_
General specications unit GB162-80 (NG) GB162-80 (LP) GB162-100 (NG) GB162-100 (LP)
Gas category Natural gas Propane Natural gas Propane
Rated thermal load btu/h 69,000 - 290,000 58,000 - 270,000
Rated heating capacity,
heating curve 176/140°F(80/60°C)
btu/h
61,400 - 255,200 51,600 - 237,600
Rated heating capacity,
heating curve 122/86°F(50/30°C)
btu/h
68,300 - 281,300
Boiler eciency at max. capacity,
heating curve 176/140°F(80/60°C)
%
8888
Boiler eciency at max. capacity,
heating curve 122/86°F(50/30°C)
%
8979
CSA Output btu/h 261,000 243,000 295,000 279,000
De-ration altitudes 2,000 - 5,500 ft % / 1,000 ft 2.22.32.02.1
De-ration altitudes 5,500 - 8,000 ft % / 1,000 ft 2.02.51.72.1
De-ration altitudes 8,000 - 10,200 ft % / 1,000 ft 2.82.02.61.9
Heating
Maximum ow temperature °F(°C) 190 (88)
Maximum working pressure (boiler) psi (bar) 50 (3.6)
Minimum water circulation volume Gal/h (l/h) 0
Flow temperature °F(°C) 86-190 (30-88), can be set on the BC10 basic controller
Resistance at ΔT = 36°F(20°C) psi (ft.hd) )
(75.4)7.51(62.3
Heating circuit volume of heat exchanger Gal (L) 1.3 (5.0)
Pipe connections boiler, without pump group.
Gas connection in Rp1“
Heating water connection in G1½’’ union nut with female thread enclosed
Condensate connection in (mm) Ø1¼” (32 mm)
Flue gas values
Condensate quantity at 104/86°F
(40/30 °C) Gal/h (L/h) )8.01(58.2)0.9(4.2
pHvalue of condensate pHapprox. 4.1
Flue gas mass ow rate, full load g/s 9.443.53
Flue gas temperature 176/140 °F
(80/60 °C), full load
°F(°C) 153 (67) 149 (65) 169 (76) 165 (63)
Flue gas temperature 176/140 °F
(80/60 °C), partial load
°F(°C) 142 (61) 136 (58) 142 (61) 136 (58)
Flue gas temperature 122/86 °F
(50/30 °C), full load
°F(°C) 118 (48) 114 (46) 124 (51) 120 (49)
Flue gas temperature 122/86 °F
(50/30
°C), partial load
°F(°C) 93 (34) 88 (31) 93 (34) 88 (31)
CO 2content at full load %9.39.69.49,7
Free fan feed pressure Inch w.c.
(Pa) )022(388.0)051(206.0
Flue gas connection
Ø ue gas system, room-air dependent in (mm) Ø 4”(100 mm)
Ø ue gas system, room-air independent in (mm) Ø 4”(100 mm) / 4”(100 mm) parallel
Electrical data
Mains connection voltage VAC, Hz120, 60
Electrical protection rating IPX4D
Fuses Amp 5
Electrical power consumption,
full load (without a pump group)
W
651401
Electrical power consumption,
partial load (without a pump group)
W
9292
Table 2 Technical specications of GB162
61,400 - 293,000 51,600 - 277,200
69,000 - 333,000 58,000 - 315,000
57,400 - 261,900 68,300 - 326,300 57,400 - 308,700
10.54