TECHNICAL DEVICE INFORMATION
1 Type and order code LA12MI LA16MI
2 Design
2.1 Degree of protection according to EN 60 529 for a compact unit or heating
element IP 24 IP 24
2.2 Installation location Outdoors Outdoors
3 Performance Data
3.1 Operating temperature limits:
Heating water flow / return flow °C Max. 55 / min. 25 Max. 55 / min. 25
Air °C -20 to+35 -20 to+35
3.2 Heating water temperature difference at
standard rating condition K55
Heat output / COP at A7 / W35 1kW / --- 12.0 / 4.67 16.0 / 4.23
at A2 / W35 1kW / --- 11.0 / 3.50 14.0 / 3.10
at A-7 / W35 1kW / --- 12.0 / 2.90 14.1 / 2.72
3.3 Sound power level 2dB(A) 62 64
3.4 Heating water flow rate m³/h 2.1 2.8
3.5 Air flow m³/h 4800 5400
3.6 Refrigerant; total filling weight Type / kgR410A / 2.3 R410A / 2.3
3.7 Lubricant; total filling quantity Type / Litre
FV50S (PVE) / 1.2 FV50S (PVE) / 1.2
4 Dimensions, connections and weight
4.1 Device dimensions without connections H x W x L mm
1410 ×1283 ×320 1410 ×1283 ×320
4.2 Device connections to heating system Inch 1 1/4” ext. thread 1 1/4” ext. thread
4.3 Weight of the transportable unit(s) incl. packaging kg165 165
5 Electrical Connection (Heat Pump)
5.1 Nominal voltage; fuse protection V / A 230 / 32 230 / 32
5.2 Norminal power consumption 1A7 W35 kW 2.57 3.78
5.3 Starting current (Inverter driven) A7 W35 A Gradual increase
from 0-12 Gradual increase
from 0-18
5.4 Nominal current A7 W35 / cosϕA / --- 11.6 / 0.96 17.1 / 0.96
5.5 Power input of integral fan and pump 3W 60 / 180 60 / 180
6 Electrical Connection (Back-Up Heater)
6.1 Nominal voltage; Frequency; Fuse protection V / Hz / A 230 / 50 / 26 230 / 50 / 26
6.2 Norminal power consumption kW 6.0 6.0
7 Heating Water Circuit
7.1 Expansion Vessel Litre / Bar 10 / 3 10 / 3
7.2 Pressure Relief Valve Bar Open 3.0 /
Close 2.65 Open 3.0 /
Close 2.65
7.3 Free pressure, heating circulating pump (max speed) kPa 83 83
8 Other design characteristics
8.1 Defrosting Automatic Automatic
Type of defrosting Reverse Cycle Reverse Cycle
8.2 Heating water in device protected against freezing yes yes
8.3 Controller internal / external External External
1) These data characterise the size and performance of the system according to EN 14511 with clean heat exchangers. Abbreviations have the
following meaning, e.g. A2 / W35: outside temperature 2°C and heating water supply temperature 35°C. A2 / W35 test, takes into account
defrosting as per EN 14511.
2) According to EN 12102, EN ISO 3744.
3) Power input to pump relates to factory setting, speed 2. Fan is variable speed, rated input relates to maximum input power.