ADF Web HD67302-B2 Series Manuale utente

Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com hone +39.0438.30.91.31
User Manual
GSM I/O and Alarms Modem
Document code: MN67302_ENG Revision 1 100 Page 1 of 35
User Manual
Revision 1 100
English
GSM I/O and Alarms Modem
for Website information:
www adfweb com?Product=HD67302
for Price information:
www adfweb com?Price=HD67302-B2-02
www adfweb com?Price=HD67302-B2-20
www adfweb com?Price=HD67302-B2-11
Benefits and Main Features:
Very easy to configure
SMS / Call to get/trigger an input/output
Wide power input range
Temperature range: -20°C / +70°C (-4°F / +158°F)
Analyzer / Scanner /Sniffer, M-Bus
www adfweb com?Product=HD67031
Multi-Drop onverter RS232/RS485 to Optic Fiber
www adfweb com?Product=HD67033M
(RS232, SL)
www adfweb com?Product=HD67034M
(RS232, DL)
www adfweb com?Product=HD67035M
(RS485, SL)
www adfweb com?Product=HD67036M
(RS485, DL)
Isolator & Repeater, RS485
www adfweb com?Product=HD67149-A1
AN, ANopen, J1939, DeviceNet, NMEA2000 Analyzer
www adfweb com?Product=HD67316
AN, ANopen, J1939, DeviceNet, NMEA2000 from/to USB
www adfweb com?Product=HD67390
Do you have an your customer protocol?
See the following links:
www adfweb com?Product=HD67003
Do you need to choose a device? do you want help?
Ask it to the following link:
www adfweb com?Cmd=helpme
HD67302
-
B2
-
xx
User Manual

Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com hone +39.0438.30.91.31
User Manual
GSM I/O and Alarms Modem
Document code: MN67302_ENG Revision 1 100 Page 2 of 35
INDEX:
Page
INDEX 2
UPDATED DOCUMENTATION 2
REVISION LIST 2
WARNING 2
TRADEMARKS 2
SECURITY ALERT 3
EXAMPLE OF CONNECTION 4
CONNECTION SCHEME 5
CHARACTERISTICS 6
CONFIGURATION 6
POWER SUPPLY 7
FUNCTION MODES 8
LEDS 9
GSM 10
DIGITAL INPUT 11
DIGITAL OUTPUT 13
ANALOG INPUT 14
USB 15
USE OF COMPOSITOR SW67302 16
NEW CONFIGURATION 17
LOAD CONFIGURATION 18
DEVICE SETTING 19
INPUT SETTING 20
OUTPUT SETTING 22
PROFILES 26
DATE TIME SETTING 28
UPDATE DEVICE 29
SOFTWARE PREFERENCES 31
MECHANICAL DIMENSIONS 32
ORDERING INFORMATIONS 33
DISCLAIMER 34
OTHER REGULATIONS AND STANDARDS 34
WARRANTIES AND TECHNICAL SUPPORT 35
RETURN POLICY 35
UPDATED DO UMENTATION:
Dear customer, we thank you for your attention and we remind you
that you need to check that the following document is:
Updated
Related to the product you own
To obtain the most recently updated document, note the “document
code” that appears at the top right-hand corner of each page of this
document
With this “Document Code” go to web page
www adfweb com/download/ and search for the corresponding code on
the page Click on the proper “Document Code” and download the
updates
REVISION LIST:
WARNING:
ADFweb com reserves the right to change information in this manual
about our product without warning
ADFweb com is not responsible for any error this manual may contain
TRADEMARKS:
All trademarks mentioned in this document belong to their respective
owners
Revision
Date Author hapter
Description
0 900 26/05/2011
Fl All First Release
1 000 03/09/2012
Fl All Software changed (v1 008)
1 001 08/02/2013
Nt All Added new chapters
1 100 15/06/2017
Ff All New hardware version

Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com hone +39.0438.30.91.31
User Manual
GSM I/O and Alarms Modem
Document code: MN67302_ENG Revision 1 100 Page 3 of 35
SE URITY ALERT:
G
ENERAL
I
NFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual When using the device, legal and
safety regulation are required for each individual application The same applies also when using accessories
I
NTENDED
U
SE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i e
independent limit switches, mechanical interlocks, etc )
Q
UALIFIED
P
ERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and
who have appropriate qualifications for their job
R
ESIDUAL
R
ISKS
The device is state-of-the-art and is safe The instruments can represent a potential hazard if they are inappropriately installed and
operated by untrained personnel These instructions refer to residual risks with the following symbol:
This symbol indicates that non-observance of the safety instructions is a danger for people that could lead to serious injury or
death and / or the possibility of damage
E
ONFORMITY
The declaration is made by our company You can send an email to support@adfweb com or give us a call if you need it

Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com hone +39.0438.30.91.31
User Manual
GSM I/O and Alarms Modem
Document code: MN67302_ENG Revision 1 100 Page 4 of 35
EXAMPLE OF ONNE TION:

Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com hone +39.0438.30.91.31
User Manual
GSM I/O and Alarms Modem
Document code: MN67302_ENG Revision 1 100 Page 5 of 35
ONNE TION S HEME:
Figure 1: Connection scheme for HD67302-B2-xx

Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com hone +39.0438.30.91.31
User Manual
GSM I/O and Alarms Modem
Document code: MN67302_ENG Revision 1 100 Page 6 of 35
HARA TERISTI S:
The GSM I/O and Alarms Modem is a powerful, flexible and economic instrument which is used to control Digital and Analog I/O by SMS or
Phone Call
It allows the following characteristics:
2 Digital Output (standard version);
2 Digital Input (standard version);
1 Analog Input (standard version);
SMS alert for state’s changing of the Digital/Analog Input;
Setting Output via SMS and/or call;
Mountable on 35mm Rail DIN;
Power Supply 8…24V AC or 12…35V DC;
Temperature range -20°C / +70°C (-4°F / +158°F)
ONFIGURATION:
You need Compositor SW67302 software on your PC in order to perform the following:
Define the Digital Input settings;
Define the Analog Input settings;
Define the Digital Output settings;
Set Date and Time;
Update the device

Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com hone +39.0438.30.91.31
User Manual
GSM I/O and Alarms Modem
Document code: MN67302_ENG Revision 1 100 Page 7 of 35
POWER SUPPLY:
The devices can be powered at 8…24V AC and 12…35V DC The consumption depends to the code of the device For more details see the two
tables below
VA
VD
Vmin Vmax Vmin Vmax
8V 24V 12V 35V
Consumption at 24V DC:
Device [W/VA]
HD67302-B2-xx 3 5
HD67302-B2-xx
aution: Not reverse the polarity power

Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com hone +39.0438.30.91.31
User Manual
GSM I/O and Alarms Modem
Document code: MN67302_ENG Revision 1 100 Page 8 of 35
FUN TION MODES:
The device has got two functions mode depending of the position of the ‘Dip1 of Dip-Switch A’:
The first, with ‘Dip1 of Dip-Switch A’ at “OFF” position, is used for the normal working of the device;
The second, with ‘Dip1 of Dip-Switch A’ at “ON” position, is used for uploading the Project and/or Firmware
For the operations to follow for the updating, see ‘UPDATE DEVICE’ section
According to the functioning mode, the LEDs will have specifics functions, see ‘LEDS’ section
Warning:
Dip2 of ‘Dip-Switch A’ must be at ON position to work even if the Ethernet cable isn’t inserted

Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com hone +39.0438.30.91.31
User Manual
GSM I/O and Alarms Modem
Document code: MN67302_ENG Revision 1 100 Page 9 of 35
LEDS:
The device has got four LEDs that are used to give information of the functioning status
The various meanings of the LEDs are described in the table below
LED Normal Mode Boot Mode
1: Device state (green) Blinks slowly (~1Hz)
Blinks quickly: Boot state
Blinks very slowly (~0.5Hz): update in progress
2:GSM module comm
(yellow)
Blinks quickly the GSM module is
communicating
Blinks quickly: Boot state
Blinks very slowly (~0.5Hz): update in progress
3: USB comm (yellow) Blinks quickly when USB messages
are received
Blinks quickly: Boot state
Blinks very slowly (~0.5Hz): update in progress
4: GSM comm error
(yellow)
OFF: GSM connected
ON: GSM not connected
Blinks quickly: Boot state
Blinks very slowly (~0.5Hz): update in progress

Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com hone +39.0438.30.91.31
User Manual
GSM I/O and Alarms Modem
Document code: MN67302_ENG Revision 1 100 Page 10 of 35
GSM:
The HD67302 uses a Quad-band GSM/GPRS module and allows to send/receive SMS and
phone call
The Antenna connector is a SMA Female (‘Female Outer Shell’ and ‘Female Receptacle’) so
the Antenna must have a SMA Male connector
The SIM type is Micro-Sim
Altri manuali per HD67302-B2 Series
1
Questo manuale è adatto per i seguenti modelli
3
Indice
Altri manuali ADF Web Modem


















