HD50 - 10 - V1.0
Address Type Coil description
9 b
Protection of configuration with password: 0=no, 1=yes
Changing the parameter requires the Administrator password (see Holding
Register 10036).
Input Registers - Read-only parameters
Address Type Input Register description
Measured values and status of measurement alarms
0 SW TEMPERATURE in the set measurement unit (x10).
1 B
Alarm for temperature:
0=OFF, 1= lower threshold alarm, 2= higher threshold alarm
2 SW RELATIVE HUMIDITY in % (x10).
3 B
Relative humidity alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
4 SW DEW POINT in the set measurement unit (x10).
5 B
Dew Point alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
6 SW PARTIAL VAPOR PRESSURE in hPa (x100).
7 B
Partial vapor pressure alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
8 SW MIXING RATIO in g/Kg (x10).
9 B
Mixing ratio alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
10 SW ABSOLUTE HUMIDITY in g/m3(x10).
11 B
Absolute humidity alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
12 SW WET BULB TEMPERATURE in the set measurement unit (x10).
13 B
Wet bulb temperature alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
18 SW SOLAR RADIATION in W/m2.
19 B
Alarm for solar radiation:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
20 SW ILLUMINANCE in lux.
21 B
Illuminance alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
24 SW
ATMOSPHERIC PRESSURE in the set measurement unit (the multiplier de-
pends on the set unit).
25 B
Atmospheric pressure alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
30 SW DAILY SOLAR RADIATION in Wh/m2.
31 B
Alarm for daily solar radiation:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
32 SW CO2in ppm.
33 B
CO2 alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
86 SW RAIN RATE in counts/h.
87 B
Rain rate alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
88 SW DAILY RAIN in counts.
89 B
Daily rain alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.