Argo AWIBS9 Manuale

TECHNICAL DATA
& SERVICE MANUAL
INDOOR UNIT: AWIBS9
0.8180.545.01 09/12
SPLIT SYSTEM AIR CONDITIONER
Model No. Product Code No.
AWIBS9 38.7004.093

IMPORTANT!
Please read before installation
This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important to install or
service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes.
• Pay close attention to all warning and caution notices given in
this manual.
•The unit must be supplied with a dedicated electrical line.
This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.
SPECIAL PRECAUTIONS
• During installation, connect before the refrigerant system and
then the wiring one; proceed in the reverse orden when removing
the units.
When wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are
completed or reconnected and checked, to ensure the grounding.
• Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause
accidental injury and death.
•Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection
different from the ground connection.
• Connect all wiring tightly. Loose wiring may cause overheating
at connection points and a possible fire hazard.
• Do not allow wiring to touch the refrigerant tubing, compressor,
or any moving parts of the fan.
• Do not use multi-core cable when wiring the power supply and
control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.
When installing...
... In a ceiling or wall
Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.
... In a room
Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls
and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for
the outdoor unit.
This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare
and union tubes before connecting them; screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.
When servicing
• Turn the power OFF at the main power board before opening
the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no
metal scraps or bits of wiring have been left inside the unit being
serviced.
• Ventilate the room during the installation or testng the refrigeration
system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.
WARNING
CAUTION
WARNING
2

Table of Contents Page
1. SPECIFICATIONS 4
1-1 Unit specifications 4
1-2 Major Component specifications 5
1-3 Other Component specifications 6
2. DIMENSIONAL DATA 7
3. PERFORMANCE DATA 8
3-1 Air Throw Distance Chart 8
4. ELECTRICAL DATA 9
4-1 Electric Wiring Diagrams 9
5. FUNCTION 10
5-1 System operation control 10
5-2 Cool Mode Operation 11
5-3 Heat Mode Operation 11
5-4 Auto Mode Operation (only monosplit) 12
5-5 Dry Mode Operation 13
5-6 Fan Mode Operation 13
5-7 Auto Fan Speed 13
5-8 Forced-Made 14
5-9 Protection Operations in indoor unit 14
5-10 Protection Operation outdoor unit 15
5-11 Defrost 16
5-12 I Feel Function 16
5-13 Hi Power mode 16
5-14 Night Function 17
5-15 Leds off function 17
5-16 Capacity Test Mode 17
5-17 Diagnostic 18
5-18 Indoor unit jumpers Configuration 19
5-19 Outdoor unit jumpers Configuration 19
5-20 Contacts for building automation 19
6. INDOOR UNIT AND REMOTE CONTROL ADDRESS 20
6-1 Address Switches (only for multisplit) 20
6-2 Refrigerant Circuit Check (only for multisplit) 20
6-3 Changing the Address of the Air Conditioner 20
7. TROUBLESHOOTING 21
7-1 Check before and after troubleshooting 21
7-2 Circuit Breaker Trips or Fuse Blows 21
7-3 System does not run 22
7-4 Outdoor Unit does not run and no Fault is displayed 24
7-5 Only Outdoor Unit is Off 24
7-6 Fault on outdoor unit 25
7-7 Air Conditioner operates, but abnormalities are observed 26
7-8 Noise problem 28
8. CHECKING ELETRICAL COMPONENTS 29
8-1 Measurement of Insulation Resistance 29
8-2 Checking Continuity of Fuse on PCB Assy 29
8-3 Checking motor capacitor 29
3

1. SPECIFICATIONS
1-1 Unit Specifications
Power source
V
oltage rating
Performance
Capacity
Air circulation High/Med./Low m³/h
Features
Controls/Temperature controls
Control unit
Timer
Fan speed
Airflow direction Horizontal
Vertical
Air Filter
Power noise level High/Med./Low dB-A
Refrigerant tubing connections
Refrigerant Narrow tube mm(in.)
tube diameter Wide tube mm(in.)
Refrigerant
Air clean filter
Dimensions & Weight
Unit dimensions Height mm
Width mm
Depth mm
Package dimensions Height mm
Width mm
Depth mm
Weight Net kg
Shipping kg
Shipping volume m3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
R410A
Flare type
Washable, Anti-Mold
55/52/47
Cooling Heating
See catalogue with the requested matching
880 / 710 / 580
360
Microprocessor/ I.C. thermostat
Wireless remote control unit
3 and Auto
ON/OFF 24 hours
285
Manual
Auto
12.7 (1/2)
Optional
0,11
220 - 240 V ~ 50 Hz
230 V - 50 Hz
1070
290
12
15
6.35 (1/4)
995
240
4

1-2 Major Component Specifications
Controller PCB
Part No.
Controls
Control circuit fuse
Jumper setting JP1..JP5
Remote Control Uni
t
Fan & Fan Moto
r
Type
Q'ty ……. Dia. and lenght mm
Fan motor model…Q'ty
No. Of poles…rpm (230 V, Hi/Me/Lo)
Nominal output W
Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close
Run capacitor µF
VAC
Flap Moto
r
Type
Model
Rating
Coil resistance (Ambient temp. 25 °C )
Heat Exch. Coil
Coil
Rows
Fin pitch mm
Face area
DATA SUBJECT TO CHANGE WITHOUT NOTICE
0,25
SAC ON-OFF IDU
SAC W-REM
Cross - flow
UF2Q-21SB5P…1
2… 1550/1250/1025
Aluminium plate fin / Copper tube
DC 12 V
400 ± 7%
2
1,3
440
MP24Z2
Stepping motor
24,07
YEL-ORG: 73,55
Microprocessor
250 V - 3,15 A
1…. Ø 88 / L 746
2,54mm-5pcs
1,5
79 ± 15
BRN-WHT: 163,7
VLT-ORG: 33,16
YEL-PNK: 43,72
termal protector
130 ± 8
VLT-WHT: 68,84
5

1-3 Other Component Specifications
Trasformer
(
TR
)
Rating Primary
Secondary
Thermal cut-off temp. (PTC) (on the board)
Thermistor
(
Coil sensor
)
Resistance k
Thermistor
(
Room sensor
)
Resistance k
DATA SUBJECT TO CHANGE WITHOUT NOTICE
A040C5026AA
AC 230 V, 50 Hz
13 V - 5VA
NTC-THERMISTOR
10 at 25 °C
NTC-THERMISTOR
C 883 - 120°C
10 at 25 °C
6

2. DIMENSIONAL DATA
REAR WIEW
dimension in mm
DRAIN HOSE D.18
WIDE TUBE D.12,7 (1/2")
NARROW TUBE D.6,35 (1/4")
CENTER OF TUBING HOLE
(2 PLACES)
7

3. PERFORMANCE DATA
3-1 Air Throw Distance Chart
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C
Fan speed : High
Cooling
0
1
2
3
4
0123456789
: Flap angle 0° , : Axis air velocity 0°
: Flap angle 30°, : Axis air velocity 30°
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20°C
Fan speed : High
Heating
0
1
2
3
4
0123456789
: Flap angle 45° , : Axis air velocity 45°
: Flap angle 60° , : Axis air velocity 60°
8

4. ELECTRICAL DATA
4-1 Electric Wiring Diagram
9

5.FUNCTION
5-1 System operation control
The inputs to the systems come from indoor and outdoor sensors. The outdoor unit is the system
MASTER while the indoor one is the SLAVE.
Communication between units is made with a 2 poles RS485 bus
The indoor units receives the user input (fan speed, flap position etc) through remote controlle
r
which sends signal every time a button is pressed and in any case, automatically, every 5 minutes
.
5.1.1 control specification
During operation compressor speed can be subjected to change due to thermal load variations
or protection activations but in any case:
• The minimum time interval between an OFF and a ON operation is not lower than 3 minutes
• The minimum operating time is not lower than 3 minutes
• The maximum acceleration/deceleration rate is fixed at 20rpm /sec
• During the start-up compressor speed increases according to a defined rule which is
independent from the thermal load calculation.
5-1.2 Multisplit available modes
If the unit is a part of a multisplit system, there could be some mode combination not available
(example: unit A - heat mode and unit B - cool mode).
In this case the system automatically stops, leds TMR and STB blink while led OPR is on
●= LED blinking
●= LED on
A
VAILABLE MODE COMBINATION TABLE
AUTO HEAT DRY COOL FAN
AUTO □□□□□
HEAT □■□□■
DRY □□■■■
COOL □□■■■
FAN □■■■■
■AVAILABLE
□NOT AVAILABLE
INDOOR UNIT B
INDOOR UNIT A
10
Indice
Altri manuali Argo Condizionatore d'aria

Argo
Argo dados 40 Manuale utente

Argo
Argo ABDGI 20 HW Manuale utente

Argo
Argo IRO Manuale utente

Argo
Argo ECOLIGHT PLUS 9000 UI Manuale operativo

Argo
Argo AD28AL Manuale

Argo
Argo ASIAS8DC Manuale utente

Argo
Argo AWIBS9DC Manuale utente

Argo
Argo AUG38PCLI Manuale

Argo
Argo ASR525CL Manuale

Argo
Argo ARGO 245C Manuale utente

Argo
Argo NEWAGE 9000 UI Manuale utente

Argo
Argo AWIAS12DC Manuale utente

Argo
Argo GREENSTYLE PLUS DUAL 9000 UI Manuale utente

Argo
Argo ADG ECO 35PH Manuale operativo

Argo
Argo X3I ECO PLUS AF27 HL Manuale operativo

Argo
Argo Husky Manuale utente

Argo
Argo AEG ECO PLUS 35PIH Manuale utente

Argo
Argo Holly Manuale utente

Argo
Argo X3 ECO PLUS Manuale operativo

Argo
Argo LUDVIG Manuale utente