Airflow MultiPlexBox ECO Manuale utente

80001028 –Issue 1 11/20
MultiPlexBox ECO Controller
Part No: 90001253
Manual on the correct usage, maintenance, and
installation of the MultiPlexBox ECO controller

2
Contents
Contents
Contents.........................................................................................................................................................2
1.0 General Information.................................................................................................................................. 3
2.0 Installation.................................................................................................................................................5

3
1. General Information
To ensure complete and effective operation, and for your own safety, all the following instructions should be
read carefully and observed. The relevant national standards, safety regulations, instructions and actions
required by law as well as the technical connection conditions of the energy supply company must be
observed and applied. Keep the Installation and Operating Instructions as a reference. After the final
assembly, the document must be handed out to the operator (tenant/owner).
1.2 Warranty and Liability claims
To safeguard the guarantee and liability claims of the customer, the following must be observed:
Implementation according to “unit” Installation and Operating Instructions. The use of accessories, which are
not approved, recommended, or offered by Airflow Developments, is not permissible. Any damages are
excluded from the guarantee. If these instructions are not observed, all warranty claims are excluded. This
also applies to any liability claims extended to the manufacturer.
1.3 Regulations - Guideline
If the product is installed correctly and used to its intended purpose, it conforms to all applicable regulations
including UKCA and CE guidelines at its date of manufacture.
1.4 Receipt
Please check delivery immediately on receipt for accuracy and damage. If damaged, please notify the carrier
immediately. In case of delayed notification, any possible claim may be void.
1.5 Storage
When storing for a prolonged time, the following steps are to be taken to avoid damaging influences:
Protection by dry, air-dustproof packing (plastic bags with drying agent and moisture indicators). The storage
place must be waterproof, vibration-free, and free of temperature variations. Damages due to improper
transportation, storage or commissioning must be verified and are not liable for warranty.
1.6 Intended use
The control element is intended for controlling the MultiPlexBox. It is not a ready-to-use product and it may
only be operated once the ventilation system has been properly installed and connected. The controller is
designed for flush mounting in an empty socket with a diameter of 68mm. Any use other than the intended
use is prohibited.
1.7 Disposal
An authorised specialist waste processing company must dispose of the unit or the individual components.
The appointed contractor must ensure that:
–The components are separated according to material types.
–The used operating materials are sorted and separated according to their respective properties.
1.1 Warning: Safety instructions will be presented in a box such as this. All information must
be followed and adhered to. To not do so will or could result in a dangerous situation.

4
1.8 Functions
The following functions of the unit can be set using the control element:
•Automatic Operation
•Manual Operation
•Ventilation Stage 1-3
•Basic Ventilation
•Off
Automatic Operation (Only possible with optional sensors)
When the A button is pressed, automatic operation of the unit is activated and displayed by the lit-up LED
next to the A button. The ventilation stages are automatically controlled based on the air quality.
The ventilation stages LEDs display the selected ventilation level setting (level 1, level 2, level 3). This can
be manipulated by pressing the up and down arrow buttons. After a short time of inactivity, the LEDs are
turned off. Display them again by briefly pressing the arrow buttons.
Manual Operation
Manual operation is activated by pressing the M button and displayed by the LED next to the button. The
ventilation unit is in manual operation now. The individual ventilation levels can be changed and set with the
arrow buttons on the right of the LEDs. The LEDs display the selected ventilation level. If ventilation level 1 is
flashing, basic ventilation is selected. If the down button is pressed until none of the three LEDs are lit up or
flashing, the unit is deactivated (only possible when basic ventilation is deactivated).
Basic ventilation
If ventilation level 1 is flashing, basic ventilation is active. Basic ventilation ensures a minimum air flow which
serves as moisture protection.
OFF (only possible when basic ventilation is deactivated)
When “Off”mode is selected, the unit’s dampers will be closed and the air discharge/supply to the service
unit will be interrupted.
Error Message
The error message shall be displayed in case of a unit operating error by lighting up the LED. If an error
message is displayed, promptly inform the relevant persons or seek advice from your point of sale contact.

5
Error List
The errors you may encounter are listed below:
Error
Number
Flash Code
Description
0
-
No Error
1
2x flashing,
pause
Error system memory. Unable to load Parameter data.
3
6x flashing,
pause
Error communication internal sensor. Unable to set up communication with
configured sensor
4
8x flashing,
pause
Error communication. Unable to set up communication between
MultiPlexBox and ECO controller.
2. Installation
2.0 Technical Data
ECO controller for flush-mounted installation
Voltage: 12 V
Operating stages: 4 (ventilation level 1-3, basic ventilation/off)
Control line: J-Y(St) 2 x 2 x 0.6
Protection rating: IP20
Dim. (W x H x D) mm: 80 x 80 x 10
Ambient temperature / humidity: 0-55°C <95% RH (none condensing)
Weight: 54g
2.1 Wiring Diagram
Connect the controller following the below wiring diagram 1. The location of connection is on the Box.
Warning!Danger to life due to electric shock, the electrical connection and maintenance, as
well as installation work, must only be carried out by a qualified electrician with proper legal
authorisation to do so.
Diagram 1: Wiring of ECO controller

6
Location reference
Use this diagram to refer to what port to use and where it is located on the box if you have difficulty finding it.
A. Mains Voltage (230 V AC)
B. Switching contact (potential-free max. 5 A)
C. Modbus A
D. Modbus B
E. Control unit
F. USB (PC connection)
Diagram 2: Location of connection on the MultiPlexBox

7
Airflow Developments Limited
Aidelle House, Lancaster Road
Cressex Business Park, High Wycombe
Buckinghamshire, HP12 3QP, UK
Email: info@airflow.com
Telephone: +44(0)1494 525252
Facsimile: +44(0)1494 461073
©Copyright 2016. Airflow Developments Ltd
Questo manuale è adatto per i seguenti modelli
1
Indice
Altri manuali Airflow Controllori