Chore-Time Turbo-Cool Specifiche

Turbo-Cool™ With Open Top
6" Recirculating Evaporative Cooling
Installation & Operator’s Instruction Manual
Mv1669-018 04/01
MV1669UNovember 2018

LIMITED Warranty6" Recirculating Evaporative Cooling
2MV1669U
Chore-Time Group, a division of CTB, Inc. (“Chore-Time”) warrants new Turbo-CoolTM Open Top Evaporative Cooling
manufactured by Chore-Time to be free from defects in material or workmanship under normal usage and conditions, for
One (1) year from the date of installation by the original purchaser (“Warranty”). If such a defect is determined by Chore-
Time to exist within the applicable period, Chore-Time will, at its option, (a) repair the Product or Component Part free of
charge, F.O.B. the factory of manufacture or (b) replace the Product or Component Part free of charge, F.O.B. the factory of
manufacture. This Warranty is not transferable, and applies only to the original purchaser of the Product.
CONDITIONS AND LIMITATIONS
THIS WARRANTY CONSTITUTES CHORE-TIME’S ENTIRE AND SOLE WARRANTY AND CHORE-TIME
EXPRESSLY DISCLAIMS ANY AND ALL OTHER WARRANTIES, INCLUDING, BUT NOT LIMITED TO,
EXPRESS AND IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, WARRANTIES AS TO
MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSES. CHORE-TIME shall not be liable for any direct,
indirect, incidental, consequential or special damages which any purchaser may suffer or claim to suffer as a result of any
defect in the Product. Consequential or Special Damages as used herein include, but are not limited to, lost or damaged
products or goods, costs of transportation, lost sales, lost orders, lost income, increased overhead, labor and incidental costs,
and operational inefficiencies. Some jurisdictions prohibit limitations on implied warranties and/or the exclusion or
limitation of such damages, so these limitations and exclusions may not apply to you. This warranty gives the original
purchaser specific legal rights. You may also have other rights based upon your specific jurisdiction.
Compliance with federal, state and local rules which apply to the location, installation and use of the Product are the
responsibility of the original purchaser, and CHORE-TIME shall not be liable for any damages which may result from non-
compliance with such rules.
The following circumstances shall render this Warranty void:
· Modifications made to the Product not specifically delineated in the Product manual.
· Product not installed and/or operated in accordance with the instructions published by the CHORE-TIME.
· All components of the Product are not original equipment supplied by CHORE-TIME.
· Product was not purchased from and/or installed by a CHORE-TIME authorized distributor or certified
representative.
· Product experienced malfunction or failure resulting from misuse, abuse, mismanagement, negligence, alteration,
accident, or lack of proper maintenance, or from lightning strikes, electrical power surges or interruption of
electricity.
· Product experienced corrosion, material deterioration and/or equipment malfunction caused by or consistent with
the application of chemicals, minerals, sediments or other foreign elements.
· Product was used for any purpose other than for the care of poultry and livestock.
The Warranty and Extended Warranty may only be modified in writing by an officer of CHORE-TIME. CHORE-TIME
shall have no obligation or responsibility for any representations or warranties made by or on behalf of any distributor,
dealer, agent or certified representative.
Effective: April, 2014
LIMITED Warranty

Table of Contents
Topic Page
MV1669U * Legend: C = Customer (end user), D = Distributor (sales), I = Installer of equipment 3
LIMITED Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Support Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
DANGER : Electrical Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Materials and Tools Required for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Planning Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
System Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Framing Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Framing Diagrams for Systems with Sump at the End. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Framing for System with Sump in the Middle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Splash Guard and Pipe Hanger Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Evaporating Cooling System Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Sump Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Sump End Clamp Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Sump Support installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Attaching the Sump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Trough Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Trough Installation Continued. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Attaching the Trough to the Sump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
End Panel Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Water Deflector Installation (PVC and Metal shown) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Distribution Pipe Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
End Panel Support Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Pad Support Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Caulking the End Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Evaporative Cooling Pad Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Pad Retainer Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Trough End Insert Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Distribution Pipe Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Sump Lid Cutout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Sump Components Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Sediment Trap Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Securing Water Supply Inlet Hose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
System Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
System Operation & Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Parts Lists and Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Sump Kits 49046, 49046-3,-4,-5, and -6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
46587-XX (Metal Frame Kits), 55440-5,-20 (PVC Frame Kits), and
55438 (Frame End Kit) Turbo-Cool™ w/Open Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
46725 Center Panel Kit (to install in center of a system) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
90° Around the Corner Kit (50464) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Miscellaneous Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

General6" Recirculating Evaporative Cooling
4MV1669U
Support Information
The Turbo-Cool 6'' Recirculating Evaporative Cooling System is designed to help cool livestock and poultry
houses. The system is shipped unassembled. Using this equipment for any other purpose or in a way not within
the operating recommendations specified in this manual will void the warranty and may cause personal injury.
This manual is designed to provide installation, operation, and parts listing information. The Table of Contents
provides a convenient overview of the information in this manual. The Table of Contents also specifies which
pages contain information for the sales personnel, installer, and consumer (end user).
DANGER : Electrical Hazard
Ground all electrical equipment for safety.
All electrical wiring must be done by a qualified electrician in accordance with local
and national electric codes.
Disconnect electrical power before inspecting or servicing equipment unless
maintenance instructions specifically state otherwise.
Use a Wet Locations Outlet Box Cover when plugging the Sump Pump Cord into an
outside Outlet.
General
Safety Information
Electrical Connection
Wet Locations
Water Level Safety
Switch Cord
Sump Pump Cord
Outlet Box Cover
(230 V)

6" Recirculating Evaporative CoolingElectrical Connection
MV1669U 5
Materials and Tools Required for Installation
Socket Wrench · 5/16” 3/8”, and 7/16" Sockets · Teflon Tape
PVC Cement · Utility Knife · Saw · Tape Measure · Chalk-Line · Caulking
· Pressure Treated Lumber for Framing. See Figure 2 (on page 9)
Required fresh water supply
*Assumes 80% pad efficiency and 425 fpm (2.2 m/s) air velocity through pad. For air velocities less than 425 fpm,
the water requirement should be reduced by the ratio of the actual pad air velocity to 425 fpm. For example: given
outside air conditions of 100° F, 40% RH, two 5’ x 60’ pads/house, and ten 48" fans producing 22,000 cfm @
.10" w.c., the total air flow is 10 x 22,000 =220,000. The pad area is 2 x 5 x 60 = 600 sq. ft. The air velocity through
the pads is the airflow divided by the pad area; 220,000 ÷ 600 =367 fpm. From the chart 1.5 gpm is required per
100 sq. ft. of pad. Because the air velocity is less than 425 fpm the actual water requirement is 1.5 x 367 ÷ 425 =
1.3 gpm per 100 sq. ft. of pad. The total water required for the house is 1.3 x 600 ÷ 100 =7.8 gpm.
Water Quality: 6 - 8 PH, salt concentration less than 40,000 ppm
Trough and Sump Water Capacity:
Trough Water Capacity-is 2.25 Gal/FT. [27.9 l/m]
Sump Water Capacity- 10.5 Gallons [39.7 Liters] when full to the top of the Water Level Indicator.
Important! CTB, Inc. strongly recommends that a good alarm system should be installed
in confinement buildings to warn of power failure and high temperature.
CTB Inc. also recommends that an alternate power source be available for
confinement buildings in case of power failure.
CTB, Inc. recommends the use of a Water Level Safety Switch. The absence of
a Water Level Safety switch will void any Warranty on the Water Pump.
Outside Air Water Required in Gallons/Minute
Per 100 sq. ft. of Pad * (l/min/m²)
Temp in °F (°C) % Relative Humidity
110 (43) 10 2.9 (1.18)
110 (43) 20 2.4 (.97)
100 (38) 20 2.2 (0.90)
100 (38) 30 1.8 (0.73)
100 (38) 40 1.5 (0.61)
95 (35) 40 1.4 (0.57)
Valve-PS75LS (Sump Kit
49046)
Valve-PS75SS (Sump Kit
49046-3,-4)
Valve-PT100SS Sump Kit
49046-5,-6
Flowrate @ 5 psi (gpm) -- -- 18 gpm
Flowrate @ 10 psi (gpm) 5 gpm 8 gpm 26 gpm
Flowrate @ 20 psi (gpm) 7 gpm 11 gpm 37 gpm
Maximum Water Pressure 100 psi 50 psi 25 psi
Submersible Pump Options
Sump Kit Part No. /
Maximum System Length
(ft)
Part No. Model PH HZ Run Amps Start Amps 49046 49046-3 49046-4
52075 EP52X 1 60 3.4 7.2 65 75
52074 EP72X 1 60 4.3 7.7 80 90 110
49367 DOC7T 3 50 1.6 6.4 65 75
52075 EP52X 1 50 2.8 7.9 50 55
52074 EP72X 1 50 3.2 8.5 65 75 90

Planning Information6" Recirculating Evaporative Cooling
6MV1669U
System Layout
The Sump Assembly can be installed anywhere within a system following these guidelines....
•The maximum length of the system is determined by the Pump used (See “Submersible Pump
Options” on page 5). Maximum system length includes the length of system on both sides of the
Sump in "Sump in the middle" and "around the corner" systems.
•A system can turn 90° around a corner with the use of a 50464 Corner Kit. Install the Sump on the wall
with the longest Pad Length.
•The maximum amount of slope is 1-1/2"[38 mm] per system. The Sump end must be level with, or
lower than the rest of the trough.
Planning Information
Mv1669-019 04/01
2 3
1
2
The Sump must be on Side with
the longest Pad length.
3
Item Description
Sump on End of System 1 Maximum length = 70’
Sump in Center of System 2,3 Maximum length each = 70’
2+3 Max length of system Determined by
Pump used (See page 5)
Figure 1.System Layout

6" Recirculating Evaporative CoolingPlanning Information
MV1669U 7
This page left blank intentionally.....

Framing Information6" Recirculating Evaporative Cooling
8MV1669U
Figure 2. on page 9 shows two options for installing the cooling pad relative to the
tunnel curtain and provides information for the Evaporative Cooling System opening
with Sump on either end. See Figure 3. on page 10 for opening information for
Evaporative Cooling System with Sump in the middle
It is recommended to frame the Pad opening using treated lumber.
1.Determine the location of the bottom stringer. See Figure 2, Item 3.
Use Wood or Lag Screws to secure the Bottom Stringer to the Studs.
The Lower Stringer must be capable of supporting 30 lbs/ft [45 kg/m] plus
3 lbs/ft [4 kg/m] for each foot of Cooling Pad Height.
Example: A 6' Cooling Pad requires a Stringer capable of supporting 30 lbs/
ft + (3 lbs/ft x 6') = 48 lbs/ft.
2.Determine the location of the top stringer. See Figure 2, Item 8. The distance
between the top and bottom stringers should be 2'' [51 mm] less than the height
of the Evaporative Cooling Pads.
Example: For a 60'' [1524 mm] tall Evaporative Cooling Pad the distance
between the stringers would be 60'' [1524 mm] - 2'' [51 mm] =
58'' [1473 mm].
Note: The slope (if any) of the top stringer must be the same as the bottom
stringer.
3.Snap a Chalk-Line on the lower stringer at the locations specified in Figure 2,
Item 13. This Chalk-Line will determine the location of the lag screws for the
Trough Supports.
4.Snap a Chalk-Line on the top stringer at the locations specified
in Figure 2, Item 12 &15. This Chalk-Line will determine the location of the
Splash Plate lower holes.
5.A short section of 2 x 6 treated lumber (Figure 2, Item 20) is required beneath
the Bottom Stringer at the Sump end to provide a back support for the Sump
assembly.
Framing Information

6" Recirculating Evaporative CoolingFraming Information
MV1669U 9
Framing Diagrams for Systems with Sump at the End
3
4
20
18
2
19
21
119
2
3
21
18
10
8
7
6
9
9
11
16
17
15
14
6
13
11
12
20
Option 1 Option 2
Mv1669-006 04/01
5
1
22
Item Description Item Description
1 Curtain 12 Pad Height plus 2'' [51 mm]
2 7.5'' [191 mm] Minimum Clearance 13 1-1/4'' [32 mm]
3 14-1/2'' [368 mm] Minimum Sump Clearance 14 Bottom Stringer Chalk-Line
4 30'' - 36'' [762 - 914 mm] Walkway 15 Top Stringer Chalk-Line
56'' [152 mm] Minimum Clearance 16 19'' [432 mm] for Sump Assembly
6 2 x 6'' [38 x 140 mm] Top Stringer 17 6'' [152 mm] for Trough End Insert
7 Wall Studs 18 7-1/2'' [191 mm]
8 Pad Height less 2'' [51 mm] 19 3'' [76 mm]
9 End Framing 20 2 x 6 Sump Back Support
10 Width of Pad Bank 21 Pad Height plus 20" Min. Clearance
11 2 x 6'' [38 x 140 mm] Bottom Stringer 22 Minimum Trough Clearance 9-1/4" [23.5 mm]
Figure 2.Framing overview diagram (Sump at either end)

Framing Information6" Recirculating Evaporative Cooling
10 MV1669U
Framing for System with Sump in the Middle
Splash Guard and Pipe Hanger Installation
Note: The end holes in the Splash Guard must align with the chalk line and the end of the
first Splash Guard must be flush with the inside of the end framing. (See Figure 4.)
Secure the Splash Guards to the upper stringer, using a 1/4 x 1-1/2'' Lag Screw at each end. Secure the
Pipe Hangers to the stringer, through the Splash Guard, using (4) 1/4 x 1-1/2'' Lag Screws. Install the
remaining Splash Guards butting them tightly end to end. If the last Splash Guard is too long to fit
within the end framing, cut as shown and fasten the loose end to the Stringer with a 1/4 x 1-1/2" Lag
Screw.
MV968-32 6/99
145
6
1
2
3
Item Description
16" [152.4 mm] Minimum Clearance
for Trough End Insert
2 Cover this opening
3 18" [458 mm]
4 1/2 Total System Length rounded
to nearest 5' increment
5 Remainder of Total System Length
6 Total System Length
plus 18" [458 mm]
Note: See Figure 2 for all other framing
information
Figure 3.Frame opening dimensions for Sump in middle
Item Description
1 1/4 x 1-1/2'' Screw
2 Pipe Hanger
3 Splash Guard
4 Upper Stringer
5Chalk Line
6 Flush with edge
of end framing
7 Cut here if too long
3
4
5
66
7
1
2
1
3
Figure 4.Pipe Support and Splash Guard Installation
Altri manuali per Turbo-Cool