Atag iC Economiser 27 Guida rapida

Appliance
Technical Guide
SERVICE ENGINEER EDITION

2
The heating
industry has
just had an
upgrade
We will help you grow and protect
your business.
Now you
have too

3
Contents
APPLIANCES COVERED AND SERIAL NUMBER 4
iC & iC ECONOMISER COMBINATION BOILERS
TECHNICAL DATA 5
iS SYSTEM & iR REGULAR BOILERS
TECHNICAL DATA 6
BOILER L AYOUT 7
CONTROL PANEL 8
CONTROLS AND EXPLANATION
OF THE FUNCTIONS 9
HOT WATER TEMPERATURE 9
CENTRAL HEATING TEMPERATURE 9
BOILER INFORMATION 9
RESET BUTTON 10
ANCILLARY FUNCTIONS 10
HOT WATER SUPPLY 11
COMFORT AND ECO 11
CH SYSTEM 11
FROST PROTECTION 11
DANGER OF FROST 11
INSTALLATION FROST PROTECTION 11
BOILER FROST PROTECTION 11
PUMP KICK AND DIVERTER
VALVE KICK 12
BOILER ANTI-CYCLE TIME 12
PUMP OVERRUN 12
SERVICE CHIMNEY SWEEP MODE 12
BOILER DE-AERATION PROGRAM 13
COMBI BOILER 13
SYSTEM BOILER 13
REGULAR BOILER 13
COMMISSIONING FUNCTION 13
YOU HAVE UPGRADED TO ATAG, WE WILL HELP YOU TO GROW AND PROTECT YOUR BUSINESS
WATER PRESSURE SENSOR 14
FLOW SWITCH (REGULAR BOILER) 14
COMBI BOILER CENTRAL HEATING MODE (CH) 15
COMBI BOILER HOT WATER MODE (DHW) 16
COMBI BOILER CH MODE 17
CH CONTROLS 17
COMBI BOILER DHW MODE 17
DHW CONTROLS (COMBINATION BOILERS) 17
SYSTEM & REGULAR BOILER CENTRAL
HEATING MODE 17
CH CONTROLS 17
CHECKING COMBUSTION CO218
BOILER PARAMETERS 19
GRADIENT SPEED CH 20
HEATING LINE 20
SUMMER-ECO TEMPERATURE 20
WEATHER COMPENSATOR 21
FLUE LENGTHS 21
ERROR CODES 22
RESISTANCE TABLE SENSORS 23
PCB ELECTRICAL DIAGRAM (LMU) 24
VOLT FREE CONNECTIONS 25
ATAG 3-PORT EXTERNAL DIVERTER
VALVE AND ONE CONTROLLER KIT 26
ROUTINE SERVICING 30
AIR BOX/COVER 30
SIPHON 31
FAN UNIT AND BURNER CASSETTE 31
HEAT EXCHANGER 33
IGNITION ELECTRODE 34

MODEL GC NUMBER
iC 24 Combination Boiler 47-310-19
iC 28 Combination Boiler 47-310-21
iC 36 Combination Boiler 47-310-23
iC 40 Combination Boiler 47-310-25
iC 24 Combination Boiler LPG 47-310-20
iC 28 Combination Boiler LPG 47-310-22
iC 36 Combination Boiler LPG 47-310-24
iC 40 Combination Boiler LPG 47-310-26
iC Economiser 27 Combination Boiler 47-310-27
iC Economiser 35 Combination Boiler 47-310-29
iC Economiser 39 Combination Boiler 47-310-31
iC Economiser 27 Combination Boiler LPG 47-310-28
iC Economiser 35 Combination Boiler LPG 47-310-30
iC Economiser 39 Combination Boiler LPG 47-310-32
iS 15 System boiler 41-310-20
iS 18 System boiler 41-310-22
iS 24 System boiler 41-310-24
iS 32 System boiler 41-310-26
iS 40 System boiler 41-310-28
iS 15 System boiler LPG 41-310-21
iS 18 System boiler LPG 41-310-23
iS 24 System boiler LPG 41-310-25
iS 32 System boiler LPG 41-310-27
iS 40 System boiler LPG 41-310-29
iR 15 Regular boiler 41-310-32
iR 18 Regular boiler 41-310-34
iR 24 Regular boiler 41-310-36
iR 32 Regular boiler 41-310-38
iR 40 Regular boiler 41-310-40
iR 15 Regular boiler LPG 41-310-33
iR 18 Regular boiler LPG 41-310-35
iR 24 Regular boiler LPG 41-310-37
iR 32 Regular boiler LPG 41-310-39
iR 40 Regular boiler LPG 41-310-41
SERIAL NUMBER: P144040766
P 14 40 4 0766
YEAR WEEK DAY No.
Appliances covered
and serial number
4

iC & iC Economiser combination
boilers technical data
iC ECONOMISER COMBINATION BOILERS iC Economiser 27 iC Economiser 35 iC Economiser 39
Part number BE200127 BE200135 BE200139
ErP Seasonal space heating energy eciency class A A A
ErP Seasonal space heating energy eciency (%) 94 94 94
ErP Water heating energy eciency class A A A
ErP Water heating energy eciency (%) 94 96 96
ErP Declared load profile DHW XXL XXL XXL
DHW input (kW) 29.8 40.3 42.5
CH output (kW) 23.2 31.2 31.2
Hot water flow rate @ 35°C rise (l/min) 12.6 16.1 17.0
SEDBUK 2009 (%) 89.7 89.7 89.7
Dimensions (H x W x D) (mm) 700 x 440 x 355 700 x 440 x 355 700 x 440 x 355
Boiler lift weight with jig (Kg) 43 46 46
Standard warranty (years) 10 10 10
LPG conversion kit available Yes Yes Yes
NOx class 6 6 6
Ingress protection (IP) IPX4D IPX4D IPX4D
Maximum equivalent horizontal flue length (m) 60/100mm 18 6 6
Maximum equivalent vertical flue length (m) 60/100mm 18 6 6
Maximum equivalent horizontal flue length (m) 80/125mm 50 45 45
Maximum equivalent vertical flue length (m) 80/125mm 50 45 45
iC COMBINATION BOILERS iC24 iC28 iC36 iC40
Part number BC100124 BC100128 BC100136 BC100140
ErP Seasonal space heating energy eciency class A A A A
ErP Seasonal space heating energy eciency (%) 94 94 94 94
ErP Water heating energy eciency class A A A A
ErP Water heating energy eciency (%) 85 84 90 90
ErP Declared load profile DHW XL XL XL XL
DHW input (kW) 26.6 30.3 39.3 42.0
CH output (kW) 23.2 23.2 31.2 31.2
Hot water flow rate @ 35°C rise (l/min) 10.1 11.5 14.9 16.2
SEDBUK 2009 (%) 89.7 89.7 89.7 89.7
Dimensions (H x W x D) (mm) 700 x 440 x 355 700 x 440 x 355 700 x 440 x 355 700 x 440 x 355
Boiler lift weight with jig (Kg) 41 41 44 44
Standard warranty (years) 10 10 10 10
LPG conversion kit available Yes Yes Yes Yes
NOx class 6 6 6 6
Ingress protection (IP) IPX4D IPX4D IPX4D IPX4D
Maximum equivalent horizontal flue length (m) 60/100mm 18 18 6 6
Maximum equivalent vertical flue length (m) 60/100mm 18 18 6 6
Maximum equivalent horizontal flue length (m) 80/125mm 50 50 45 45
Maximum equivalent vertical flue length (m) 80/125mm 50 50 45 45
5

iS SYSTEM BOILERS iS15 iS18 iS24 iS32 iS40
Part number BS300115 BS300118 BS300124 BS300132 BS300140
ErP Seasonal space heating energy eciency class A A A A A
ErP Seasonal space heating energy eciency (%) 93 93 94 94 94
CH output kW (50/30°C) 14.7 17.5 23.2 31.2 38.8
SEDBUK 2009 (%) 89.8 89.8 89.8 89.8 89.8
Dimensions (H x W x D) (mm) 700 x 440 x 355 700 x 440 x 355 700 x 440 x 355 700 x 440 x 355 700 x 440 x 355
Boiler lift weight with jig (Kg) 39 39 39 42 42
Standard warranty (years) 10 10 10 10 10
LPG conversion kit available Yes Yes Yes Yes Yes
Solar compatible Yes Yes Yes Yes Yes
NOx class 6 6 6 6 6
Ingress protection (IP) IPX4D IPX4D IPX4D IPX4D IPX4D
Maximum equivalent horizontal flue length (m) 60/100mm 18 18 18 6 6
Maximum equivalent vertical flue length (m) 60/100mm 18 18 18 6 6
Maximum equivalent horizontal flue length (m) 80/125mm 50 50 50 45 45
Maximum equivalent vertical flue length (m) 80/125mm 50 50 50 45 45
iR REGULAR BOILERS iR15 iR18 iR24 iR32 iR40
Part number BR400115 BR400118 BR400124 BR400132 BR400140
ErP Seasonal space heating energy eciency class A A A A A
ErP Seasonal space heating energy eciency (%) 94 94 94 94 94
CH output kW (50/30°C) 14.7 17.5 23.2 31.2 38.8
SEDBUK 2009 (%) 89.8 89.8 89.8 89.8 89.8
Dimensions (H x W x D) (mm) 700 x 440 x 355 700 x 440 x 355 700 x 440 x 355 700 x 440 x 355 700 x 440 x 355
Boiler lift weight with jig (Kg) 32 32 32 35 35
Standard warranty (years) 10 10 10 10 10
LPG conversion kit available Yes Yes Yes Yes Yes
Solar compatible Yes Yes Yes Yes Yes
NOx class 6 6 6 6 6
Ingress protection (IP) IPX4D IPX4D IPX4D IPX4D IPX4D
Maximum equivalent horizontal flue length (m) 60/100mm 18 18 18 6 6
Maximum equivalent vertical flue length (m) 60/100mm 18 18 18 6 6
Maximum equivalent horizontal flue length (m) 80/125mm 50 50 50 45 45
Maximum equivalent vertical flue length (m) 80/125mm 50 50 50 45 45
iS system and iR regular
boilers technical data
6

iC ECONOMISER COMBINATION BOILER LAYOUT
1Heat exchanger 9Control panel 17 Safety valve
2Ignition unit 10 Three-way valve 18 DHW Economiser
3Fan unit 11 Circulation pump 19 Siphon
4Air supply damper 12 Filling loop 20 Isolation valve flow CH
5Gas valve 13 Flue gas exhaust 21 Isolation valve gas
6Automatic de-aerator 14 Combustion air supply 22 Isolation valve cold water
7DHW plate heat exchanger 15 Boiler data plate 23 Isolation valve return CH
8Control unit 16 Expansion vessel 24 Flue non return valve
T1 Flow sensor P1 Water pressure CCondensation pipe
T2 Return sensor GGas pipe KCold water pipe
T3 Hot water sensor AFlow pipe CH WHot water pipe
F1 DHW flow sensor RReturn pipe CH
Boiler layout
20
A W G
21
K
22
R
23
13
14 5
24 6
3
2 1
16
T1
P1
T2
18 15
7 4
11 9
12
817
19C
F1
T3
10
7

DHW function ON / Flashing request for heat
ECO DHW ECO mode or DHW comfort mode
Flame Burner on
Heating function ON / Flashing request for heat
Bell Error indication
Spanner Service mode or blocking
Snow Flake Frost protection
LCD display
with backlight
Full load for
emissions check
Directly operated
soft cushion button
OK and Escape
(ancillary function)
Scroll and + / −
function
(ancillary function)
Setting of boiler temperature
(max. supply temperature)
Eco buttonReset button
Setting of hot water temperature
Frost protection
manual mode
Control panel
(All ATAG boiler range)
8

Hot water temperature
Setting the hot water temperature:
Briefly press +or -; the display will show the flashing pre-set value;
Briefly press +or -to change the set value. Each change becomes
active directly.
Hot water program OFF: Press -until the lowest value is reached
and then press -again, -- appears in the display.
The will disappear from the display
Switching on works in reverse order.
(combi boiler only)
Central heating temperature
Setting the CH water temperature:
Briefly press +or - ; the display will show the flashing pre-set value;
Briefly press +or -to change the set value. Each change becomes
active directly.
CH program OFF: Press -until the lowest value is reached and then
press -again, -- appears in the display.
The will disappear from the display
Switching on works in reverse order.
Boiler Information
By pressing the eco button for 6 seconds the display changes to info mode
A0: Flow water temperature in °C
A1: Return water temperature in °C
A2: DHW temperature in °C (combi or system boiler with 3-port kit only)
A3: T-set temperature (calculated) in °C
A4: Flue gas temperature (only if a flue gas sensor is connected) in °C
A5: Outside temperature (only if an outside sensor is connected) in °C
A6: Water pressure in bar (combi & system boilers only)
A7: DHW flow rate in l/min (combi only)
A8: Ionisation current in µA.
A9: rpm of fan (x100)
To return to the standard view press ESC.
Controls and explanation
of the functions
scroll
scroll
scroll
9

Reset button
The reset button allows the boiler to restart if an error has occurred.
In case of an error the symbol is displayed with a XXX code.
In other cases the reset button does not function and will not respond to
operation.
scroll
Ancillary functions
scroll
Both + buttons = Commissioning-mode
for checking the CO2
Both – buttons: Pump continuous on/o
DHW button: Scroll function
(‘scrolling’ through parameters)
CH + button = OK (confirm)
CH – button = ESC function
(back to standard display)
10
Questo manuale è adatto per i seguenti modelli
33
Indice
Altri manuali Atag Caldaia

Atag
Atag A200S Nota di rilascio

Atag
Atag Q 25S Manuale utente

Atag
Atag XL-F Series Manuale utente

Atag
Atag Q 25S Nota di rilascio

Atag
Atag iSteel Series Manuale utente

Atag
Atag Blauwe Engel S-HR Series Guida utente

Atag
Atag A325EC Manuale utente

Atag
Atag iR 12 Nota di rilascio

Atag
Atag i24C Guida rapida

Atag
Atag Q 25S Nota di rilascio

Atag
Atag iR 15 Nota di rilascio

Atag
Atag i28C Nota di rilascio

Atag
Atag XL140 Nota di rilascio

Atag
Atag XL-W Series Manuale utente

Atag
Atag IS 12 Nota di rilascio

Atag
Atag A-Series Manuale utente

Atag
Atag E 22S Guida utente

Atag
Atag 41-310-12 Manuale utente

Atag
Atag A200SOV Manuale utente

Atag
Atag Premier E-SHR 15 Guida utente