Delta AlertMaxx Manuale

01992 523523
www.deltamembranes.com
AlertMaxx™
Installation & Operating Instructions Rev 4
For Ground Water (DMS-270) & Foul Water (DMS-269)
Pump Station High Level Alarm
T.
E.
W.

AlertMaxx
AM-M-V4-02.16
Legal information/Copyright
All rights reserved. Contents provided herein must neither be distributed, copied, reproduced, edited or
processed for any other purpose, nor otherwise transmitted, published or made available to a third party
without express written consent from Delta Membranes.
Subject to technical modication without prior notice.
© Delta Membranes 2016

AlertMaxx
For technical support, please call 01279 757400 3
Contents
1.0 AlertMaxx overview 4
2.0 Box contents 4
2.1 Cardboard box contents 4
2.2 AlertMaxx unit contents 4
3.0 Technical information 5
4.0 Unit location 5
5.0 Mounting the AlertMaxx unit 5
6.0 Connecting mains power to the AlertMaxx unit 6
7.0 Installing a nger oat into a ground or surface water chamber 7
8.0 Connecting a nger oat to the AlertMaxx unit 8
9.0 Installing a pendant oat into a foul water chamber 9
10.0 Connecting a pendant oat to the AlertMaxx unit 10
11.0 Activating & testing the AlertMaxx unit 11
11.1 Turning on the AlertMaxx unit for the rst time 11
11.2 Testing the AlertMaxx unit 11
12.0 Connecting external devices 12
13.0 Servicing 13
14.0 Spares 13
15.0 LED codes 14
16.0 Troubleshooting 14

1.0 AlertMaxx overview
2.0 Box contents
4 For technical support, please call 01279 757400
AlertMaxx
Ground Water version (DMS-270)
• 1 x Finger Float Switch
• 1 x Blue washer
• 1 x Green washer
• 1 x Securing nut
• 1 x Finger Float Housing
• 3 x Cable Ties
Foul Water version (DMS-269)
• 1 x Pendant Float Switch
• 2 x Cable Ties
2.1 Cardboard box contents
• 2 x Large Cable Glands
• 2 x Large Blanking Plugs
• 2 x Small Cable Glands
• 2 x Small Blanking Plugs
• 1 x 6V Battery
2.2 AlertMaxx unit contents
• 1 x AlertMaxx Unit
• 1 x Chamber Location Sticker Sheet (For AlertMaxx)
• 1 x Chamber Location Sticker Sheet (For Spurs)
• 1 x Installation & Operating Instructions (this document)
This high level alarm is designed to alert home owners when the water level in their pump chamber becomes
too high. The unit will also inform home owners when a service is due on their pump station.
CAUTION!
The AlertMaxx should be installed by a qualied tradesperson.

AlertMaxx
For technical support, please call 01279 757400 5
3.0 Technical information
AlertMaxx Specication
Size (without cable glands) W: 115mm x D: 95mm x H: 60mm
Weight 650g
Mains Supply 200-250V AC (50Hz)
Internal Battery Pb 6V - 1.2Ah
Alarm Sound Level 81db
Visual Display Red, Blue, Green LED
Operating temperature 5-35°C
Approximate Installation time 30 minutes
4.0 Unit location
The AlertMaxx must be positioned in an area where the alarm can be clearly heard and is permanently
accessible.
5.0 Mounting the AlertMaxx unit
CAUTION!
The AlertMaxx unit is not waterproof and must be installed indoors or inside a kiosk.
1. Using the template provided on page 15 of this instruction manual (gure 1), mark the xing
positions on the wall.
2. Drill the two holes and t suitable wall plugs (ensure correct wall plugs are used for the wall type).
3. Remove the screws from the front of the unit that secure the front fascia.
4. Secure the AlertMaxx unit to the wall using appropriate screws.
PLEASE NOTE
When securing the unit to the wall, avoid over tightening the screws as this may cause the box to crack.

6.0 Connecting mains power to the AlertMaxx unit
6 For technical support, please call 01279 757400
AlertMaxx
1. Insert a large cable gland into the far right hole of the AlertMaxx unit.
2. Feed the mains power cable through the right hand cable gland (large) and connect the power cable
to the terminal strip (see gure 2).
WARNING!
Ensure mains power is isolated before connecting it to the AlertMaxx unit.
Figure 2. Connecting mains
ENL
40
120
20
70
50
80
BLUE
BLACK
BROWN
BLUE
PLEASE NOTE
If you have a nger oat, move to section 7.0
If you have a pendant oat, move to section 9.0
BROWN
BLACK
ENL
40
120
20
70
50
80
Finger oat
Move to section 7.0
Pendant oat
Move to section 9.0

AlertMaxx
For technical support, please call 01279 757400 7
7.0 Installing a nger oat into a ground or surface water chamber
Care must be taken to ensure the correct type of oat switch is installed into the chamber. The AlertMaxx
is sold either with a nger oat or pendant oat. The nger oat must only be used for ground water
applications and the pendant oat must only be used for foul water applications.
1. Using the nut and washers provided, secure the nger oat to the inside of the oat housing so that the
oat rises with rising water levels (see gure 2).
2. Using the two cable ties provided, attach the oat housing to the discharge arm so it is 300mm from the
base of the chamber (see gure 3).
Figure 3. Ground Water Sump (DMS-164)Figure 2. Ground Water Float Switch
300mm
BROWN
BLACK
ENL
40
120
20
70
50
80

8.0 Connecting a nger oat to the AlertMaxx unit
8 For technical support, please call 01279 757400
AlertMaxx
Figure 4. Wiring a nger oat switch
1. Using a draw cord, pull the oat cable through the cable duct on the chamber.
2. Insert a large cable gland into the second from right hole of the AlertMaxx unit.
3. Pull the oat cable through the small cable gland on the AlertMaxx unit.
4. Connect the blue and a brown cable from the oat switch cable to the terminal strip (see gure 4).
PLEASE NOTE
If the cable supplied with the oat switch is too short, the cable can be extended using a cable with a
minimum core cross sectional area of 1mm².
ENL
40
120
20
70
50
80
BLUE
BLACK
BROWN
BLUE
BROWN
BLACK
ENL
40
120
20
70
50
80

AlertMaxx
For technical support, please call 01279 757400 9
9.0 Installing a pendant oat into a foul water chamber
Figure 6. Foul Water Sump (DMS-165)Figure 5. Foul Water Float Switch
200mm
PLEASE NOTE
The pendant oat switch should be located in a position where the oat can pivot with rising water levels
and not become obstructed (see gure 5).
Option 1 - Free standing foul pump
1. Using the cable tie provided, attach the oat cable to the discharge arm allowing the bottom of the oat
switch to hang approximately 200mm above the base of the chamber (see gure 6).
Option 2 - Guide rail mounted foul pump
1. Pull the oat cable through the oat weight.
2. Using a cable tie, secure the oat weight to the oat cable so there is 80mm of oat cable between the
top of the oat switch and the bottom of the oat weight.
3. Drill a hole through the oat bracket. Hang the pendant oat from the oat bracket so the bottom of the
oat switch hangs approximately 200mm from the base of the chamber. Once the pendant oat is at the
correct height, secure the oat cable to the oat bracket using a cable tie.
BROWN
BLACK
ENL
40
120
20
70
50
80

10.0 Connecting a pendant oat to the AlertMaxx unit
10 For technical support, please call 01279 757400
AlertMaxx
Figure 7. Wiring a pendant oat switch
ENL
40
120
20
70
50
80
BLUE
BLACK
BROWN
BLUE
1. Using a draw cord, pull the oat cable through the cable duct on the chamber.
2. Insert a large cable gland into the second from right hole of the AlertMaxx unit.
3. Pull the oat cable through the large cable gland on the AlertMaxx unit.
4. Connect the black and a blue cable from the oat switch cable to the terminal strip (see gure 7).
The brown cable should be disregarded and isolated.
PLEASE NOTE
If the cable supplied with the oat switch is too short, the cable can be extended using a cable with a
minimum core cross sectional area of 1mm².
Indice
Altri manuali Delta Sistema di sicurezza
Manuali Sistema di sicurezza popolari di altre marche

EDM
EDM Solution 6+6 Wireless-AE Manuale utente

Highway Safety Group
Highway Safety Group EA401 Manuale utente

Siren
Siren LED GSM Manuale utente

Detection Systems
Detection Systems 7090i Istruzioni per il montaggio

Se-Kure Controls
Se-Kure Controls MicroMini SK-4841 Manuale utente

Siemens
Siemens FDM273 Manuale utente