Series S Solid-State Staging Controller Instruction Manual
Series S Solid-State Staging Controller Instruction Manual
Series “S” Agency Approvals
E57435 Industrial Control Equipment Component, Auxiliary Devices
UL-508
Models SCA, SUA
E66598 Component, Temperature Indicating and Regulating Equipment
UL-873
Models SCB, SCC, SUB, SUC
Athena Controls, Inc.
5145 Campus Drive
Plymouth Meeting, PA 19462
Phone: 610-828-2490
Fax: 610-828-7084
www.athenacontrols.com
You can reach our technical support team by phoning 1-800-782-6776 (from the United
States) or 610-828-2490 (from anywhere in the world). The e-mail address for tech
support is [email protected]
Athena® is a registered trademark of Athena Controls, Inc.
© 2004 Athena Controls, Inc. All rights reserved.

Series S Solid-State Staging Controller Instruction Manual
Series S Solid-State Staging Controller Instruction Manual
Two-Year Limited Warranty
THIS EQUIPMENT IS WARRANTED TO BE FREE FROM DEFECTS OF MATERIAL
AND WORKMANSHIP. IT IS SOLD SUBJECT TO OUR MUTUAL AGREEMENT THAT
THE LIABILITY OF ATHENA CONTROLS, INCORPORATED IS TO REPLACE OR
REPAIR THIS EQUIPMENT AT ITS FACTORY, PROVIDED THAT IT IS RETURNED
WITH TRANSPORTATION PREPAID WITHIN TWO (2) YEARS OF ITS PURCHASE.
THE PURCHASER AGREES THAT ATHENA CONTROLS, INCORPORATED ASSUMES
NO LIABILITY UNDER ANY CIRCUMSTANCES FOR CONSEQUENTIAL DAMAGES
RESULTING FROM ITS USE OR FROM IMPROPER HANDLING OR PACKAGING OF
SHIPMENTS RETURNED TO THE FACTORY.
COMPONENTS WHICH WEAR OR WHICH ARE DAMAGED BY MISUSE ARE NOT
WARRANTED. THESE INCLUDE CONTACT POINTS, FUSES, ELECTROMECHANICAL
RELAYS, AND TRIACS. UNITS WHICH HAVE BEEN MODIFIED BY A CUSTOMER IN
ANY WAY ARE NOT WARRANTED.
Other than those expressly stated herein, THERE ARE NO OTHER WARRANTIES
OF ANY KIND, EXPRESS OR IMPLIED, AND SPECIFICALLY EXCLUDED BUT NOT
BY WAY OF LIMITATION, ARE THE IMPLIED WARRANTIES OF FITNESS FOR A
PARTICULAR PURPOSE AND MERCHANTABILITY.
IT IS UNDERSTOOD AND AGREED THE SELLER’S LIABILITY WHETHER IN
CONTRACT, IN TORT, UNDER ANY WARRANTY, IN NEGLIGENCE OR OTHERWISE
SHALL NOT EXCEED THE RETURN OF THE AMOUNT OF THE PURCHASE PRICE
PAID BY THE PURCHASER AND UNDER NO CIRCUMSTANCES SHALL SELLER BE
LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
THE PRICE STATED FOR THE EQUIPMENT IS A CONSIDERATION IN LIMITING
SELLER’S LIABILITY. NO ACTION, REGARDLESS OF FORM, ARISING OUT OF THE
TRANSACTIONS OF THIS AGREEMENT MAY BE BROUGHT BY PURCHASER MORE
THAN ONE YEAR AFTER THE CAUSE OF ACTION HAS ACCRUED.
SELLER’S MAXIMUM LIABILITY SHALL NOT EXCEED AND BUYER’S REMEDY IS
LIMITED TO EITHER (i) REPAIR OR REPLACEMENT OF THE DEFECTIVE PART OR
PRODUCT, OR AT SELLER’S OPTION (ii) RETURN OF THE PRODUCT AND REFUND
OF THE PURCHASE PRICE, AND SUCH REMEDY SHALL BE BUYER’S ENTIRE AND
EXCLUSIVE REMEDY. THE SPECIFICATIONS PUT FORTH IN THIS MANUAL ARE
SUBJECT TO CHANGE WITHOUT NOTICE.

Series S Solid-State Staging Controller Instruction Manual Series S Solid-State Staging Controller Instruction Manual
1
Contents
Section 1 General Introduction
1.1 General Description…………………………...1
1.2 Typical Configurations...……………………....2
1.3 Specifications………...………………………...4
Section 2 Installation Instructions
2.1 Installation………………………...……….…...5
2.2 Module Explanation …………………….....….8
2.3 Operation………………………………..……...9
2.4 Adjustments…………………………..………...9
2.5 Time Proportioning Adjustment…..…………..10
2.7 Span Adjustment…………..…………………..11
2.8 System Adjustments………..…………………11
2.9 Fusing…………………………..………………11
Section 3 Options
3.1 Thermistor Input - “B” Option……...…………12
3.2 Thermistor Input - “C” Option………………...12
Section 4 Unit Repairs..................................................19

Series S Solid-State Staging Controller Instruction Manual Series S Solid-State Staging Controller Instruction Manual
1
Section 1 General Introduction
1.1 General Description
The Athena “S” Series Solid State Staging Controls
Provide pilot duty sequencing of multiple loads up to
18 stages.
SU - Up-Down Mode:
Adds stages in progression. Removes stages in
reverse order., the last stage ‘on’ being the first stage
‘off’ on load reductions. Blue Handle Cooling stages
provide automatic transfer to cooling. Starts with all
stages ‘off.’
Output capacity: 1 AMP per step (10 Amps inrush).
SC - Circular Mode:
Operates all heaters and contractors evenly. First
stage ‘on’ is first stage ‘off.’ Starts with all stages ‘off.’
Output capacity: 1 Amp per step (20 Amps inrush).

Series S Solid-State Staging Controller Instruction Manual
2
Series S Solid-State Staging Controller Instruction Manual
3
1.2 Typical Configurations
Circular - SC Type Controller
Ordering code example:
10 Heating Steps
Code: SCA - 10
Any number SC Heat Stages up to ten. End board
follows last used stage.
SC End Board
(Always follows
last used stage)
SC Heat Stages
Step Delay Board
Input Conditioner
BLACK
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
YELLOW
GREEN
9
8
7
6
5
10
4
3
2
1
9
8
7
6
5
10
4
3
2
1
(Timing)

Series S Solid-State Staging Controller Instruction Manual
2
Series S Solid-State Staging Controller Instruction Manual
3
1.2 Typical Configurations
Up-Down Operation – SU type Controller
Ordering code example:
6 Heating & 2 Cooling Steps
Code: SUA-06-02 or SUB-06-02
Any combination of heat and/or cool steps up to ten.
Cooling and heating modules may be intermixed if
reheat is desired. A heat module below a cool module
will provide automatic reheat.
Last position
not used on SU
SU Heat Stages
SU Cool Stages
Step Delay Board
Input Conditioner

Series S Solid-State Staging Controller Instruction Manual
4
Series S Solid-State Staging Controller Instruction Manual
5
1.3 Specifications
Input ‘A’: 4-20 mA dc. 60 mA max,
or 6 V dc, 9 V max. 135
ohms slidewire, 100-1000
ohms acceptable
Input ‘B’: Thermistor probe to match
range
Output: One amp per step max
(ten amps inrush)
Signal Isolation: 1500 volts from power
circuits and ground
Time Delay: Adjustable, from 2.5 to 12
seconds; automatic
slowdown near balance
Adjustments: Time Proportioning –
Adjustable from differential
to time proportioning
Span – Adjusts to input
range
Indication: L.E.D. logic status light on
each output stage.
Supply voltage: 120 V + 10%, - 15%,
50/60 Hz 4 VA plus total
contactor VA
Ambient Temperature: 30º to 130º F. (-1.1º to 54.4º C)
Dimensions: 13" L, 6" W, and 3" H
(34.3 cm L x 15.2 cm W x
8.9 cm H)

Series S Solid-State Staging Controller Instruction Manual
4
Series S Solid-State Staging Controller Instruction Manual
5
Section 2 Installation Instructions
2.1 Installation.
1. Carefully unpack instrument. Handle with care.
Inspect for shipping damage. Report and damage to
carrier immediately.
2. Pick a location for the controller where it will not be
subjected to excessive shock, vibration, dirt, moisture
or oil. The ambient temperature of the area should
be between 30º and 130ºF (-1.1º to 54.4º C).
3. Mount the controller
with four 8-32 x
” screws. The
controllers are not
position sensitive
and can be mounted
in any plane.
4. Consult the wiring
diagram on the next
page. Standard
units require
120 V 50/60 Hz.
5. Be certain that
power is off. Then
connect power wires
to .250 push-on
terminals marked X1
and X3. If used on
a grounded system,
the X2 terminal should be grounded.

Series S Solid-State Staging Controller Instruction Manual
6
Series S Solid-State Staging Controller Instruction Manual
7
Standard Wiring (up to 10 steps)
Standard Wiring (11 to 18 steps)
“A”
“A”
“B”
“C”
Indice
Altri manuali Athena Controllori

Athena
Athena 18C Series Manuale utente

Athena
Athena 1ZC Series Manuale utente

Athena
Athena SERIES 16 Manuale utente

Athena
Athena C10 Series Manuale per l'uso e la cura

Athena
Athena 2000 Series Manuale utente

Athena
Athena RMB/1 Manuale utente

Athena
Athena 16C series Manuale utente

Athena
Athena 18C Series Manuale utente

Athena
Athena SERIES 16 Manuale utente