ZWS150PAF Series
INSTRUCTION MANUAL
3. Explanation of Functions and Precautions
3-1. Input Voltage Range
Input voltage range is single phase 85 ~ 265VAC ( 47 ~
63Hz ) or 120 ~ 370VDC. Input voltage which is out of
specification may cause unit damage. For cases where con-
formance to various safety specs(UL,CSA,EN) are re-
quired, input voltage range will be 100 ~ 240VAC
( 50/60Hz ).
3-2. Output Voltage Range
V.ADJ trimmer(VR51) that is nearby to output connector
is for output voltage adjustment within the range of speci-
fications. To turn the trimmer clockwise, the output volt-
age will be increased. Note over voltage protection (OVP)
function may trigger if the output voltage is increased ex-
cessively.
3-3. Inrush Current
This series has used Power Thermistor to protect the cir-
cuit from Inrush Current. Please carefully select input
switch and fuse in cases of the high temperature and re-
input the power.
3-4. Over Voltage Protection ( OVP )
The OVP function ( Inverter shut down method, manual
reset type ) is provided. OVP function operates within the
range of OVP specification.When OVP triggers, the out-
put will be shut down. The input shall be removed for a
few minutes, and then re-input for recovery of the output.
OVP setting is fixed and not to be adjusted externally.
3-5. Over Current Protection ( OCP )
Constant current limiting, automatic recovery. OCP func-
tion operates when the output current exceeds OCP speci-
fication. The output will be automatically recovered when
the overload condition is cancelled. Do not operate over-
load or dead short conditions for more than 30 seconds,
which could result in damage or insulation failure.
3-6. Over Temperature Protection ( OTP )
For /OTP, /JOTP, /TOTP, /SOTP models, OTP circuit is
built into the power supply to prevent power supply from
damage when ambient temperature over the specification.
3-7. Output Ripple & Noise
The standard specification for maximum ripple value is
measured according to measurement circuit specified by
JEITA-RC9131. When load lines are longer, ripple be-
comes larger. In this case, electrolytic capacitor, film ca-
pacitor, etc. might be necessary to use across the load ter-
minal. The output ripple cannot be measured accurately if
the probe ground lead of oscilloscope is too long.
Oscilloscope
Bandwidth : 100MHz
INPUT
L +
-
P.S. C2 C3
Load
1.5m 50ΩCable
150m
R : 50
C1 : 4700pF Film Capacitor
C2 : 100uF Electrolytic Capacitor
C3 : 0.1uF Film Capacitor
+
FG R
C1
3-8. Series Operation
For series operation, either method (A) or (B) is possible.
Method ( A )
Output
Terminal
Output
Terminal
Power
Supply
Load
Method ( B )
Output
Terminal
Output
Terminal
Power
Supply
Loa
Loa
3-9. Parallel Operation
(A) To increase the output current is not possible.