Operational Instruction (Original) Distribution box Type 07-5103-…./…., 07-5105-
…./…., 07-5106-…./…. and 07-5107-…./….
BARTEC
Varnost d.o.o.
Cesta 9.avgusta 59
1410 Zagorje o Savi
Slovenia
Tel.: +386 59 221 471
Fax: +386 59 221 470
info@ artecvarnost.si
www. artecvarnost.si
Reservation Technical data su ject to change without notice. Changes, errors and
misprints may not e used as a asis for any claim for damages.
EN 2/3
– 11 01 301 (issue No I / 2.11.2016)
The distri ution ox
specified temperature class and the tempera-
ture range indicated for it (see type la el).
The distri ution ox
may e operated only if it
is clean and not damaged in any way. Dust
deposits > 5 mm (> 0.2 in) must e removed.
As for distri ution
dust, the ignition temperatur
mixture and the glowing temperature of the
dust concerned must e greater than the
maximum surface temperature of the distri u-
tion ox taking into account of the given safe
factor specified in EN 60079-0.
Utilization in areas other than
the modification of the product y anyone other
than the manufacturer is not permitted and will
exempt BARTEC Varnost
defects and any further lia ility.
The generally applica le statutory rules and
other inding direc
tives relating to workplace
safety, accident prevention and environmental
protection must e o served.
O serve the applica le laws and directives
when commissioning or restarting operation.
Always follow the safety instructions on the
operating equipment.
Marking
Particularly important points in these instruc-
tions are marked with a sym ol:
DANGER indicates a hazardous situation
which, if not avoided, will result in death
serious injury.
WARNING indicates a hazardous
which, if not avoided, could
serious injury.
CAUTION indicates a hazardous situation
which, if not avoided, could result in minor
moderate injury.
NOTICE is used to address practices not
related to personal injury.
Note
Important instructions and information on
effective, economical and environmentally
compatible handling.
2014/34/EU
as well as
EN 60079-0:2012/IEC 60079-0:2011
EN 60079-7:2007/IEC 60079-7:2006-07
EN 60079-11:2007/IEC 60079-11:2006
EN 60079-31:2009/IEC 60079-31:2008
as well as
EN 62208:2011/IEC 62208:2011
EN 60445:2010/IEC 60445:2010
EN 60529:1991 + A1:2000
Transport, storage
Risk of injury due to heavy loads.
Use an appropriate carrying aid or an
appropriate means of transport (e.g. a fork-
lift) with an adequate load-carrying a ility.
Ensure that the lifted load will not tip over
or slip off.
Damage through incorrect transport or
incorrect storage.
Transport the distri ution ox
packaging, handle with
drop.
Store the distri ution ox
packaging.
Assembly, installation, and
commissioning
Risk of serious injury due to incorrect
proceedings.
Only qualified personnel who are
authorized and trained to assem le electri-
cal
components in hazardous (potentially
explosive) areas may do any of the as-
sem ly, disassem ly, inst
commissioning work.
For assem ly and operation of explo
protected electrical equipment, relevant in-
stallation and operating regulations are
adhere (e.g. Betr.SichV, IEC/EN 60079-
and series DIN VDE 0100).
The data on the la el and the EEC design
test data are to e o served. Further tech-
nical information is
catalog and on the product itself.
User may not drill holes in the
oxes and add terminals
Do not open the distri ution ox
energized.
Death or serious injury because of a miss-
ing protective earth connection.
Metallic conductor entries must e con-
nected to the ground. With plastic enclo-
sures, BARTEC Earth loc or appropriate
ground plates serve the similar purpose.
Risk of serious injury due to incorrect pro-
ceedings.
The assem ly with connecting and/or rail-
mounted terminals must e implemented
under the consideration o
inspection certificate.
Check when assem ling:
• Use suita le tools.
•
Pay attention to the type of mounting
required (for fitting into enclo-
sure/attachment with distri ution ox).
• For distri ution ox
steps must e tak
operation, for example rain protected
roofs, and if necessary, sufficient enclo-
sure protection.
Installation
Risk of injury due to incorrect proceedings.
Extensions or modifications to the distri u-
tion ox are only permissi le if the manu-
facturer’s approval is o tained first.
The IEC/EN60079-14 must e o served.
Installations for the highly com usti le rang
must exhi it an EEC design inspection certifi-
cate.
Installation of these components must
take place in such way, so that at lea
enclosure remains IP54.
Connection of ca les and conductors to equip-
ment in hazardous areas require Ex
entries, which are suita le for re
and conductor types. They must possess the
protection type e” and contain a suita le se
gasket, so that the prote
enclosure remains at least IP54.
Unused holes for ca le en
sealed with Ex-
certified plugs. Connection of
ca les and conductors of zone 21 and 22
equipment require at least the protection cla
IP 66.