5. Modbus parameter overview in device menu
Devicemenuparameterscan also be setviathe AUMA CDT software.Forinformation
on AUMA CDT, refer to the operation instructions and our website at www.auma.com.
For further information on these parameters and all other settings, refer to the Manual
(Operation and setting).
Table 4:Modbus parameters Setting valuesMenuSetting valuesMenu
Device configuration M0053Customer settings M0041
Modbus M0799Modbus M0341
Redundancy M0800MD1 slave address M0342
None (default value)
1 ... 247, default value = 247
AUMA redundancy IBaud rate M0343
AUMA redundancy II
1 ... 247, default value = 247
Loop redundancyBaud rate M0343
Connection type M1967Auto (default value)
AUMATIC .2 (default value)9.6 kbit/s
AM Triple Play19.2 kbit/s
AC 01.138.4 kbit/s
AM/VM 0...1000 ‰57.6 kbit/s
AM/VM 0...100 %115.2 kbit/s
DeviceNet like AC 01.1Parity/stop bit M0782
Even, 1 stop bit (default value)
Odd, 1 stop bit
None, 2 stop bits
None, 1 stop bit
Monitoring time M0781
0.1 ... 900.0 [s] seconds, default value = 15.0 [s]
Response Timeout M0916
0.1 ... 5.0 [s] seconds, default value = 2.5 [s]
Bus termin. ch 1 M2566
Function not active (default value)
Function active
Bus termin. ch 2 M2935
Function not active (default value)
Function active
Self.ret. fieldbus M2896
Off (push-to-run op.) (default value)
OPEN
CLOSE
OPEN and CLOSE
OPEN & CL w/o STOP
Fieldbus comm. eval. M2897
Level controlled (default value)
Edge controlled
Information MD2 slave address M0409 menu will only be available if parameter Redundancy
M0800 has been set to value AUMA redundancy I. For settings AUMA redundancy
II and Loop redundancy, the address of the second channel is automatically assigned:
MD1 slave address = MD2 slave address
Information Bus termin. ch 1 M2566 and Bus termin. ch 2 M2935 menus will only be available
ifparameterRedundancy M0800 hasbeenset to valueAUMA redundancy I or AUMA
redundancy II.
9
Modbus parameter overview in device menu