AC FUSE 15A
ST C NC NO
+-+-
AC AC
BATTERY DC OUTPUT TRANSFORMER
POWER SUPV
ON
OFF
PM
AD
BA
FAULT RELAY
AC
DC
FAULT
G
G
Y
AC
BATT FUSE 10A
XP10
BASE
MAX. OUTPUT
12 OR 24 VDC, 10A
DC POWER SUPPLY
AND BATTERY CHARGER
12
24
ADJ
Output Voltage Switch
Voltage Adjustment
12vdc (11.5 - 14.0)
24vdc (23.0 - 28.0)
AC Input Fuse - 15ABattery Fuse - 10A
Power Monitor Options LED Status Indicators
28-32 VAC Input
From Transformer
To Standby Battery
DC Output
to Devices
+ -
+
-
XP10 DC Power Supply and Battery Charger
© 2005-2006 BASE Electronics, Inc.
Limited Warranty
This XP Series DC Power Supply Module is warranted by BASE Electronics against manufacturing defects in materials and
workmanship for a period of 2 years from date of purchase. During this period, any warranty repair required will be made at no
charge for parts or labor. This warranty does not apply to any work or materials provided by any outside persons or technicians
involved in the installation, unauthorized repair, connection, or testing of this product. This warranty does not cover any
damage or failure caused by or attributable to Acts of God, abuse, misuse, improper or abnormal usage, faulty or improper
installation or maintenance, neglect or accident. BASE Electronics is not responsible or liable for any special, consequential or
indirect damages resulting from or in connection with the use or performance of this product as pertaining to economic loss,
property loss, costs for removal or installation, or loss of revenues or profit. Except as provided herein, BASE Electronics
makes no expressed or implied warranties. The duration of product performance for its intended purpose is limited to the
duration set forth herein.
For Warranty or other repair, send the product postage prepaid to BASE Electronics and include Sender's name, company,
address, phone and brief problem description. BASE Electronics will notify sender of any required repair costs not covered
under this warranty prior to making such repairs.
This Warranty gives you specific legal rights. You may have other rights that vary from state to state.
LISTED
®
U
The information in this manual is believed to be accurate in all respects. However, BASE Electronics cannot
assume responsibility for any consequences resulting from the use thereof. The information contained herein is
subject to change and BASE Electronics may issue a revision to incorporate such changes at any time.
BASE Electronics, Inc. • 2856-C Janitell Road • Colorado Springs, CO 80906 • (719) 540-9697 • Fax (719) 540-9698 BASE
• Indoor Temperature Range: -25°C. to +70°C. XP10 Specifications
• Electrical
AC Input: 28-32 VAC, 50-60 Hz
Maximum Output: 13.8 or 27.6 VDC, 10A (at 25°C)
Maximum No-Load Current Consumption: 125mA (0.125 A)
Maximum Battery Charge Current : 700mA (0.700 A)
Battery Type: Sealed Lead Acid Gel Cell Type Only
Fault Supervision Relay Form-C Contact Rating: 2A
Connections: Captive Screw Terminals for #14 to #22AWG Wire
AC Input Fuse: 15A, Type 3AG, Fast Blow
Battery Fuse: 10A, Type 3AG, Fast Blow
• Size: 4.00 wide by 5.75 long by 2.38 high (inches)
• Mounting: (4) 1/4 inch high nylon standoffs included
• Controls and Indicators
Output Voltage is Single-Switch selectable and adjustable: 12 or 24 VDC
Fault Supervision Select 4-pole Dip Switch: PM, BA,AC, AD
3 LED Indicators for AC Power (Green), DC Power (Green), Fault (Flashing Yellow)
• Special Features
On-board selectable Fault Supervision with Relay Form-C Contact Ouput
Charger for Lead Acid Gel Cell Batteries
Separately fused AC input and Battery circuits
Calculating Total Current Draw
The Total Current Draw must not exceed 10 Amps, or the power supply
may overheat. The XP10 has built-in current limit/thermal overload
protection and the DC output will turn off if either occurs.A better design
guidline (to prevent early power problems and extend the life of power
supplies and batteries) is to limit the calculated draw to 50-75% of Max.
(5.00-7.50A), especially when charging batteries.Also, future system
expansion should be considered in your load calculations.
Cable Resistance
When powering devices over considerable distances, cabling resistance
may be so high that the voltage available at the device has dropped to an
unacceptable level. To prevent this from occuring, system cabling should
be designed with adequate sized conductors.
Heat Buildup
A by-product of all step-down power supplies/regulators/transformers is
heat. Continuously pushing power supplies to their limits will maximize
heat dissipation and buildup within power cabinets - which will thereby
work to reduce the life of these components. Consider their location or the
use of cabinet grills or fans to reduce heat buildup.
Power Distribution
Separately fusing output devices or groups of output devices greatly
reduces trouble-shooting efforts. The larger the power supply and number
of devices powered, the greater the need for power distribution. BASE has
a variety of power distribution products that help speed installations while
providing easier maintenance and a custom professional appearance.
=
Total
Current Draw
+ No-load Current Draw (See Specifications)
+ Max Battery Charge Current (See Specifications)
+ Estimated Load Current of Powered Devices
+ Estimated Load Current (for Future Expansion)
Power System Design Tips
+
-12V Battery
+
-12V Battery
RED
YELLOW
JUMPER
BLACK -
+
To Power Supply
Battery Terminals
Battery Wiring - 24 VDC
+
-12V Battery
RED
BLACK -
+
To Power Supply
Battery Terminals
Battery Wiring - 12 VDC
Power Status LED Indicators
Green (G), Yellow (Y)
AC POWER
DC POWER
FAULT
G
G
Y
ON = AC power from transformer present.
OFF = AC power fault/failed.
ON = DC output power present.
OFF = DC power fault/failed..
FLASH = Selected fault condition present.