Daiya Electronic RTU5011 Manuale utente

Shenzhen Daiya Electronic Technology Co., Ltd.
http://daiya.en.alibaba.com/ www.daiyagsmalarm.com
GSM Controller RTU5011
User Manual
Ver 1.2 Date Issued: 2009-02-28
All Rights Reserved by Shenzhen Daiya Electronic Technology Co., Ltd.
Website: http://daiyagsmalarm.com

Shenzhen Daiya Electronic Technology Co., Ltd
http://daiya.en.alibaba.com/ www.daiyagsmalarm.com
2/31
CONTENTS
I Preface.....................................................................................................................................3
Package list.......................................................................................................................................................3
II Introduction............................................................................................................................ 4
Features.............................................................................................................................................................4
Parameter..........................................................................................................................................................5
RTU5011 interface........................................................................................................................................... 6
III Configuration guide of RTU5011...................................................................................... 7
3.1 Access setup mode................................................................................................................................ 7
3.2 Add “CS number”.................................................................................................................................... 9
3.3 Basic parameter configuration............................................................................................................10
3.4 Parameters for alarm............................................................................................................................11
3.5 ALL SMS................................................................................................................................................ 12
3.6 CS’s authority........................................................................................................................................ 13
3.7 Inputs_Outputs types........................................................................................................................... 14
3.8 Define alarm and recover sms of digital input................................................................................. 15
3.9 Digital inputs timeouts..........................................................................................................................16
3.10 Config digital inputs/outputs name.................................................................................................... 17
3.11 CS’s DIN authority................................................................................................................................ 18
3.12 Analog input alarm................................................................................................................................19
3.13 Define alarm and recover sms of AD input...................................................................................... 20
3.14 Config AD inputs name........................................................................................................................20
3.15 CS’s AIN Authority................................................................................................................................ 21
3.16 Buzzer.....................................................................................................................................................22
3.17 Tmp100 sensor (optional)................................................................................................................... 22
3.18 Internal battery (optional).................................................................................................................... 23
3.19 Realtime Interlock.................................................................................................................................24
3.20 Timers..................................................................................................................................................... 25
3.21 Weekly Timers.......................................................................................................................................26
3.22 Program Interlock................................................................................................................................. 26
3.23 Define users commands......................................................................................................................27

Shenzhen Daiya Electronic Technology Co., Ltd
http://daiya.en.alibaba.com/ www.daiyagsmalarm.com
3/31
I Preface
Thank you for using the RTU5011 GSM RTU. You will know well about the functions and operation
methods of this product quickly through this User’s Manual.
This product is mainly used for remote alarming and control application based on GSM network. Please
use it according to the parameters and technical specifications in the User’s Manual. Meanwhile, the
Notes shall be considered for the usage of radio-control products, especially GSM products. Our
Company bears no liability for property loss or bodily injury arising from abnormal or incorrect usage of
this product.
Package list
GSM RTU RS232 cable
12V Adaptor GSM antenna CD

Shenzhen Daiya Electronic Technology Co., Ltd
http://daiya.en.alibaba.com/ www.daiyagsmalarm.com
4/31
II Introduction
RTU5011 GSM RTU is designed as a cost effective remote control system alert device. It monitors up
to 8 dry contacts and 8 drivable relay outputs and 4 AD input. User-defined SMS is sent to pre-configure
mobile phone numbers when a pre-defined alarm condition happens.These pre-configured mobile
phone numbers can belong to technicians or engineers who are responsible in handling corresponding
alarms. With the aid of this GSM RTU, the alarm condition brings attention to in-charge personnel
immediately. Besides it allows those mobile phone users to trigger any relay output by using SMS. The
output can be connected with alarm indication device, such as alarm, and others.
There is a built-in microprocessor chip running on a real-time operating system. It gives immediate
response to any change in both inputs and outputs condition. A GSM modem is embedded in the GSM
RTU, user has to subscribe a SIM card for the GSM RTU. The GSM RTU can be installed in any location
under GSM coverage.
Features
8 digital inputs, connect dry contact device
8 relay drivable outputs(12V-24V),drive electricity <0.2A
4 Analog input, 0-53 Ma,10 precision
Reliable performance with built-in double watchdog
Automatic device condition report through SMS every 24 hour interval
User-defined alarm condition (normally close or open), alarm and recovery SMS message for each
alarm point; Supporting drive relay output
Maximum of 10 mobile phone numbers can be programmable
Supporting voice monitoring
Inside temperature sensor (optional)
Being available for internal battery and providing power cut off alarm (optional)
Configuration can be done via COM port.

Shenzhen Daiya Electronic Technology Co., Ltd
http://daiya.en.alibaba.com/ www.daiyagsmalarm.com
5/31
NXP
Industrial MCU
GSM Engine
Digital inputs
Relay drive output
RS-232 Interface
Power
management
Battery
DC Input
Internal
temperature
sensor
Watchdog
Audio
management
Parameter
Parameter item Reference scope
DC Power supply 9-28V DC (Standard adapter: DC 12V/1.5A)
Power consumption 12V input Max. 50mA/Average 50mA
Frequency range Dual-frequency 900/1800 or 900/1800/850/1900
SIM Card Supporting 3V SIM Card
Antenna 50 Ω SMA Antenna interface
Serial RS232
Temperature range -20-+70 °C
Humidity range Relative humidity 95%
Output drive voltage Equal to input DC voltage
Output drive power Drive voltage ≤35V, drive current ≤200mA
On state input current Max. 0.33mA
Input signal Dry contact
Exterior dimension 130×80×25mm
Weight 330 g

Shenzhen Daiya Electronic Technology Co., Ltd
http://daiya.en.alibaba.com/ www.daiyagsmalarm.com
6/31
RTU5011 interface
RTU5011 interface
LED indicator description
Indicator Status Indication description
PWR (Red) Normally light on Indicator for power supply, which will be light on when
the system is power on
NET (Green) Flicker SMS module signal indicator, which will flicker slowly
after the system is registered in GSM network
SRV (Yellow) Light on during handling
It will be light on when the system receives or sends
short messages and light off when the handling is over
ACT (Orange) Flicker
It will flicker periodically when the system is under
operation, and the interval time is 6 sec

Shenzhen Daiya Electronic Technology Co., Ltd
http://daiya.en.alibaba.com/ www.daiyagsmalarm.com
7/31
Terminal Description
AD
Device
Relay
1
2
3
4
5
1. [DC9-28V]
Terminal Description
DC positive terminal of the DC power supply (+)
GND Negative terminal of the DC power supply (- )
2. [RS232]:Connecting computer RS232 to config
3. 8 Digital input: Digital input connecting open or close contact

Shenzhen Daiya Electronic Technology Co., Ltd
http://daiya.en.alibaba.com/ www.daiyagsmalarm.com
8/31
4. 8 relay drivable output: driving relay close or open, Output drive voltage Equal to input DC voltage
Positive pole of relay coil connecting DC, negative pole of relay coil connecting DO,
5. 4 AD input: connecting analog device and receive 0 to 53 mA signal.
III Configuration guide of RTU5011
3.1 Access setup mode
Connect RTU5011 with RS232 of the computer and open the configuration software, make RTU5011
access setup mode according to the following figure.
Note: Please choose the serial port No. and rate correctly, the default communication rate is 9600;
default password is “000000”
Basic Parameters

Shenzhen Daiya Electronic Technology Co., Ltd
http://daiya.en.alibaba.com/ www.daiyagsmalarm.com
9/31
Definition: Working mode and setup mode
In setup mode, all functions is disabled, only to set parameters. And RTU5011 must be restart to enter
working mode.
In working mode, all functions is enabled, the RTU5011 can alarm and control.
NOTE
Access setup mode, the simcard and antenna is no need, but access wording mode, the simcard and
antenna is necessary.
How to know current mode:
Method 1: Check the ACT light, if the ACT light flickers twice per second, that means it is under the setup

Shenzhen Daiya Electronic Technology Co., Ltd
http://daiya.en.alibaba.com/ www.daiyagsmalarm.com
10 /31
mode currently; the flicker period of the ACT light can be up to 6 sec under the working mode
Method 2: Check the information from the serial port, if the character string of “dtu come in setup mode”
occurs, it means that RTU5011 is under the setup mode.
3.2 Add “CS number”
RTU5011 under working mode, the “CS number” can send sms commands to control RTU5011 and
receive RTU5011 sms (include alarm sms, report sms etc). User can set 10 CS numbers, CS0-CS9
Indice