Defensor Defensor H15A Manuale utente

SERVICE MANUAL
2543355 EN 1310
Adiabatic Humidifiers
Defensor PH15/PH15A
Defensor PH27/PH27A
Defensor PH28/PH28A
For internal use only!


3
Contents
1 Introduction 4
2 Working with the service and diagnostic level 5
2.1 Overview service and diagnostic level 5
2.2 Settings in the service level 6
2.2.1 Viewing/deleting the error list 6
2.2.2 Setting the correction value for the internal humidity sensor 6
2.2.3 Setting the correction value for the external radio humidity sensor 7
2.2.4 Selecting the signal source from which the actual humidity value is taken 7
2.2.5 Modifying the remaining operation time until
a filter change warning is triggered 8
2.2.6 Calling the diagnostic level 8
2.2.7 Setting the unit type 9
2.2.8 Interrogation of the software version 9
2.3 Diagnostic level 10
2.3.1 Selecting the diagnostic level 10
2.3.2 Operating status of the carriage/rear cover lock switch 10
2.3.3 Operating status of the leakage sensor (option) 10
2.3.4 Operating status of the level switch 11
2.3.5 Operating status of the safety switch 11
2.3.6 Opening and closing the inlet valve Y1 12
2.3.7 Opening and closing the inlet valve Y2 12
2.3.8 Checking the fan levels 13
2.3.9 Switching on and off the centrifuge/drum drive 13
2.3.10 Checking the error relay 14
2.3.11 Checking the error LED (red) 14
2.3.12 Checking the operation LED (no function) 15
2.3.13 Checking the safety valve relay KY1 15
2.3.14 Checking the buzzer 16
2.3.15 Resetting the unit to factory default settings 16
3 Installation of options 17
3.1 Installation of the silver ionization (for PH15/PH15A only) 17
3.2 Installation and commissioning of the external radio humidity sensor 20
3.3 Installation of the leakage sensor (PH15/PH15A and PH27/PH27A) 23
3.3.1 Installation of the leakage sensor (PH15/PH15A) 23
3.3.2 Installation of the leakage sensor for PH27/PH27A 25
4 Replacing unit components 27
4.1 Replacing the level switch/safety switch 27
4.1.1 Replacing the level switch/safety switch on the PH15/PH15A 27
4.1.2 Replacing the level switch/safety switch on the PH27/PH27A 28
4.1.3 Replacing the level switch/safety switch on the PH28/PH28A 29
4.2 Replacing silver ionization rods 31
4.2.1 Replacing silver ionization rods on the PH15/PH15A 32
4.2.2 Replacing silver ionization rods on the PH27/PH27A 33
4.2.3 Replacing silver ionization rods on the PH28/PH28A 34
4.3 Replacing the control board 35
5 Fault elimination 37
5.1 Event messages 37
5.2 Warning messages 37
5.3 Error messages 38
5.4 What, if...? 39
6 Appendix 41
6.1 Wiring diagram PH15/PH15A 41
6.2 Wiring diagram PH27/PH27A 42
6.3 Wiring diagram PH28/PH28A 43

4
1 Introduction
This service manual is meant for well trained service personnel, which is entrusted with the service
and repair work on the Defensor PH15/PH15A, Defensor PH27/PH27A or Defensor PH28/PH28A.
The service manual is a supplement of the existing operating instructions of the Defensor PH15/
PH15A, Defensor PH27/PH27A and the Defensor PH28/PH28A. It is assumed that the service per-
sonnel in charge with service and repair work has read and understood these operating instructions,
particularly the safety instructions.

5
Cover
Closed
Leakage sensor
Open
Float switch
Closed
Sec.float switch
Closed
Valve Y1
Closed
Valve Y2
Closed
Error History
8/8/6/6
Calibr. Internal
+ 2%rH Act:38%rH
Calibr. Radio
+ 2%rH Act:38%rH
Act.Value Source
Internal
Filter
0000
Diagnostic
Program
Model type
PHXX
2 Working with the service and diagnostic level
2.1 Overview service and diagnostic level
Software
VX.XX
Drive
Off
Error relay
Off
LED1 Error
Off
LED2 Operation
Off
Relais KY1
Off
Buzzer
0
Fan power
0
EEPROM
Clear
Code
8808
+>3 s
Code wrong
Service level Diagnostic level
Call service level: Press both arrow keys until the
code entry display appears (approx. 3 seconds).
**
PHXX
Act 38%rH B2
Act 38%rH B2
Set 45%rH
PH28/PH28A
PH15/PH15A / PH27/PH27A

6
2.2 Settings in the service level
2.2.1 Viewing/deleting the error list
Delete error list:
press <Enter> key >3 seconds
With this function you can view the error list with the last 4 malfunctions occurred and if required,
delete the error list.
Note: The error list can give you important information for the elimination of malfunctions.Therefore
the error list should be deleted only, after a possible malfunction has been eliminated.
Error History
Error History
1/4/1/2
(see chapter 2.2.8)
(see chapter 2.2.2)
With this function you can determine a correction value, if the actual value of the integrated humidity
sensor deviates from the value of a certified humidity measuring instrument.
Note: Before the sensor is calibrated or the correction value is determined, the unit should have been
some hours in the operation, so that the air around the sensor can adapt itself to the ambient air.
Setting range: -20 %rh ... +20 %rh
Factory setting: 0 %rh
2.2.2 Setting the correction value for the internal humidity sensor
Calibr. Internal
+02 %rH
Calibr. Internal
New Value
Calibr. Internal
Old Value
Calibr. Internal
+02%rH Act:38%rH
(see chapter 2.2.1)
(see chapter 2.2.3)
modify
confirm
cancel
- 20%rh ... + 20%rh

7
Act.Value Source
Internal
Act.Value Source
New Value
Act.Value Source
Old Value
Act.Value Source
Internal
2.2.4 Selecting the signal source from which the actual humidity value is taken
(see chapter 2.2.3)
(see chapter 2.2.5)
modify
confirm
cancel
Intern, Radio 1, Radio 2,
Radio 3 or Radio 4
With this function you can determine from which signal source the actual humidity value is taken.
Available settings: Internal (internal humidity sensor)
Radio 1 (external radio humidity sensor channel 1)
Radio 2 (external radio humidity sensor channel 2)
Radio 3 (external radio humidity sensor channel 3)
Radio 4 (external radio humidity sensor channel 4)
Factory setting: Internal
2.2.3 Setting the correction value for the external radio humidity sensor
(see chapter 2.2.2)
(see chapter 2.2.4)
modify
confirm
cancel - 20%rh ... + 20%rh
With this function you can determine a correction value, if the actual value of the external radio
humidity sensor deviates from the value of a certified humidity measuring instrument.
Note: Before the radio humidity sensor is calibrated or the correction value is determined, the radio
humidity sensor should have been some hours in the operation, so that the air around the sensor
can adapt itself to the ambient air.
Setting range: -20 %rh ... +20 %rh
Factory setting: 0 %rh
Calibr. Radio
+01 %rH
Calibr. Radio
New Value
Calibr. Radio
Old Value
Calibr. Radio
+01%rH Act:38%rH

8
Cover
Closed
Diagnostic
Program
2.2.6 Calling the diagnostic level
(see chapter 2.2.5)
(see chapter 2.2.7)
call diagnostic level
exit diagnostic level
Detailed information regarding the functions in the diagnostic level can be found in chapter 2.3
“Diagnostic level”.
Filter
0800
Filter
New Value
Filter
Old Value
Filter
0600
2.2.5 Modifying the remaining operation time until
a filter change warning is triggered
(see chapter 2.2.4)
(see chapter 2.2.6)
modify
confirm
cancel
This setting shows the remaining operation time in hours (related to the operation on fan level 1),
until the filter change warning (warning 6) is triggered.
Note: The filter change warning is triggered fixed after 6000 operation hours (related to the opera-
tion on fan level 1).
If required the remaining operation time can be modified (e.g. increasing the value, if the filters are
already very dirty). A reduction of the value (extension of the operation time) should be made only
in exceptional cases.

9
Model type
PHXX
Model type
New Value
Model type
Old Value
Model type
PHXX
2.2.7 Setting the unit type
(see chapter 2.2.6)
(see chapter 2.2.8)
modify
confirm
cancel
PH15 or PH15 A
PH27 or PH27A
PH28 or PH28A
With this setting you determine the unit type. Afterwards, in the operating display PH15 (for PH15
and PH15A) or PH27 (for PH27 and PH27A) or PH28 (for PH28 and PH28A) is displayed.
Available settings: PH15 (tank version), PH15A (fresh water version),
PH27 (tank version), PH27A (fresh water version)
PH28 (tank version), PH28A (fresh water version)
Factory setting: depending on the unit
Notes on setting: This setting must be made only after the control board has been replaced or
after resetting the unit to factory defaults.
Software
VX.XX
2.2.8 Interrogation of the software version
(see chapter 2.2.7)
(see chapter 2.2.1)
Note: This is a display function only.

10
2.3 Diagnostic level
With the different functions in the diagnostic level you can interrogate and simulate operating con-
ditions of the unit. These functions may help you to check the correct function of the unit and its
components.
When leaving the diagnostic level modified settings are reset.
2.3.1 Selecting the diagnostic level
Note: This is a display function only (no function for PH27).
Operating status: Closed (carriage/rear cover inserted and locked)
Open (carriage/rear cover not inserted or locked, lock switch is open, error
1 should be displayed).
Cover
Closed
(see chapter 2.3.15)
(see chapter 2.3.3)
Call the diagnostic level from the service level (see overview in chapter 2.1).
2.3.2 Operating status of the carriage/rear cover lock switch
2.3.3 Operating status of the leakage sensor (option)
(see chapter 2.3.2)
(see chapter 2.3.4)
Note: This is a display function only.
Operating status: Closed (contact of the leakage sensor is closed, no leakage present)
Open (leakage sensor has triggered or is defective, error 5 should be dis-
played)
Leakage sensor
Closed