Connecting the Nim Controller and Boards.
MASTER UNIT
1. Plug the cable supplied with the Nim board into CN1 on the Nim and connect it to
CN4 on the master unit indoor pcb
2. Plug the Netware controller cable into CN2 on the Master Unit Nim board and
match the coloured wires to the corresponding coloured connections on the inside
back of the Netware controller.
Address the Master unit using the dip switches as follows:
3. Dip Switch marked DSW1 (eight switches)
LEAVE ALL SWITCHES DOWN (OFF)
4. Dip Switch Marked DSW2 (four switches)
LEAVE ALL SWITCHES DOWN (OFF)
This unit is now addressed as the master unit.
SLAVE UNIT
5. Plug the cable supplied with the Nim board into CN1 on the Nim and connect it to
CN4 on the slave unit indoor pcb
Address the Slave unit as follows:
6. Dip Switch marked DSW1 (eight switches)
LEAVE ALL SWITCHES DOWN (OFF)
7. Dip Switch marked DSW2 (four switches)
LEAVE SWITCH 1 / 2 / 3 SET DOWN (OFF)
MOVE SWITCH 4 UP (ON)
This unit is now addressed as the slave unit number 1
Connect the Nim Boards together as follows:
8. Connect a two core cable of about .75mm to CN3 on the Master unit Nim
board (connector is on top right of board) and note which cable plugs in to A
and which in to B as the connection has polarity.
9. Run the cable to the Slave unit Nim board and connect it in the same way.
MAKE SURE THAT THE CABLES ARE IN THE SAME CONNECTIONS
AS IN THE MASTER UNIT NIM BOARD.
The Nim Boards connection is now complete. Once power is applied the Master
unit will be controlled by the Netware controller and the Slave unit will copy the
function of the Master unit.