8INDICATOR CONFIGURATION
The Levikos M18 is configured via the Front fascia of the
Indicator (see Figure 2.).
The installer/User shall step through the following to complete
configuration.
8.1 PRE-REQUISITES
1. System is plugged into recommended Power Supply
2. Level Sensor’s 4-20mA output is connected to
Controller’s terminals X1:1 and X1:2
3. Indicator N1500 is turned on (note indicator takes
3s to boot-up)
8.2 PARAMETER SET-UP
Provided all pre-requisites are actioned the user shall proceed
according to the steps below.
SETTING INPUT TYPE –Configuration Cycle
1. From main menu press Program and Back Key
simultaneously until the display shows
2. Move up or down the menu using the Up or Down
Key to select
SETTING INPUT LIMITS –Configuration Cycle
3. will display again after a short time. When
it does using the Program Key navigate to
& set the decimal point to desired location using Up
or Down Key
4. will display again after a short time. When
it does using the Program Key navigate to
5. Using the Up or Down Key set the lower range value
to be displayed for 4mA
6. will display again after a short time. When
it does using the Program Key navigate to
7. Using the Up or Down Key set the higher range
value to be displayed for 20mA
SETTING ALARM SET POINTS –Work Cycle
8. From main menu use the Up or Down Key navigate
to & set the desired high level alarm value
(this set point shall be within range set in
& )
9. will display again after a short time. When
it does use the Program Key to navigate to
& set the desired low level alarm value
using the Up or Down Key (this set point shall be
within range set in & )
10. will display again after a short time. When
it does use the Program Key to navigate to
& set the desired high level alarm value
using the Up or Down Key (this set point shall be
set identical to )
11. will display again after a short time. When
it does use the Program Key to navigate to
& set the desired low level alarm value
using the Up or Down Key (this set point shall be
set identical to )
SETTING ALARM FUNCTIONS –Alarm Cycle
12. From main menu press Program and Back Key
simultaneously until the display shows .
Using the Up and Down Key set the function to
13. will display again after a short time. When
it does use the Program Key to navigate to
. Using the Up and Down Key set the
function to
14. will display again after a short time. When
it does use the Program Key to navigate to
. Using the Up and Down Key & set the
function to
15. will display again after a short time. When
it does use the Program Key to navigate to
. Using the Up and Down Key & set the
function to