Acrel ARD2M Manuale utente

472
ARD2M
Motor Protector Operating
Manual V1.1
ACREL Co., Ltd

Declaration
All rights reserved. Without the written permission of the Company, the contents
of any paragraph or section in this manual shall not be copied, copied or disseminated
in any form. Otherwise, all consequences shall be borne by the violator.
Our company reserves all legal rights.
Our company reserves the right to modify the product specifications described in
this manual without prior notice. Before placing an order, please consult your local
agent for new specifications of this product.

Catalog
1 Overview...................................................................................................1
2 Product Features....................................................................................... 1
3 Model Description.................................................................................... 2
4 Main parameters....................................................................................... 3
5 Overall dimensions and installation......................................................... 5
6 Protection function description.................................................................9
7 Function setting and description.............................................................24
8 Communication Settings and instructions..............................................37
9 Features and Functions........................................................................... 69
10 Examples of ordering............................................................................70

-
1
-
1 Overview
The ARD2M motor protector (hereinafter referred to as the protector) is suitable for
low-voltage motor circuits with rated voltage up to 380V and integrates protection, measurement,
control, communication, operation and maintenance.Its perfect protection function ensures the
safe operation of the motor, with logic programmable function, can meet a variety of control
methods.
The product adopts split structure, which is composed of main body, panel, mutual inductor
and optional communication module, and can adapt to the installation of various cabinets.
Product Implementation standards:
——GB 14048.4-2020 Low-voltage switchgear and control gear -- Part 4-1: Contactors and
motor starters -- Electromechanical contactors and motor starters (including motor protectors);
——JB/T 10736-2007 Low voltage motor protector.
2 Product Features
■ Support fundamental and full-wave power parameter measurement (U, I, P, Q, S, PF, F, EP,
EQ), voltage and current imbalance degree, voltage and current positive sequence, negative
sequence, zero sequence component, three-phase voltage phase Angle, residual current.
■ Protection functions include overload inverse time, overload definite time, grounding, starting
timeout, leakage, underload, locked-rotor, obstruction, short circuit, phase, overflow, imbalance
(current, voltage, power, less power, over voltage, under voltage, phase sequence, temperature,
external fault, tE time, running time alarm, fault alarm.
■ 8 channels programmable DI input, the default use of DC24V power supply, or external active
wet contact can be selected (see the selection table).
■ 5 programmable DO output, to meet the direct starting, star - triangle starting,
auto-transformer starting, and other starting modes, can be through the communication bus to
achieve the master station to the motor remote control "start/stop".
■ Optional anti-shaking function: support immediate restart of shaking power and restart of
voltage loss.
■ MODBUS_RTU and PROFIBUS DPV1 communication modules are available for selection.2
MODBUS_RTU communication channels or MODBUS_RTU+PROFIBUS DPV1
communication modules can be chosen.
■ Optional 1 channels DC4-20MA analog output interface, connected with DCS system, can
realize the monitoring of field equipment.
■ With fault record, start record, stop record, DI displacement record, restart record and other
records of various events, you can view a number of motor operation and maintenance
information.
■ The display interface supports Chinese/English LIQUID crystal display

-
2
-
3 Model Description
ARD 2 M /
Display module (Table 2)
Current Specification(Table 1)
Design serial number
Enterprise code
The corresponding relation between ARD2M current specification and the rated current and
power of the applicable motor is shown in Table 1:
Table 1
Protector
current
specification
(A)
Ratio
setting
Primary side coil
number of
transformer
Applicable scope of
motor (kW)
Suitable for motor
Rated current range
(A)
1Support 5circle 0.12-999 0.1-5000
5 1cirlce 0.12-999 0.5-5000
25
Does not
support
1cirlce 3-11 6.3-25
100 1circle 15-45 25-100
250 1circle 55-132 63-250
800 1circle 160-250 250-800
Additional function of ARD2M are shown in Table 2:
Table 2
Additional function code Additional function code
Energy metering Ep SOE Event record SR
4-20mA analog output M 1channel Modbus-RTU
communication C
Anti - electric shock
function SU Temperature protection T
Leakage protection L 1channel Profibus-DP
communication CP
Remarks:
(1)Integrated current transformer is used for integrated protector with current specification of
100A and below;The split current transformer is used for the current specification of 100A and
below;
250A and 800A current specifications use another type of split current transformer. For the
external dimensions of the transformer, please refer to the "external dimensions and installation".
(2)The temperature measurement support sensor type is PTC or NTC or PT100.

-
3
-
(3)After the leakage function (L) is selected, each protector is equipped with a leakage transformer.
The dimensions of the leakage transformer are shown in the section "overall dimensions and
installation". Leakage transformer is equipped with 2m ±10cm secondary line as standard. If
you need other length, please contact the manufacturer.
4 Main parameters
4.1 Technical indicators
ARD2M technical indicators are shown in Table 3:
Table 3
Technical parameters Technical indicators
Protector auxiliary
power supply AC85-265V/DC100-350V
Rated working voltage
of the motor AC220V / 380V,50Hz / 60Hz
Rated operation current
of the motor
1 (0.1A-5000A)
Integrated/Split current transformer
5 (0.1A-5000A)
25(6.3A-25A)
100(25A-100A)
250(63A-250A) Split current transformer
800(250A-800A)
Relay output contact
capacity Impedance load AC250V、10A
Switching input 8 channels of passive dry contact (active DC110V, DC220V, AC220V
input can be optional)
Communication RS485 Modbus_RTU,Profibus_DP
Environment
Working temperature -10ºC~55ºC
Storage temperature -25ºC~70ºC
Relative temperature ≤95 ﹪No condensation, no corrosive
gas
Altitude ≤2000m
Pollution levels 3 level
Protection grade IP65(installed on the cabinet panel)
Installation category III 级
4.2 Functional configuration
ARD2M Functional configuration shown in Table 4:
Table 4
Type
Function
Functional configuration
Standard
function Optional function
Protection
function
Fixed time overload √
Inverse time overload √

-
4
-
Starting timeout √
Phase loss √
Voltage unbalance √
Current unbalance √
Locked-Rotor √
underload √
External fault √
Block √
Temperature protection(PTC/NTC) √
Residual current(One
only)
grounding √
leakage √(leakage)
Phase sequence √
Under voltage √
Over voltage √
Under power √
Over power √
Te time protection √
Overflow protection √
Alarm of starting times √
Running time alarm √
Fault frequency alarm √
Control
mode
Protection mode √
Direct start mode
√Two-step mode
Two-speed mode
Voltage loss restart √
Communica
tion
function
1 channel Modbus-RTU
communication √
1 channel Profibus-DP communication √
Switching
input 8 channel DI √
Relay
output 5 channel DO √
Analog
output 1 channel DC4-20mA √
Event
record
Start record, stop record, DI
displacement record, restart record,
(support communication transmission)
√

-
5
-
5 Overall dimensions and installation
5.1 Composition
The product composition of ARD2M is shown in Figure 1, Figure 2:
Figure1 The composition of integrated protector
Figure2 The composition of split protector
5.2 Panel size and opening(Unit:mm)
The shape and opening size are shown in Figure3,4::
Front view Side view
vertical view
Figure 3 Panel size of integrated protector ARD2M

-
6
-
4
Ua
5
Ub
6
Uc
3
Un
35
AO+
36
AO-
32
T1
33
T2
34
T3
41 43
Ia
44
Ib
45
Ic
2
N
1
L
94 96
D05
95 97
D04
98 11 12 9 10 7 8
D03 D02 D01
14
DI1
15 16 17 18 19 20 21 23 28
A2
29
B2
30 25
A1
26
B1DI2 DI3 DI4 DI5 DI6 DI7 DI8
27
Front view Side view
Vertical view Hole size
Figure 4 Panel size of split protector ARD2M
5.3 Size of installation of current transformer(unit:mm)
5.3.1 The external dimensions of Integrated/split current transformer(100A and below current
specification)are shown in figure 5(Unit:mm):
Figure 5 The external dimensions of Integrated/split current transformer(100A and below current
specification)

-
7
-
5.3.2 The external dimensions of split current transformer(250A and 800Acurrent specification)are
shown in figure 6(Unit:mm):
Figure 6 The external dimensions of split current transformer(250A and 800Acurrent
specification)
5.3.3The external dimensions of leakage current transformer are shown in figure 7 and table
5(Unit:mm):
Figure 7 The external dimensions of leakage current transformer
The leakage transformer is equipped with a secondary wire of 2m±10cm. If other lengths are
needed, please contact the manufacturer
Table 5
dimension
Spec.
Overall
size(mm)
Go through
size(mm) Installation size(mm) Tolerance
(mm) Weight (g)
W H D Φ M N L Φ2
L45 75 75 22 46 65 65 4.3 4 ±1 200±10