ActronAir REPE-01 Manuale utente

REPEATER
Operation Manual
Repeater
REPE-01
Model Number
REPE-01
IMPORTANT NOTE:
Please read this manual carefully before installing
or operating your air conditioning unit.


Contents
Operating
Instructions
Installation
Instructions
Main Parameters 01
Product Overview 02
Descriptions on Indicators 03
Precautions
Package Contents 05
Repeater Installation 06
Power Cable Connection 08
Communication Wire Connection 10
04
Precautions 01

01
Main Parameters
Operating Instructions
Precautions
●
●
●
●
●
Name
Rated Voltage
Operating environment temperature
Operating environment humidity
216-253V~50HZ
REPE-01
-5℃~43℃
≤RH90%
Entrust a qualified local technician to perform installation. Do not try to install the unit
by yourself.
Before cleaning or maintenance, ensure the power supply is cut off. Do not use water
for washing to prevent electric shocks.
Do not operate with wet hands to avoid electric shocks.
Do not use pesticides, disinfectants, or flammable directly on the controller as they
may damage the device or cause fires.
When the IDUs are powered separately and the number of IDUs to be connected is
more than 10 or the communication distance is larger than 200, repeaters are
required.

02
Repeater
REPE-01
Product Overview
A repeater is a connector working on the physical layer, with the following features:
●Signal repeater: re-transmits or forwards data signals to extend the network
transmission distance.
●Power supply repeater: compensates the voltage drop caused by communication
wire resistance to increase the bus voltage.

03
Communication indicator
(yellow)
Power indicator (green)
Communication indicator (blue)
Short circuit indicator (red)
Descriptions on Indicators
Repeater
REPE-01
Indicator Normal Abnormal
Communication indicator
Communication indicator
Short circuit indicator
Power indicator
Blinking
Blinking
On
Off
Remarks
On/off
On/off
On
Off Abnormal power supply for the main board
Short circuit of communication bus
downstream the repeater
Abnormal communication
Abnormal communication

04
Installation Instructions
Warning
Precautions
●To ensure correct installation, read the "Installation Instructions" section of this manual.
●All the warnings provided here are important for safety and must be followed.
●Entrust the local distributor or local service agent to appoint a qualified technician to
perform the installation. Do not try to install the unit by yourself.
●Do not connect the communication wire when the power is on. Otherwise, the circuit
board will be damaged.
●Do not connect the power cable (high voltage) to the communication (low voltage)
terminal. Otherwise, the circuit board will be damaged.
●Do not connect M1M2 with the PQ of IDU. Otherwise, the circuit board will be
damaged.
●Note the distinction between the communication port of the upstream IDU and that of
the downstream IDU. Be careful not to make them confused. Otherwise,
communication failure will occur.
●Use the specified cables as the communication wires.The wires should be fixed with
clamps to avoid stress on the terminal block.
●Do not install the repeater in any corrosive, flammable or explosive environment or
place with oil mist (such as a kitchen).
●Do not install the repeater outdoor or in a wet place and avoid direct sunlight.
●Do not knock, throw, or disassemble the wired controller.
●Please install the repeater after painting the wall to prevent water, lime and sand
from entering the repeater.
●When installing the equipment, all requirements of the mentioned standard must be
fulfilled. And when necessary, suitable enclosure and type of supply connection
should be provided by end system.

Product List
The below items are included when ordering the repeater:
05
No. Description Quantity Remarks
1 REPE-01 repeater 1 Used to increase bus voltage
2
Installation and Operation Manual
1
Providing instructions on
repeater installation
3 4 Used to fix the pedestalPhilips head screw
4 Used to fix the pedestal4White plastic expansion pipe
5Crimp clamp 4 Used to fix the wire
6Cross recessed pan head
tapping screw (3.9x10) 8Used to fix the crimp clamp
7Cross recessed pan head
tapping screw (2.9x8) 2Used to fix the box cover and
pedestal after installing

06
Repeater Installation
Ⅰ. Push the cover hard on the screwdriver icon till snap fasteners of the
cover seperate from the base, then open the cover. Install the power cables
and communications wires properly according to the wiring diagram.
Make sure the power is off when operating.
Do not raise the upper cover with excessive force to avoid damage to the
cover or the circuit board.
Warning
Snap fastener

Ⅱ. Fix the repeater base on the wall or a proper location with a screwdriver.
Four positions need to be fixed with screws.
07
Ⅲ. Finally, close the upper cover and the bottom cap of the repeater and
tighten them with two fixing screws.
Location to
accept a screw
Fixing screw
Make sure that no cables are clamped when buckling the upper cover and bottom cap
of the repeater.
●
Warning
Indice