Braeburn 140202 Istruzioni per il montaggio

Premier 2-Zone Controller
model 140202
Installer Guide
Controlador de 2 zonas premier
modelo 140202
Guía de instalación
Régulateur 2 zones de première qualité
modèle 140202
Guide de l’installateur
English, 2-12
Español, 13-23
Français, 24-34
140202-100-03

CONTENTS
1 Specifications 4 Configuration
2 Suitable Mounting Locations 5 System Checkout
3 Wiring Diagrams 6 Operation
Warning
• Read all of the instructions before proceeding.
• Always turn off power to the heating/air conditioning system prior to installing or adjusting the
Premier 2-Zone Controller. Wire the entire panel before applying transformer power.
• This controller should only be installed and configured as described in this manual. Any other use is
not recommended and will void the warranty.
1Specifications
• Storage temperature: -40º–150ºF
(-40º–65ºC)
• Operating temperature: -20º–125ºF
(-30º–50ºC)
• Operating humidity: 5–95% RH
• Voltage: 24 VAC, 60Hz
• Max. damper power: 35 VA @ 24 VAC
• Dimensions: See Figure 1
6.00”
1.25”
6.00”
Figure 1
2

2Suitable Mounting Locations
Mount the Premier 2-Zone Controller panel near the HVAC equipment (see Figure 2). The panel can be
mounted in any orientation on a wall, stud, roof truss, or the return-air plenum. For appearance, mount the
panel level.
Remove the panel cover and use the base as a template to drill mounting holes 4.5” apart (see Figure 3).
Attach the panel with appropriate screws (not included). Use mounting anchors as needed for drywall or
plaster installations.
return air
ducts
return air
plenum
bypass
duct coil
supply air
sensor
zone dampers
electric or
barometric
bypass damper
filtration
system
furnace
typical mounting location
4.50”
Figure 3
Figure 2
3

3 Wiring the Panel
Always turn off power to the heating/air conditioning system prior to installing or
adjusting the Premier 2-Zone Controller. Wire the entire panel before applying
transformer power.
Use the following general wiring instructions for all systems. Specific wiring will vary depending on the
equipment and type of system (conventional or heat pump).
3.1 Damper Wiring
Install the system dampers using the instructions provided
by the manufacturer.
Connect the dampers to the zone panel as shown for
either a 2-wire or 3-wire damper.
The sum of all dampers powered by the zone panel
should not exceed 35 VA at 24 VAC. Use a slave relay if
additional damper power is required.
Max. damper VA per panel 35 VA @ 24 VAC
M
M
PO
COM
PC
Zone Panel 2-Wire Damper
PO
C
PC
PO
COM
PC
Zone Panel 3-Wire Damper
4

3.2 Thermostat Wiring
Install the system thermostats using the instructions
provided by the manufacturer.
Connect the thermostats to the zone panel as shown.
Notes:
• Use only single stage conventional thermostats.
• Wiring to the C terminal is required only for
thermostat power.
• E terminal at thermostat 1 is for connecting an external
emergency heat switch (heat pump systems only).
3.3 External Emergency Heat Switch
For heat pump systems requiring an external emergency
heat switch, connect as shown.
Note: Equipment and zone panel transformers should be
on the same phase.
E
R
Y
G
W
C
Rh
Rc
Y
G
W
C
Thermostat Zone Panel
5
Switch
(2A min.)
RH
RC
Y
G
W1
EH
W2
O/B
C
EQUIPMENT
THERMOSTAT 1
E
R
Y
G
W
C
Zone Panel

3.4 Transformer Wiring
Install the transformer using the instructions provided
by the manufacturer. Size the transformer to the damper
requirements. The zone panel has a built-in, self-resetting
fuse. The maximum damper power per panel is 35 VA at
24 VAC.
Connect the transformer to the zone panel as shown.
Note: Additional dampers or dampers with a higher current draw will require the use of a separate
slave relay.
24V
24C
CC
HOT
Dedicated
Zoning Transformer
Zone
Panel
6
3.5 Conventional System Wiring
Note: For a heat pump system, see Section 3.6.
Connect a conventional heating system to
the zone panel as shown.
For a single stage heating and cooling
system, the 2nd stage connections are
not used.
For a system using a dual transformer,
open jumper J1 (see Configuration
section, Figure 4). Make sure the neutrals
(common) are connected.
RH
RC
Y
G
W1
EH
W2
O/B
C
C
HOT
1st stage
compressor
control 1st stage
fan
control
1st stage
heat
control 2nd stage
heat
control
24 VAC

3.6 Heat Pump System Wiring
Connect a single or multi-stage
heat pump system to the zone panel
as shown.
Conventional thermostats must be used
with a heat pump system. However,
emergency heat will be controlled by
the panel emergency heat switch or the
optional remote emergency heat switch.
For a single-stage system, the auxiliary
heat control is not used.
• Use DIP switch 1 to select between conventional and heat pump system.
• Use DIP switch 3 for heat pump reversing valve control. Setting 0 means that the O/B terminal is
active in a cooling call. Setting B means that the O/B terminal is active in a heating call.
RH
RC
Y
G
W1
EH
W2
O/B
C
C
HOT
1st stage
compressor
control 1st stage
fan
control
aux heat /
E-heat
control reversing
valve
24 VAC
7

Figure 4
8
4Configuration
Use the following instructions to configure the Premier 2-Zone Controller.
1. Open J1 jumper for dual transformer installations.
2. Open J2 short cycle protection jumper for system test.
Note: Replace J2 when system testing is completed or leave J2 open if compressor has built in
short cycle protection.
FLASHING
WHEN NORMAL
Braeburn
2-Zone
JI REMOVE TO SEPARATE
RH AND RC TERMINAL
J2-SHORT CYCLE
PROTECTION
EMERGENCY
HEAT
ON OFF
RH
RC
Y
G
W1
EH
W2
O/B
C
EQUIPMENT
HEAT PUMP
DUAL FUEL
O
ELEC/HP
15
ACTIVE
ZONE1
NON HP
NORMAL
REV VALVE B
FAN GAS
OPP CALL 20
LOCKOUT NONE
PRIORITY ALL
J2 jumper
J1 jumper

9
3. Set the DIP switches to meet system requirements.
Switch Label Function
1 Non-HP / Heat Pump Set to NON-HP for conventional equipment. Set to HEAT PUMP for
heat pump equipment.
2 Normal / Dual Fuel HP 1st stage lockout when 2nd stage calls
3 Rev Valve B / O O/B terminal active in heating (B position) or cooling (O position)
4 Fan Gas / Elec & HP Fan controlled by HVAC system or panel
5 Opp Call 20 / 15 Opposite call answer time in minutes
6 Lockout None / Active 2nd stage lockout without 2 zones calling
7 Priority All / Zone 1 Changeover priority zone 1 or first call
5System Checkout
After the wiring and configuration is complete, use the following checklist to verify the panel operation
is correct.
[ ] Make sure the Emergency Heat Switch is in the Off (right) position.
[ ] Open jumper J2 by moving cap from both pins to only one pin.
[ ] Use table and diagram in section 4 of this installer guide or inside the zone panel cover to
verify DIP switches are set properly.
[ ] Make sure no zones are calling by turning off zone 1 and zone 2 thermostats.
[ ] Apply 24 VAC power to the panel.
[ ] Verify green power LED near 24 VAC terminals is lit.
HEAT PUMP
DUAL FUEL
O
ELEC/HP
15
ACTIVE
ZONE1
NON HP
NORMAL
REV VALVE B
FAN GAS
OPP CALL 20
LOCKOUT NONE
PRIORITY ALL

10
[ ] Verify green heartbeat LED in middle of panel is pulsing.
[ ] Verify zone LEDs near damper terminals are green.
[ ] Switch zone 1 thermostat to heat mode, and call for heat in zone 1 by raising set
temperature above room temperature.
[ ] Verify zone 1 damper LED stays green (open) and zone 2 damper LED changes to red
(closed).
[ ] Verify heating system is operating, air is moving out zone 1 vents, and zone 2 vents have
minimal airflow.
[ ] Switch zone 2 thermostat to heat mode, and call for heat in zone 2 by raising set
temperature above room temperature.
[ ] Verify zone 1 damper LED stays green (open) and zone 2 damper LED changes to
green (open).
[ ] Verify heating system is operating and air is moving out into zone 1 and zone 2.
[ ] If installed, verify emergency heat remote and panel switch. Return E-Heat switches to
normal position when test is complete.
[ ] Return zone 1 thermostat to the off position. Verify zone 1 damper LED turns red and
zone 2 damper LED stays green.
[ ] Verify heating system is operating, air is moving out zone 2 vents, and zone 1 vents have
minimal airflow.
[ ] Return zone 2 thermostat to the off position. Verify system fan shuts off at the end of
90-second purge cycle.
[ ] Verify zone LEDs near damper terminals are green.
[ ] If the outside temperature is acceptable, repeat the above steps in cooling mode.
Cooling will not work if E-Heat is on.
[ ] Restore thermostats and replace J2 jumper if short cycle protection at zone panel
is required.