HEALTH AND SAFETY WARNING
As e dehumidifier embodies electrical and rotational equipment, ONLY competent
persons should carry out any work on is type of machine. (See warranty).
OWNER/INSTALLATION MANUAL
WALLHUNG/FLOORSTANDING
DEHUMIDIFIERS
DH44/66 RANGE
SD496251 ISS 9
01/11/16
Contents
1.1 MOUNTING, POSITION.........................................................................................................................2
1.2 WALL HANGING/FLOOR STANDING ..................................................................................................4
2.1 CONDENSATE DRAIN CONNECTION.................................................................................................5
2.2 ELECTRICAL CONNECTION................................................................................................................6
3.0 HUMIDISTAT SETTINGS.......................................................................................................................7
4.1 OPTIONAL HYGROSTAT/AIRSTAT......................................................................................................8
4.2 OPTIONAL LPHW ...............................................................................................................................10
4.3 OPTIONAL AIR FILTER.......................................................................................................................11
4.4 FRESH AIR FEATURE.........................................................................................................................12
5.1 OPERATION ........................................................................................................................................13
5.2 SERVICE NOTES ................................................................................................................................13
6.0 TECHNICAL DATA ..............................................................................................................................14
7.0 WIRING DIAGRAMS............................................................................................................................15
8.0 WARRANTY CONDITIONS.................................................................................................................19
CALOREX HEAT PUMPS & DEHUMIDIFIERS
The Causeway, Maldon, Essex CM9 4XD
Service No: +44(0)1621 857171
Tel No: +44(0)1621 856611
Fax No: +44(0)1621 850871
Website http://www.calorex.com
R


Page 2
SD496251 iss 9
For optimum performance of e dehumidifier, care needs to be taken when considering it’s
position.
1. Good air circulation.
2. The unit needs to be horizontally level.
3. At least 200mm away from ceiling and corners of e room.
4. At least 200mm service access is required.
5. If e dehumidifier is positioned on a wall, e wall needs to be load bearing. (A
plasterboard or wood cladded wall is not suciently strong).
1.1 MOUNTING, POSITION
200 MINIMUM 200 MINIMUM
200 MINIMUM
Heal and Safety
This appliance is not intended for use by persons (including children) wi reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless ey have been
given supervision or instruction concerning use of e appliance by a person responsible for
eir safety.
Children should be supervised to ensure at ey do not play wi e appliance.

Page 3
SD496251 iss 9
2)THE ISOLATOR FOR THE DEHUMIDIFIER MUST COMPLY TO THE APPROPRIATE IPX REGULATION
CAN BE WITHIN 1,25M BUT
MUST THEN BE 2,5M ABOVE
POOL SURFACE
1) N.B. THE RCD IS AN EARTH LEAKAGE TRIP & ALTHOUGH NOT ALWAYS REQUIRED
IT IS RECOMMENDED THAT IT IS USED ON ALL INSTALLATIONS. (A 30mA RCD SHOULD BE USED).
IF THE UNIT IS WITHIN 1,25M
OF THE POOL HORIZONTALLY
THEN IT MUST BE 2,5M ABOVE
THE POOL SURFACE.
ALTHOUGH THE UNIT IS 2,5M
ABOVE THE HEIGHT OF THE
POOL IT IS NOT ACCESSIBLE
FOR SERVICE & SO BREAKS
THE NEW REGULATIONS
2,5M
1,25 - 2,0M MUST BE FITTED WITH AN RCD
AND BE AT LEAST 300mm FROM FLOOR
MUST BE FITTED WITH RCD
ANY HEIGHT ACCEPTABLE
2,0-3,5M
16TH EDITION REGULATIONS AND CALOREX UNITS

Page 4
SD496251 iss 9
1.2 WALL HANGING/FLOOR STANDING
DH44 MODEL
DH66 MODEL
When e dehumidifier is unpacked it is suitable for use standing on e floor. The feet can
be adjusted to allow for unevenness in e surface. If e unit is to be mounted on a wall, e
complete package contains wall brackets and antivibration buffers. Once e unit has been hung
on e wall e floor stand arrangement can be removed. Access to e fixings for e stand
arrangement can be gained by removing e round grommets in e feet.
WALL BRACKET
MACHINE BRACKET
ANTIVIBRATION
BUFFER
POSITIONS
CHECK
BRACKET
IS LEVEL CHECK ALL
FIXINGS
ARE TIGHT
80 80 80
880
622
315
630
931
WALL
REMOVE
GROMMETS
95
MAX
30
340
274.20
294.20
FIT
ANTIVIBRATION
BUFFERS
1345
80
540
1080
80
80
622
931
CHECK BRACKET
IS LEVEL CHECK ALL
FIXINGS
ARE TIGHT
WALL BRACKET
MACHINE BRACKET
ANTIVIBRATION
BUFFER POSITIONS

Page 5
SD496251 iss 9
DH66 DEHUMIDIFIER SHOWN.
POSITIONS OF KNOCKOUTS FOR CONDENSATE DRAIN CONNECTION
2.1 CONDENSATE DRAIN CONNECTION
The condensate output and electrical connections can be at eier end of e machine, at
e side or in e back, depending on e requirements of e user. To gain access to e unit
remove e covers, unscrewing e fixing screw in bo end mouldings.The driptray can be
removed and turned round. Remove e desired knockouts, insert grommet (supplied) and route
condensate pipe rough e knockout.(Tube outside diameter 19mm).
REMOVAL OF COVERS
CONDENSATE
DRAIN
L
40
110
110
CONDENSATE
DRAIN
22
100
20%
80%
60%
40%
22
100

Page 6
SD496251 iss 9
2.2 ELECTRICAL CONNECTION
The electrical connection should be carried out by an auorised electrician, paying special
attention to e latest IEE regulations. In any case, e mains power supply should be fitted wi
a 30mA/30ms protection switch. The cable access position can be selected by e customer
from e positions shown above. Once e desired knockout has been removed a cable gland
(supplied in package) can be fitted to neaten off e hole.
The electric box is situated under e compressor cover which will need to be removed.
The connections are made to e terminal box on e outside of e electric box in e
bottom right hand corner of e dehumidifier.
The machine should be installed in accordance wi EMC2004/108/EC.
FAN MODE SWITCH
A fan mode switch is positioned on e electric box wi e following modes:
Fan continuous - continuous operation of e fan.
Fan cycle - e fan will be switched on and off automatically by e humidistat.
The mode “fan cycle” helps, especially wi a covered swimming pool, to save energy:
(but in is mode larger humidity swings may be experienced).
Aer connecting e electrical supply, e compressor cover and machine cover need to be
installed in e manner shown on page 5.
The dehumidifier is now ready to operate.
Attention. The dehumidifier should not be switched on wiout it’s covers in place.
Operation wiout a cover causes poor airflow. Due to safety features e unit will switch off aer
a short period of time.
DH66 DEHUMIDIFIER SHOWN
POSITIONS OF KNOCKOUTS FOR ELECTRICAL CONNECTION
30.00
22.00
20%
80%
60%
40%
22.00
30.00
ELECTRICAL
ENTRY POINT
ELECTRICAL
ENTRY POINT
45.00
40.00
45.00
40.00 POSITION OF
ELECTRIC BOX
CAUTION!
REMOVE COMPRESSOR TRANSPORT BLOCK BEFORE RUNNING MACHINE
TRANSPORT BLOCK

Page 7
SD496251 iss 9
3.0 HUMIDISTAT SETTINGS
The dehumidifier is provided wi automatic control by a humidistat at can be adjusted to
suit room requirements. Adjustment is by a dial at is located on e right hand side of e unit.
The dial is marked as % relative humidity. When e % relative humidity is lower, e air is drier.
To set e dial, turn it so at e requred room humidity is positioned adjacent to e
reference mark as shown below. A room relative humidity of 50% to 60% is recommended. To
operate e dehuidifier continuously or to test its operation, turn e dial to e 20% position. In
is position e fan and compressor will run continuously (aer e initial 6 minute time delay).
50%
70%
Dial set to
“comfortable”
setting
50%
70%

Page 8
SD496251 iss 9
4.1 OPTIONAL HYGROSTAT/AIRSTAT
WITH REMOTE HUMIDISTAT FITTED ENSURE HUMIDISTAT
IN MACHINE IS SET FULLY ANTI-CLOCKWISE (IE MAXIMUM DEHUMIDIFICATION)
REMOVE PINK WIRE LINK
REMOTE HUMIDISTAT CONNECTIONS
1mm SQ CABLE
100M MAX
HUMIDISTAT
(NOT SUPPLIED, WE
RECOMMEND CALOREX
PART SD385250.
SIEBE PART No.119 1701
91100) REMO
V
LIN
K
N (L2)
L (L1)
E (GND)
8
7
6
5
4
3
2
1
AIR STAT
REMOTE AIR THERMOSTAT CONNECTIONS
1mm SQ CABLE
100M MAX
AIR STAT
(NOT SUPPLIED, WE
RECOMMEND CALOREX
PART SD385251.
JAEGER TYPE TA639.01.
INTERCONTROLS TYPE
Q302.07
N (L2)
L (L1)
E (GND)
8
7
6
5
4
3
2
1
AIR STAT
BOILER DEMAND
SIGNAL VOLT FREE
HUMIDISTAT
COMMON
BOILER DEMAND
SIGNAL VOLT FREE
HUMIDISTAT
COMMON

Page 9
SD496251 iss 9
WITH REMOTE HUMIDISTAT/AIR STAT FITTED ENSURE HUMIDISTAT
IN MACHINE IS SET FULLY ANTI-CLOCKWISE (IE MAXIMUM DEHUMIDIFICATION)
REMOVE PINK WIRE LINK
COMBINED REMOTE HUMIDISTAT/AIR STAT CONNECTIONS
1mm SQ CABLE
100M MAX
HUMIDISTAT/AIR STAT
(NOT SUPPLIED, WE
RECOMMEND CALOREX PART
SD385252.
EBERLE PART No.HYG-E-7001)
N (L2)
L (L1)
E (GND)
8
7
6
5
4
3
2
1
AIR STAT
5
2
7
REMOVE
LINK
BOILER DEMAND
HUMIDISTAT
COMMON
SIGNAL VOLT FREE