Installation Instructions
SYSTXBBECC01--B
EvolutionRConnextControl
NOTE: Read the entire instruction manual before starting the installation.
NOTE:Please refer to the literature provided with the connected HVAC equipment
for more details on system operations with specific pieces of equipment.
The features and functions outlined in the Installation Instructions reflect Version 1
software. See the Evolution Connex product page on the HVACPartners.com website or
the Downloads section of the www.MyEvolutionConnex.Bryant.com website for the
latest software release and literature.
US Patents: CarrierrU.S. Pat No. 7,243,004, CarrierrU.S. Pat No. 7,775,452,
pointSETtU.S. Pat No. 7,415,102

TABLE OF CONTENTS
PAGE
1.Safety Considerations 1.............................................
2.Introduction 2.....................................................
3.Quick Start 3......................................................
3.1. Set Time and Date 3............................................
3.1.1. Manually Adjust Time and Date 3............................
3.1.2. Setup Time Zone 4........................................
3.1.3. Enable Time Synchronization 4..............................
3.2. Set Dealer Information 5........................................
4.Installation 7......................................................
4.1. Overview 7...................................................
4.2. Check Equipment 7............................................
4.3. Location 8....................................................
4.3.1. Wall Control 8...........................................
4.3.2. Remote Room Sensors 9...................................
4.3.2.1.Remote Room Sensor Averaging 9...........................
4.3.3. Smart Sensors (for zoning applications) 10.....................
4.4. Wiring Considerations 10........................................
4.4.1. Shielded Wire 13.........................................
4.4.2. Damper Control Module 14.................................

TABLE OF CONTENTS (cont.)
PAGE
4.5. Mounting 14..................................................
4.5.1. Decorative Backplate 15...................................
4.6. Humidifier Connections 16......................................
4.6.1. Bypass Humidifier 16......................................
4.6.2. Fan Powered Humidifiers 16................................
5.Commissioning 16.................................................
5.1. Searching for Indoor Unit 17.....................................
5.2. Searching for Outdoor Unit 18....................................
5.3. Indoor Evaporator Selection 19...................................
5.4. Electric Heater Selection 19......................................
5.4.1. Hydronic Heat Application 20...............................
5.5. Searching SAM Module (If Applicable) 20..........................
5.6. Searching for Zones (If Applicable) 21.............................
5.7. Filter Type Selection 21.........................................
5.8. Humidifier Installation 22........................................
5.9. Ultraviolet Lights Installation 22..................................
5.10.Equipment Summary 22........................................
5.11.Airflow Verification Check 23....................................
5.12.Duct Assessment (zoned systems only) 23..........................

TABLE OF CONTENTS (cont.)
PAGE
6.Service Menu 26...................................................
6.1. Equipment Summary 27.........................................
6.2. Installation 27.................................................
6.3. Set up 28.....................................................
6.3.1. Thermostat 29............................................
6.3.1.1.Auto Mode set up 30......................................
6.3.1.2.Heat/Cool Deadband 31...................................
6.3.1.3.Offsets 32..............................................
6.3.1.4.Reset factory defaults 33...................................
6.3.1.5.Scheduling Enable 33.....................................
6.3.1.6.Smart Recovery Enable 34.................................
6.3.1.7.Room Occupancy Setup 35.................................
6.3.2. Fan Coil 35..............................................
6.3.2.1.Airflow 36..............................................
6.3.2.2.Altitude 37.............................................
6.3.2.3.Fan Coil Dehumidification 37...............................
6.3.2.4.Fan Coil G--Terminal 38...................................
6.3.2.5.Fan Coil G--Terminal Alert 39...............................
6.3.2.6.Fan Coil G--Terminal Label 39..............................

TABLE OF CONTENTS (cont.)
PAGE
6.3.3. Furnace 40..............................................
6.3.3.1.Furnace Airflow 41.......................................
6.3.3.2.AC/HP Air Flow 41.......................................
6.3.3.3.Furnace Staging 42.......................................
6.3.3.4.Furnace Airflow Limits (modulating furnace only) 43............
6.3.3.5.Furnace Off Delay 43.....................................
6.3.3.6.Altitude 43.............................................
6.3.3.7.Furnace Dehumidifier Drain 44.............................
6.3.3.8.Furnace G Terminal 44....................................
6.3.3.9.Furnace G Terminal Alert 45...............................
6.3.3.10.Furnace G Terminal Alert Label 45.........................
6.3.4. AC/Heat Pump 46........................................
6.3.4.1.Latching 46.............................................
6.3.4.2.Cooling Lockout 48......................................
6.3.4.3.Defrost Interval 48.......................................
6.3.4.4.Low Ambient Cooling 48..................................
6.3.4.5.Quiet Shift 49...........................................
6.3.4.6.AC/Heat Pump RPM Max 49...............................

TABLE OF CONTENTS (cont.)
PAGE
6.3.4.7.Defrost Fan Delay 49.....................................
6.3.4.8.Brownout Disable 49.....................................
6.3.4.9.Low Air Multiplier 50.....................................
6.3.4.10.Energy Efficiency 50.....................................
6.3.5. Heat Source Lockout 50....................................
6.3.6. Stages / Latch for 18VS 51..................................
6.3.7. Geo HP 52..............................................
6.3.7.1.Freeze Limits 52.........................................
6.3.7.2.Lockout Count 53........................................
6.3.7.3.Brownout Override 53....................................
6.3.7.4.Geothermal HP Energy Tracking 54..........................
6.3.8. Zoning (If Applicable) 54...................................
6.3.8.1.Zoning Disable 55........................................
6.3.8.2.Zone Offsets 55..........................................
6.3.8.3.Zone Airflow Limits 55....................................
6.3.8.4.Duct Assessment Time 56..................................

TABLE OF CONTENTS (cont.)
PAGE
6.3.9. Accessories 56...........................................
6.3.9.1.Filter 57................................................
6.3.9.2.Humidifier 58...........................................
6.3.9.3.Ultraviolet Lights 58......................................
6.3.9.4.Ventilator 58............................................
6.3.10. Utility Curtailment 59......................................
6.3.11. Hydronic Airflow 60......................................
6.4. Check out 61.................................................
6.4.1. Electric Heat 61..........................................
6.4.2. Furnace 61..............................................
6.4.3. Hydronic 62.............................................
6.4.4. Air Conditioning 62.......................................
6.4.5. Heat Pump Heating 63.....................................
6.4.6. Heat Pump Cooling 64.....................................
6.4.7. Humidifier 64............................................
6.4.8. Ventilator 65.............................................

TABLE OF CONTENTS (cont.)
PAGE
6.4.9. Zoning (If Applicable) 65...................................
6.4.9.1.Airflow Limits 65........................................
6.4.9.2.Damper/Sensor Check 65..................................
6.4.9.3.Zone Duct Assessment 66..................................
6.4.9.4.Sensor Type 66..........................................
6.5. Service Information 67..........................................
6.5.1. Advanced Diagnostics 67...................................
6.5.2. Fan Coil Status 67........................................
6.5.3. Furnace Status 68.........................................
6.5.4. AC Status 68.............................................
6.5.5. Heat Pump Status 69......................................
6.5.6. Geo HP Status 69.........................................
6.5.7. Zoning Status 70..........................................
6.5.8. Last 10 System Events 70...................................
6.5.9. Run/Fault History 71......................................
6.5.10. Model/Serial Numbers 72...................................
6.5.11. Service Phone Number 72..................................
6.5.12. Energy Tracking 72.......................................

TABLE OF CONTENTS (cont.)
PAGE
6.6. Refrigerant Charging: Greenspeed, 18VS, 19VS Systems 73.............
6.6.1. Charging 74.............................................
6.6.2. Pump down 76...........................................
6.6.3. Evacuation 76............................................
6.6.4. EXV Position 77..........................................
6.7. Dealer Logo 77................................................
6.8. Utility Event Setup 79..........................................
7.Wireless Setup 80..................................................
7.1. Setup and Status Information (Homeowner’s Router) 80................
7.2. Setup and Status Information (Dealer--provided Router) 84..............
8.Wiring Diagrams 88................................................
9.Statement Information 99............................................
9.1. FCC Interference Statement 99....................................
NOTE: See the Owner’s Manual for information regarding software upgrades.

1
1. Safety Considerations
Improper installation, adjustment, alteration, service, maintenance, or use can cause
explosion, fire, electrical shock, or other conditions which may cause death,
personal injury or property damage. Consult a qualified installer, service agency or
your distributor or branch for information or assistance. The qualified installer or
agency must use factory--authorized kits or accessories when modifying this HVAC
system. Refer to the individual instructions packaged with the kits or accessories
when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves.
Have a fire extinguisher available. Read these instructions thoroughly and follow
all warnings and cautions included in literature and attached to the unit. Consult
local building codes and the current edition of the National Electrical Code (NEC)
NFPA 70. In Canada, refer to the current editions of the Canadian Electrical Code
CSA C22.1.
Recognize safety information. When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal injury. Understand the
signal words DANGER,WARNING,andCAUTION. These words are used with
the safety--alert symbol. DANGER identifies the most serious hazards, which will
result in severe personal injury or death. WARNING signifies hazards, which could
result in personal injury or death. CAUTION is used to identify unsafe practices,
which may result in minor personal injury or product and property damage. NOTE
is used to highlight suggestions which will result in enhanced installation,
reliability, or operation.