Ansul CHECKFIRE 210 Manuale utente

CHECKFIRE 210
DETECTION AND
ACTUATION SYSTEM
OWNERS’ GUIDE
© 2017 Johnson Controls. All rights reserved.
All specifications and other information shown were
current as of document revision date and are subject to
change without notice. |Part No. 442045-01


PAGE 1
CHECKFIRE 210 Detection and Actuation
System Owners’ Guide
“DELAY/RESET/
SILENCE” BUTTON
“PUSH TO ACTIVATE/
ALARM WHEN LIT”
BUTTON AND LED
009275
VISUAL SEAL
DISPLAY
MODULE
This vehicle/equipment is monitored with a CHECKFIRE 210
Detection and Actuation System which is typically connected
to an ANSUL®A-101 or LVS Fire Suppression System for
24-hour fire suppression. The operator of the equipment should
be provided with hands-on training by Authorized ANSUL
Distributors or the end user.
This handbook is a quick-reference guide for basic operation
of the CHECKFIRE 210 System. Two buttons on the display
module and manual actuators provide operator control.
Power: hInternal Only hDual (External & Internal)
External Power Supply (vehicle battery, power panel, etc.):
TD1 (Time Delay 1, seconds): h0 h5 h10 h15
TD2 (Time Delay 2, seconds):
h0 h5 h10 h15
Time Delay Restarts: h2 hUnlimited
Relay #1: hAlarm hFault hNot Used
Relay #2: hShutdown hAlarm hNot Used
Pressure Switch Auxiliary Operation:
Fill-In System Information (as installed)

PAGE 2
IN CASE OF FIRE: Manual Actuation
PUSH RED BUTTON FOR
IMMEDIATE ACTIVATION
OPEN
GUARD DOOR
009343
1) Safely bring equipment to complete stop, set brake and
shut off engine.
2) Break visual seal and open guard door.
3) Push the red “PUSH To Activate / Alarm When Lit” button.
4) Release circuit immediately activates the connected fire
suppression system (if included, pressure switch activates
auxiliary operation). See Note below.
5) Safely exit equipment and stand-by with supplemental
firefighting equipment.
6) Optional manual actuation: Pull ring pin and strike red
button on electric or pneumatic manual actuator.
Note: The red “PUSH To Activate / Alarm When Lit” LED and
sounder remain steady-on for 10 sec. during initiation (release)
of fire suppression system. Post release: Detection 1 and/or
Detection 2, Shutdown, and Release LEDs and sounder
continue to pulse 1 x 10 sec. If safe to re-enter equipment,
push “DELAY/Reset/Silence” button to silence sounder for two
hours.
Electric or Pneumatic Manual Actuator Location(s):
Fill-In System Information (as installed)

PAGE 3
IN CASE OF FIRE: Automatic System Operation
1) Detector(s) registers alarm condition in hazard area and
initiates the time delay notification on display module.
2) “PUSH To Activate / Alarm When Lit” plus Detection 1
and/or Detection 2 LEDs plus sounder:
a. Pulse 2 x 1 sec. until last 5 sec. of TD1; then pulse
4 x 1 sec. with Shutdown LED at start of final 5 sec.
(See DELAY/RESET/SILENCE (grey) button below for
TD1 restart);then, only Shutdown LED is steady-on for
1 sec. indicating TD1 transferring to TD2 (restart no
longer available).
b. Pulse 4 x 1 sec. with Shutdown LED during TD2.
c. Steady-on 10 sec. with Shutdown LED during initiation
(release) of fire suppression system (if included,
pressure switch activates auxiliary operation).
3) As soon as time delay begins: Safely stop equipment, set
brake, shut off engine, and exit. Standby with supplemental
firefighting equipment.
4) Post release: LEDs and sounder pulse 1 x 10 sec.
009290
PUSH GREY
BUTTON TO
RESTART
TIME DELAY
(TD1 ONLY)
DELAY/RESET/SILENCE (Grey) Button
1) Restart Time Delay: Press and release for each restart of
TD1 during alarm condition. (Limit: 2 restarts or Unlimited,
see page 1.)
a. Must be initiated before last second of TD1. (No
response after TD1 until post release.)
b. Note: Press and hold will not extend time delay period.
2) Silence sounder (post discharge or fault notification)
for two hours: Press and release to silence sounder; LED
fault indication will continue until fault is cleared. Any new
fault or detection event will reactivate sounder.
3) Reset function is for Authorized ANSUL Distributor service
technician.

PAGE 4
FRONT PANEL INDICATORS
009290
POWER LED:
GREEN, AMBER OR OFF
1) Power LED
a. Green steady-on indicates normal external power.
b. Green pulsing 1 x 3 sec. indicates normal internal
power.
c. Amber pulsing 1 x 3 sec. indicates external power
fault; system is operating on internal power. Contact
Authorized ANSUL Distributor for service.
d. Amber pulsing 1 x 10 sec. with sounder indicates internal
or external power fault. Contact Authorized ANSUL
Distributor for service.
e. Off indicates no system power. Contact Authorized
ANSUL Distributor for service.
2) All other LEDs
a. Off indicates normal status.
b. Amber or red pulsing with sounder: Contact Authorized
ANSUL Distributor for service.
CAUTION
Any fault indication may cause the fire detection
and actuation system to not function properly;
immediately contact an Authorized ANSUL
Distributor for service.
!

PAGE 5
FRONT PANEL INDICATORS (Continued)
STEP 2 (Continued)
009290
c. LED amber or red indications
!Amber: RELEASE Circuit Fault,
pulsing 1 x 10 sec.
Red: DETECTION Circuit Alarm Condition,
pulsing 1 x 10 sec
Amber: DETECTION Circuit Fault,
pulsing Amber 1 x 10 sec.
Red*: System DISCHARGE activated pressure
switch, steady-on for remaining Release
Activated.
Pulsing 1 x 10 sec. during Post Release
Activated
Amber: ISOLATE Mode, pulsing 2 x 30 sec.
Red: SHUTDOWN status, pulsing 4 x 1 sec.
during Alarm Condition.
Steady-on during Release Activated.
Pulsing 1 x 10 sec. during Post Release
Activated.
* Australian Standard: Only active when “Pressure Switch
Feedback” is programmed.

PAGE 6
FRONT PANEL INDICATORS (Continued)
3) Red “PUSH” To Activate / Alarm When Lit” LED
(sounder matches pulse rate).
a. Pulsing 1 x 1 sec. indicates Pre-Alarm Condition, Alarm
Only Programming or Isolate Mode.
b. Pulsing 2 x 1 sec. indicates Alarm Condition and TD1
(time delay #1) starts countdown (last 5 sec. pulsing
increases to 4 x 1 sec.).
c. Pulsing 4 x 1 sec. indicates last 5 sec. of TD1 and TD2
(time delay #2) continues with pulsing at 4 x 1 sec. until
end of countdown.
d. Steady-on for 10 sec. indicates Release Activated.
e. LED is also a button, see page 2 for manual activation of
fire suppression system.
4) DELAY/Reset/Silence Button
a. Icons on button represent options for system control.
During Time Delay, press button to restart Time
Delay.
When sounder is pulsing, press button to silence.
Press and hold button for 3 sec. to reset system.