Amprobe TIC 300 PRO Manuale utente

TIC 300 PRO
High Energy Tic Tracer –
Non Contact
AC Voltage Detector
User Manual
07/2017, Rev005
©2017 Amprobe Test Tools.
All rights reserved. Printed in China
English
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Limited Warranty and Limitation of Liability
Your Amprobe product will be free from defects in material
and workmanship for 1 year from the date of purchase. This
warranty does not cover fuses, disposable batteries or damage
from accident, neglect, misuse, alteration, contamination, or
abnormal conditions of operation or handling. Resellers are not
authorized to extend any other warranty on Amprobe’s behalf.
To obtain service during the warranty period, return the product
with proof of purchase to an authorized Amprobe Test Tools
Service Center or to an Amprobe dealer or distributor. See Repair
Section for details. THIS WARRANTY IS YOUR ONLY REMEDY.
ALL OTHER WARRANTIES - WHETHER EXPRESS, IMPLIED OR
STAUTORY - INCLUDING IMPLIED WARRANTIES OF FITNESS FOR
A PARTICULAR PURPOSE OR MERCHANTABILITY, ARE HEREBY
DISCLAIMED. MANUFACTURER SHALL NOT BE LIABLE FOR ANY
SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES
OR LOSSES, ARISING FROM ANY CAUSE OR THEORY. Since some
states or countries do not allow the exclusion or limitation of an
implied warranty or of incidental or consequential damages, this
limitation of liability may not apply to you.
Repair
All test tools returned for warranty or non-warranty repair or
for calibration should be accompanied by the following: your
name, company’s name, address, telephone number, and proof of
purchase. Additionally, please include a brief description of the
problem or the service requested and include the test leads with
the meter. Non-warranty repair or replacement charges should be
remitted in the form of a check, a money order, credit card with
expiration date, or a purchase order made payable to Amprobe®
Test Tools.
In-Warranty Repairs and Replacement – All Countries
Please read the warranty statement and check your battery before
requesting repair. During the warranty period any defective test
tool can be returned to your Amprobe® Test Tools distributor
for an exchange for the same or like product. Please check the
distributors near you. Additionally, in the United States and
Canada In-Warranty repair and replacement units can also be sent
to a Amprobe® Test Tools Service Center (see address below).
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Non-Warranty Repairs and Replacement – US and Canada
Non-warranty repairs in the United States and Canada should be
sent to a Amprobe® Test Tools Service Center. Call Amprobe® Test
Tools or inquire at your point of purchase for current repair and
replacement rates.
In USA
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

1) Voltage sensor
2) ON/OFF Button
3) Circuit TEST button
4) HIGH range switch
5) HIGH range LED
6) LOW range switch
7) LOW range LED
8) Battery compartment
9) HOT STICK attachment point
10)
Detection Blue LED indicators
TIC 300 PRO
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

1
CONTENTS
SYMBOLS..........................................................................2
UNPACKING AND INSPECTION .......................................3
INTRODUCTION ................................................................4
Features ........................................................................4
OPERATION.......................................................................5
ON/OFF Button .............................................................5
TEST Button.................................................................. 5
Voltage Detection ........................................................ 6
LOW Range................................................................... 6
HIGH Range ..................................................................6
Locate breaks in insulated wire & heating elements
......7
Check Outlets and Switches ........................................8
MAINTENANCE AND REPAIR .......................................... 9
Cleaning........................................................................ 9
Battery Replacement ................................................... 9
SPECIFICATIONS ...............................................................10
Sensitivity: LOW Voltage .............................................11
Sensitivity: HIGH Voltage............................................. 11
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

2
SYMBOLS
�Refer to the manual
XCaution Dangerous Voltage
TDouble insulated
MSHA
United States Department of Labor
Mine Safety and Health Administration
In compliance with the United States
Department Of Labor Mine Safety and Health
Administration
Conforms to relevant Australian standards.
Conforms to relevant South Korean EMC standards.
Do not dispose of this product as unsorted
municipal waste.
For Use By Trained Personnel Only
Anyone using this instrument should be knowledgeable
and trained about the risks involved with measuring
medium and high voltage, especially in an industrial
setting, and the importance of taking safety precautions
and of testing the instrument before and after using it
to ensure that it is in good working condition.
�WARNING and PRECAUTIONS
• Use extreme caution when testing live electrical
circuits due to risk of injury from electrical shock.
• Do not exceed the maximum overload limits
(see specifications) or the limits marked on the
instrument itself. Never test voltage more than
122 kV AC RMS.
• When using the HIGH range, the TIC 410A HOT
STICK or equivalent extension pole MUST be used.
• Comply with local and national safety
requirements.
• Use proper protective equipment as required by
local and national authorities.
=
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

3
• Observe the proper safety precautions when
working with voltages above 33 VAC RMS to avoid
electrical shock hazard.
• Before and after hazardous voltage measurements,
test the TIC 300 PRO by pressing the TEST button
and/or on a known source such as line voltage to
determine proper operation.
• Never ground yourself when taking measurements.
Do not touch exposed circuit elements.
• Do not operate the instrument in an explosive
atmosphere.
• Do not expose this product to rain or moisture. This
increases the risk of fire or electric shock.
•
Do not rely on the TIC 300 PRO for testing shielded wire.
• Do not let the unit make contact with a live line
with voltage higher than 20 kV.
• Three phase feeder cables with conductors close to
each other may self-cancel the electric field and
will not be detected by the TIC 300 PRO tracer.
Verify that the phase conductors are separated
by at least 15 in (38.1 cm) before testing for AC
voltage.
UNPACKING AND INSPECTION
Your shipping carton should include:
1 TIC 300 PRO
1 9 V Alkaline Battery
1 User Manual
1 Carrying Case
If any of the items are damaged or missing, return the
complete package to the place of purchase for an exchange.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

4
INTRODUCTION
The TIC 300 PRO safely checks for the presence of AC
voltage without making any disconnection in cables,
wall sockets, fuses, circuit breakers, junction boxes, etc.
No current flow is needed for correct operation.
Rugged and reliable for utility, industrial and mine safety
applications, the TIC 300 PRO warns against dangerous
voltages in low and medium voltage applications up to
122 KV without contacting the energized conductor.
Features
• Utility tool for checking transmission lines, power
distribution equipment, down power lines, fuses,
and load break connectors
• Lower voltage setting for checking voltage
presence in breaker panels, breakers, power
outlets and wiring
• Verifies presence of voltage from 30 VAC to
122,000 VAC (122 kV)
• Non-contact AC voltage detection
• Visual and audible voltage indication
•
Self-test for verifying that the tester is working properly
• Ergonomic design with a convenient handle
• Drop proof up to 6 ft (1.83 m)
Use with the Hot Stick 410A when voltage exceeds 1500 V
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

5
OPERATION
ON/OFF Button
When the TIC 300 PRO is activated, the blue LEDs and
beeper will pulse at a slow rate about twice a second.
The red LED of the range (HIGH) will turn ON.
TEST Button
The TEST button should be used prior to testing actual
power circuits. The TEST function will cause the blue
LEDs and beeper of the range selected (LOW or HIGH) to
pulse at a fast rate.
OSHA listed clearance distances for working with
voltage. National or local requirements may be
different.
Line voltage (kV) Phase to ground Phase to phase
phase to phase (ft-in) (m) (ft-in) (m)
0.03 to 1.0 Note1 Note1 Note1 Note1
1.1 to 15.0 2-1 0.64 2-2 0.66
15.1 to 36.0 2-4 0.72 2-7 0.77
36.1 to 46.0 2-7 0.77 2-10 0.77
46.1 to 72.5 3-0 0.90 3-6 1.05
72.6 to 121 3-2 0.95 4-3 1.29
Note1 – No contact necessary
�Caution: If a three phase circuit is being checked and
one phase is open, the voltage from another phase
maybe detected and will give a faulty indication. Always
make sure that the phase cables are separated by at least
20 in (50.8 cm).
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

6
Voltage Detection
LOW Range
1. Push the ON/OFF push button to turn the unit ON.
2. The high voltage detection circuit is activated. A
beep will sound and the blue LEDs will flash twice
per second.
3. Push the LOW range push button. The unit is ready
for low voltage detection.
4. Place the probe tip of the TIC 300 PRO near, but not
touching, a low (<1000 V) voltage line (Fig. 1).
5. If voltage is present, the blue LEDs will blink and the
beeper will sound at an increased rate. Continuous
visual (blue LEDs) and audible indicators will increase
when the probe tip makes contact with or is very
close to the voltage line.
Fig. 1 Voltage detection in a line
HIGH Range (HOT STICK must be used)
(See Fig. 2)
1. Push the ON/OFF push button to turn the unit ON.
2. The high voltage detection circuit is activated. A
beep will sound and the blue LEDs will flash twice
per second.
3. Approach the probe tip near, but not touching, a
high voltage (>1500 V and <122 kV) conductor.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Altri manuali per TIC 300 PRO
3
Indice
Altri manuali Amprobe Sensore di sicurezza

Amprobe
Amprobe TIC 300 PRO Manuale utente

Amprobe
Amprobe TMULD-300 Manuale utente

Amprobe
Amprobe AT-8000 Series Manuale utente

Amprobe
Amprobe ULD-400 Series Manuale utente

Amprobe
Amprobe UAT-505 Manuale utente

Amprobe
Amprobe RLD-1 Manuale utente

Amprobe
Amprobe ULD-410 Manuale utente

Amprobe
Amprobe ULD-405 Manuale utente

Amprobe
Amprobe ULD-300 Manuale utente

Amprobe
Amprobe GSD600 Manuale utente