1. Mounting the pump: The tank has two slots provided to mount the unit on a vertical surface such as an adjacent wall.
The slots are located on the ends of the tank (Fig 1). Pump must be level and the inlet must be below the boiler drain
point.
2. The pump should not be installed in a manner that will subject it to splashing or spraying.
3. The pump can be mounted in a Left Hand or Right Hand orientation allowing for cabling to the left or right (Fig 2 & 3).
Inlet water connections
1. Position pump beneath boiler condensate drain so that
condensate ows into the pump inlet freely (use any of the
three openings provided).
2. The pump will accept up to three drain lines, although care
should be used to make certain that total inow does not
exceed outow of pump. If more drains into the pump than
the rated output of the pump, tank may overow.
3. Keep plugs in unused pump inlet openings to prevent debris
from falling into the pump tank.
Outlet water connections
1. Connect the supplied 3/8” I.D. tubing to the non return
valve (Fig 1 ). For best results, secure tubing with clamps (not
provided) but do not pinch collapse or otherwise restrict the
tubing.
2. The pump is supplied with an adaptor which can be
connected to standard 22mm pipe or with associated adaptors
(not supplied) to 32mm and 40mm pipe.
3. Tubing should rise vertically but not exceed the maximum shut
off head (pumping height) of 5.5 metres above the pump.
4. At highest point angle tubing horizontally and create a
downward slope to the drainage point. Do not sharply bend
or twist the tubing in a way that might result in collapse or
restriction of the tubing. Creating a downward slope will allow
the condensate to drain by gravity and keep tubing empty.
5. If it is not possible to create a downward slope, try to create an
inverted “U” trap directly above the pump at the highest point.
6. If routing in loft, basement or other area where the condensate
hose could be exposed to freezing conditions, hose should be
insulated or changed for pre insulated version.
INSTALLATION
Figure 1 Figure 2
Figure 3
Mounting blocks
Left hand orientation
(wiring to right outlet, and hose to left)
Right hand orientation
(wiring to left outlet, and hose to right)
Non return valve
WATER DRAIN CONNECTIONS