
TROUBLESHOOTING
8 CSX User Manual 710-02407-00J
5. Troubleshooting
5.1 LEDs
Off No control power Motor not running
On Ready Motor running at full speed
Flash Starter tripped Motor starting or stopping
5.2 Trip Codes
The Ready LED will flash a different number of times to indicate the cause of the trip.
x 1 Power Circuit: Check mains supply (L1, L2, L3), motor circuit (T1, T2, T3), soft
starter SCRs and bypass relays.
x 6 Supply Frequency: Check mains voltage is available and supply frequency is in
range.
x 8 Network Communication Failure (between module and network): Check
network connections, settings and configuration.
x 9 Starter Communication Failure (between starter and module): Remove and refit
accessory module.
Supply Frequency Protection
The soft starter will trip on supply frequency if the frequency rises above 72 Hz or falls below
40 Hz for more than five seconds while the soft starter is running. These trip points are not
adjustable.
In pre-start, starting and stopping modes the high and low frequency limits both apply with no
time delay.
A supply frequency trip will also occur if:
xall three input phases are lost while the soft starter is running
xall three input phases fall below 120 VAC at start or while the soft starter is running
xthe line contactor opens while running
5.3 Reset
Trips can be cleared by pressing the Reset button on the soft starter, sending a Reset
command from the serial communications network, or by switching the control inputs.
To clear a trip via the control inputs, the soft starter requires a closed to open transition on
the stop input (02).
xIn three-wire control, use the external stop button to momentarily open the stop input
(open A1-02).
xIn two-wire control, if the soft starter tripped with a start signal present, remove the
start signal (open A1 to 01, 02).
The Reset button is located on the front of the unit, above the adjustment switches.
The soft starter will trip again immediately if the cause of the trip still exists.