Akytec MV210-212 Manuale utente

MV210-212/214_3-EN-59115-1.8
© All rights reserved
Subject to technical changes and misprints
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
MV210-212/214
Digital input module
User guide

1
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
Contents
Warning notice system ............................................................................................................3
Abbreviations ..........................................................................................................................4
Safety.......................................................................................................................................5
Introduction .............................................................................................................................6
1 Overview.............................................................................................................................7
2 Specifications.....................................................................................................................8
2.1 Isolation of the Device Components..............................................................................9
2.2 Environmental conditions...........................................................................................10
3 Installation........................................................................................................................ 11
4 Connection .......................................................................................................................13
4.1 Connection recommendations....................................................................................13
4.2 Connectors ...............................................................................................................13
4.3 Power supply ............................................................................................................14
4.4 Electrical connection .................................................................................................15
4.4.1 Contact sensors .................................................................................................16
4.4.2 PNP and NPN transistors....................................................................................16
4.4.3 PNP and NPN encoders .....................................................................................17
4.5 Ethernet connection ..................................................................................................17
5 Operation..........................................................................................................................19
5.1 Operation principle ....................................................................................................19
5.2 Indication and control ................................................................................................19
5.3 Real time clock..........................................................................................................20
5.4 Log file .....................................................................................................................20
5.5 Data exchange modes...............................................................................................22
5.5.1 Modbus TCP communication ..............................................................................22
5.5.2 Error codes for Modbus protocol..........................................................................32
5.6 Digital inputs operation modes ...................................................................................34
5.6.1 Logic level detection ...........................................................................................35
5.6.2 Сounting of high-frequency pulses.......................................................................35
5.6.3 Frequency measurement ....................................................................................35
5.6.4 Encoder signal processing ..................................................................................35
6 Configuration....................................................................................................................36
6.1 Connection to akYtec Tool Pro ...................................................................................36
6.2 Configuring Network Settings .....................................................................................37
6.3 Module access password...........................................................................................38
6.4 Firmware update .......................................................................................................38
6.5 Real-time clock setting...............................................................................................39
6.6 Restore default settings .............................................................................................39
6.7 Сounter reset............................................................................................................39
7 Maintenance .....................................................................................................................40
7.1 General Instructions ..................................................................................................40
7.2 Battery replacement ..................................................................................................40
8 Transportation and storage ..............................................................................................43
9 Scope of delivery..............................................................................................................44

Warning notice system
3
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
Warning notice system
Explanation of the symbols and keywords used:
WARNING
WARNING indicates a potentially dangerous situation that could result in death or serious
injuries.
CAUTION
CAUTION indicates a potentially dangerous situation that could result in minor injuries.
NOTICE
NOTICE indicates a potentially dangerous situation that could result in damage to
property.
NOTE
NOTE indicates helpful tips and recommendations, as well as information for efficient and
trouble-free operation.

Abbreviations
4
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
Abbreviations
–PC – personal computer.
–PLC – programmable logic controller.
–RTC – real time clock.
–USB – an industry standard that establishes specifications for cables, connectors
and protocols for connection, communication and power supply between personal computers and
their peripheral devices.
–UTC – coordinated universal time.

Safety
5
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
Safety
Read this manual carefully before installing, operating or servicing the device.
The device has been designed and built solely for the intended use described in this guide, and can
only be used accordingly. The technical specifications contained in this guide must be observed.
Any other use is considered improper.
CAUTION
This device must not be used for medical devices which receive, control or otherwise affect
human life or physical health.
When installing and using this product, all applicable state, federal and local regulations must be
observed.
Based on safety considerations and compliance with the data provided in the documents, the repair
of the components of the products is carried out exclusively by the manufacturer.
There is a dangerous voltage on the terminal block. Any connections to the device and maintenance
operations must be carried out only when the power of the device is turned off.
The device's method of protection against electric shock meets the terms of class II, IEC 61131-2-
2012.
The device installation must be performed in particularized equipment cabinet, the inner access to
which is allowed only to approved specialists.
CAUTION
It is forbidden to use the device in corrosive environments with acids, alkalis, oils, etc. in the
atmosphere.
Obey all the necessary rules and instructions when using programmable logic controllers in areas
where technical safety requirements apply.
Failure to obey these warnings could result in personal injury or equipment damage.
Akytec company shall not be liable for technical or editorial errors or omissions contained in this
document.

Introduction
6
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
Introduction
This document provides detailed information about the operation principle, design, configuration,
installation and maintenance of the digital input modules MV210-212 and MV210-214, hereinafter
referred to as the Device or Module.
Connection, adjustment and maintenance of the device must be carried out only by qualified
personnel after reading this operating manual.
Device designation when ordering: МV210-212 and МV210-214.

1 Overview
7
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
1 Overview
The module is designed to collect data from the built-in digital inputs and transfer them via the
Ethernet network to the PLC, panel controllers, computers or other devices.
The module has 32 digital inputs for connecting sensors or signals of the following types:
– For МV210-212: contact sensor, npn and pnp transistors.
– For МV210-214: dry contact sensor, npn transistor.
The Module is intended for use in industry and agriculture.

2 Specifications
8
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
2 Specifications
Table 2.1 Specifications
Parameter Value
Power supply
Power supply 24 (10…48) V DC
Power consumption 9 W
Protection against reverse polarity Yes
Digital input hysteresis 0.5 V
Interfaces
Data transfer interface Dual Port Ethernet 10/100 Mbit
Configuration interface USB 2.0 (MicroUSB), Ethernet 10/100 Mbit
Date transfer protocol Modbus TCP
Protocol version IPv4
Digital inputs of MV210-212
Inputs quantity 32
Signal type – contact sensor (external power supply required);
– NPN / PNP transistors
Operation modes
– logical level definition;
– counting the number of high-frequency pulses
(only DI1-DI8);
– frequency measurement (only DI1-DI8);
– encoder signal processing (up to 3 encoders)
Minimum pulse duration perceived by the
digital input (only DI1-DI8) 5 µs (up to 100 kHz)
Minimum duration of a single pulse (for
inputs DI9-DI32) 1 ms (up to 400 Hz)
Current of logical 0 1.2 mA
Current of logical 1 min. 5.5 mA
Voltage range of logical 0 0 ... 6.1 V
Voltage range of logical 1 8.8 ... 30 V
Digital inputs of MV210-214
Inputs quantity 32
Signal type – dry contact;
– NPN transistor
Operation modes – logical level detection;
– pulse count
Minimum duration of a single pulse 1 ms
Resistance of contacts (switch) and
connecting wires connected to a discrete
input, max.
100 Ω
Flash-memory (log-file)

2 Specifications
9
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
Parameter Value
Number of write and erase cycles Up to 100000
Maximum log file size 2 KB
Maximum number of log files 1000
Minimum log writing interval 10 seconds
Real time clock
Inaccuracy at +25 °C max. 3 s per day
at –40 °C and +55 °C max. 10 s per day
Battery type CR2032
Lifetime of one battery 6 years
General specifications
Dimensions 82 × 124 × 83 mm
Ingress protection rating IP20
Error-free running time* 60.000 h
Average service life time 10 years
Weight 0.4 kg
* Except real-time clock battery
2.1 Isolation of the Device Components
The circuit of galvanic isolated components and the strength of galvanic isolation are shown in
Figure 2.1.
Fig. 2.1 Isolation of the Device Components
Table 2.2 Insulation types
Type Description
Basic insulation (BI)
The insulation used for active parts of equipment to provide protection
against electric shock. The electrical strength of the basic insulation is
checked by type tests: by applying a test AC voltage, the value of which
is different for different circuits of the Device
Supplementary
insulation (SI)
Independent insulation used in addition to the basic insulation in order to
guarantee protection against electric shock in the event of a failure of the
main insulation The electrical strength of the supplementary insulation is
checked by type tests: by applying an alternating test AC voltage of
various levels (RMS value)
Questo manuale è adatto per i seguenti modelli
1
Indice
Manuali Hardware di rete popolari di altre marche

Matrix Switch Corporation
Matrix Switch Corporation MSC-HD161DEL Manuale utente

B&B Electronics
B&B Electronics ZXT9-IO-222R2 Manuale utente

Yudor
Yudor YDS-16 Manuale utente

D-Link
D-Link ShareCenter DNS-320L Manuale utente

Samsung
Samsung ES1642dc Istruzioni per l’uso

Honeywell Home
Honeywell Home LTEM-PV Istruzioni per il montaggio