TESTING
1) Activate the call point.
LED indicator signals “Alarm activation”; the control panel receives the alarm message.
2) Deactivate the call point.
3) Reset the control panel.
BATTERY FAULTS AND BATTERY SUBSTITUTION PROCEDURE
When one or both batteries are low in charge, a specific fault message is routed to
the control panel. If such event occurs:
1) Remove the device block from the back box.
2) Extract both batteries.
3) Insert both new batteries into their holders, oriented as per polarity marks.
See POWERING UP - DEVICE LINKED TO THE SYSTEM.
4) Reinstall the device block.
TECHNICAL SPECIFICATIONS *
*See TDS-TWCPX technical specification document for further technical data.
BATTERIES SPECIFICATIONS
*Batteries lifespan depends by environmental conditions, default monitor settings and link quality.
Local safety standards may require you
to test these devices on a regular basis.
When a low battery condition is indicated,
both batteries must be changed altogether.
Batteries must be brand new.
Do not touch the Link / program switch.
Ensure that the batteries are installed properly,
with their polarities matching the indications on
the device.
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to
environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace
the devices in order to minimize the risk of reduced performance caused by external factors. Ensure that
this device is only used with compatible control panels.
Detection systems must be checked, serviced and maintained on a regular basis to confirm correct
operation. Smoke sensors may respond differently to various kinds of smoke particles, thus application
advice should be sought for special risks. Sensors cannot respond correctly if barriers exist between them
and the fire location and may be affected by special environmental conditions. Refer to and follow national
codes of practice and other internationally recognized fire engineering standards.
Appropriate risk assessment should be carried out initially to determine correct design criteria and updat-
ed periodically.
Use only in Taurus fire detection and alarm systems.
WARRANTY
All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materials or manu-
facturing defects, effective from the production date indicated on each product. This warranty is invalidat-
ed by mechanical or electrical damage caused in the field by incorrect handling or usage. Product must
be returned via your authorized supplier for repair or replacement together with full information on any
problem identified. Full details on our warranty and product’s returns policy can be obtained upon request.
ARGUS SECURITY S.R.L.
Via del Canneto, 14
34015 Muggia (TS)
Italy
TW-CP-R-01
EN 54-25:2008
EN 54-11:2001 + A1:2005
Type A (direct operation)
Indoor use only
Specification Value
Communication range with TW-MTI-01, TW-MEC-01 or TW-ME-01
network devices 200 m (in open space)
Wireless frequency band 868 MHz
Number of wireless channels 66
Radiated power 14 dBm (25 mW)
Operating temperature range -10 °C to 55 °C
Maximum humidity (non condensing) 95% RH
Environmental application Indoors
Dimensions 88 mm x 87 mm x 61 mm
Weight 160 grams (without batteries)
Table 3
Specification Value
Batteries type CR123A (3 V, 1.25 Ah)
Batteries lifespan * 10 years
Low battery threshold value (nominal) 2.850 V
Table 2