................................................................................................................................... 6
Hardware Diagram.................................................................................................................................... 7
Diagram.................................................................................................................................................7
2-Port Hardware Diagram................................................................................................................... 7
4-Port Hardware Diagram................................................................................................................... 7
Pin Definitions ......................................................................................................................................8
Power Pin Definitions ......................................................................................................................... 8
2-Port Power Pin Definitions (DC)...................................................................................................8
Ethernet Port Pin Definitions (RJ45) ................................................................................................... 8
Serial Port Pin Definitions................................................................................................................... 9
2-Port and 4-Port Pin Definitions (DB9) .......................................................................................... 9
Configuration and Management............................................................................................................. 10
Connecting to the Setup Page ........................................................................................................... 10
System information............................................................................................................................ 11
Login ................................................................................................................................................... 12
Port information.................................................................................................................................. 13
Port overview ................................................................................................................................... 13
Port .................................................................................................................................................. 14
Parameter .................................................................................................................................... 14
Serial Device Mode...................................................................................................................... 15
Miscellaneous..................................................................................................................................... 20
Basic settings................................................................................................................................... 20
Advance settings.............................................................................................................................. 21
Log setting ................................................................................................................................... 21
Maintenance ................................................................................................................................ 21
Network Settings ................................................................................................................................ 23
Log ...................................................................................................................................................... 24
System log ....................................................................................................................................... 24
Communication log........................................................................................................................... 24
Warm Start .......................................................................................................................................... 27
Reboot................................................................................................................................................. 28

User manual Version 1.0
Modbus Gateway
Configuration Examples......................................................................................................................... 29
Example 1: Serial Port to Slave Device ............................................................................................. 29
Port1 settings: .................................................................................................................................. 29
Configure the port parameters: ..................................................................................................... 29
Port1 “Serial Device Mode” setup................................................................................................. 30
Port2 settings: .................................................................................................................................. 31
Configure the port parameters: ..................................................................................................... 31
Port2 “Serial Device Mode” setup................................................................................................. 32
Example 2: Serial Port to Master Device ........................................................................................... 33
Port1 settings: .................................................................................................................................. 34
Configure the port parameters: ..................................................................................................... 34
Port1 “Serial Device Mode” setup................................................................................................. 34
Port2 “Serial Device Mode” setup................................................................................................. 35
Example 3: Modbus Gateway to Modbus Gateway Direct Link........................................................ 36

User manual Version 1.0
Modbus Gateway
Introduction
Modbus is an industry adopted communication protocol based on RTU, ASCII, and TCP protocols for various
applications; these three protocols are commonly used by hardware equipments in the industry, such as
DCS, PLC, HMI, power load measurement, various sensor and measuring instruments. The Modbus
Gateway is capable of implementing the Modbus environment between different hardware interfaces,
thereby streamlining the process of management and application.
Diverse Hardware Infrastructure
Modbus Gateway supports the four most commonly used hardware communication interfaces, RS232,
RS485, RS422, and Ethernet. The simple-to-use configuration software provided with Modbus Gateway can
quickly modify the hardware interface to use, and easily switch to the existing hardware communication
infrastructure.
Switching between Modbus Protocols
Modbus Gateway supports the standard Modbus protocol and is capable of converting any Modbus
protocols between Modbus TCP, Modbus RTU, and Modbus ASCII for all supported hardware interfaces, not
just limited to converting Modbus TCP into Modbus RTU/ASCII.
Modbus ID Routing
Modbus Gateway is not only capable of hardware and protocol conversions, and when a Modbus ID conflict
occurs the Modbus Gateway also supports ID routing to the existing Modbus hardware.
Modbus Gateway, Simple Integration for Complex Configurations
Modbus Gateway supports various types of hardware communication interfaces, Modbus protocol
conversion, and Modbus ID routing. Therefore the Modbus Gateway can integrate your existing and complex
Modbus hardware configuration into a simple network that can be easily managed.

User manual Version 1.0
Modbus Gateway
Features
Supports the four most commonly used hardware communication interfaces in the industry, RS232,
RS485, RS422, and Ethernet.
Easy-to-use webpage setup for RS232, RS485, RS422.
Effortlessly convert between Modbus TCP, Modbus RTU, and Modbus ASCII.
Hardware connections through serial and Ethernet ports for even easier integration.
No software installations necessary; simply setup configurations through the Internet browser (e.g.
Internet Explorer).
Provides up to 16 ports for connectivity.
Provides 2 Ethernet interfaces.

User manual Version 1.0
Modbus Gateway
Specifications
Specifications
Model MB5302 (2-Port) MB5404 (4-Port)
System
CPU RISC 150MHZ Processor with
MMU
32-bit 266MHz RISC Processor
with MMU
Flash 16M Bytes 32M Bytes
RAM 64M Bytes 128 M Bytes DDR
EEPROM 2K Bytes 8K Bytes
Watchdog Hardware & Software built-in
Ethernet
Compliance IEEE802.3
Port 2-port
Transmission
Rate
10/100M Auto-detection
Connector RJ-45
Auto MDI/MDI-X No
Serial
Interface RS232/422/485 software selectable
Ports 2-port 4-port
Baud Rate 110bps-921Kbps
Parity None, Odd, Even, Mark, Space
Data Bits 5, 6, 7, 8
Stop Bits 1, 2
Flow Control None, Software: Xon/Xoff, Hardware: RTS/CTS
Protection 15KV ESD 15KV ESD
Connector 9-pin D-Sub 9-pin D-Sub
Power
Input DC 9 - 30V
Consumption Max. 6W Max. 8.5W
Approval
EMC FCC Class A, CE Class A
Environment
Operating 0°C-60°C( 32º-140ºF ) 0°C-60°C ( 32º-140ºF )
Storage -40º-85ºC ( -40º-185ºF ),
5 - 95%RH
-40º-85ºC ( -40º-185ºF ),
5 - 95%RH
Dimension
W x H x D (mm) 99 x 35 x 108.5 197 x 37 x 112
Software
Configuration Web page
Support protocol TCP/IP, HTTP, Telnet, Modbus
Option Accessories
Power Adapter US315(US / EU)
AC100-240V / DC12V 1.25A ;
3 pins 5.08mm terminal block,
1A25F (US / EU):
AC100-240V / DC12V 1.25A ;
DC Jack lockable

User manual Version 1.0
Modbus Gateway
Hardware Diagram
Diagram
2-Port Hardware Diagram
4-Port Hardware Diagram

User manual Version 1.0
Modbus Gateway
Pin Definitions
Power Pin Definitions
2-Port Power Pin Definitions (DC)
DC 9V - DC 30V
Ethernet Port Pin Definitions (RJ45)
Pin Signal
1 TX+
2 TX-
3 RX+
4
5
6 RX-
7
8

User manual Version 1.0
Modbus Gateway
Serial Port Pin Definitions
2-Port and 4-Port Pin Definitions (DB9)
RS-232 RS-422 RS-485
Pin Signal Pin Signal Pin Signal
1 DCD 1 NC 1 NC
2 RXD 2 TXDB (+)
2 NC
3 TXD 3 RXDB(+)
3 DataB (+)
4 DTR 4 NC 4 NC
5 GND 5 GND 5 GND
6 DSR 6 NC 6 NC
7 RTS 7 RXDA (-)
7 DataA (-)
8 CTS 8 TXDA (-)
8 NC
9 NC 9 NC 9 NC

User manual Version 1.0
Modbus Gateway
Configuration and Management
Connecting to the Setup Page
There are two methods of connecting to the Modbus Gateway Configuration and Management webpage:
The first method is to use the included software tool (Devicevw.EXE) and directly select the IP address then
Click the “Browser” button. The software tool will use the default browser to open the setup page.
The second method is to launch the browser and then enter the IP address of the Modbus Gateway in the
address bar, e.g. http://192.168.50.100
The System Information page will be displayed after connecting to the Modbus Gateway homepage. Please
refer to the following for detailed descriptions of each page.
Indice
Manuali Portale popolari di altre marche

LST
LST M500RFE-AS Manuale utente

Kinnex
Kinnex Media Gateway Manuale utente

2N Telekomunikace
2N Telekomunikace 2N StarGate Manuale utente

Mitsubishi Heavy Industries
Mitsubishi Heavy Industries Superlink SC-WBGW256 Manuale utente

ZyXEL Communications
ZyXEL Communications ZYWALL2 ET 2WE Manuale utente

Telsey
Telsey CPVA 500 - SIP Manuale utente