Bus controlled
Initial enable state disabled / enabled
Itdenes the initial state of the IPinterface function when bus con-
trolled.
Enable activation telegram telegram“0”/telegram“1”
Itdenes the telegram sent totheobject “<General>IPInterface” to
enable the function.
Automatic deactivation time
(0=never) [min] 0 ... 255
Itdenestheautomatictimeafterwhichthefunctionisdeactivated.
Reset BUS object disabled / enabled
With this parameter it’s possible to enable the object “<General> Re-
setBUS”.
Telegram for reset telegram“0”/telegram“1”
Itdenesthetelegramsenttotheobject“<General>ResetBUS”to
enable the reset.
Additional function x
4 logics
20 MQTT channels
1 virtual holder
With this parameter it is possible to enable this functions:
4 logics-see“Logic”usermanual
20 MQTT channels -
1 virtual holder - is a logical function that automatically recognizes the
presence of a person in a room. This function can be used in hotels
orsimilarinstallationsandrequiresconnectiontootherdevices(see
“Virtual Holder”).
Surveillance conguration
Communication objects involved:
“<General>Alarms0-15” 4 bytes CRT
“<General>Alarms16-31” 4 bytes CRT
“<General>Alarms32-47” 4 bytes CRT
“<General>Alarms48-63” 4 bytes CRT
“<General>Alarms64-79” 4 bytes CRT
“<General>Alarms80-95” 4 bytes CRT
“<General>Alarms96-111” 4 bytes CRT
“<General>Alarms112-127” 4 bytes CRT
These objects are used to sum up the alarm status of the relative sur-
veillance channels.
KNX PARAMETER SETTINGS
Physical address main line 0 .. 255
This parameter denes the physical main address of the surveilled
devices(e.g.10.13.x-->10).
Physical address sub line 0 .. 255
Thisparameterdenesthephysicalsubaddressofthesurveilledde-
vices(e.g.10.13.x-->13).
Alarm time - hours 0 ... 255
Thisparameterdenesthesurveillance time (hours) beforesending
thealarm.Usedbythesurveillancemoduleswhenthealarmfunction
is enabled.
Alarm time - minutes 0 ... 255
Thisparameterdenesthesurveillancetime(minutes)beforesending
thealarm.Usedbythesurveillancemoduleswhenthealarmfunction
is enabled.
Warning time - seconds 20 ... 255
Thisparameterdenesthewarningtime(seconds).Thistimeindicates
how much before the end of the surveillance time a group value read is
sentonthebusthroughthe“WarningReadRequest”object.Usedby
the surveillance modules when the warning function is enabled.
Surveillance priority primary / secondary
Thisparameterdenesifthedeviceistheprimarysurveillancedevice
or if it is the secondary one. If secondary is selected, the heartbeat
period of the primary device must be aligned to the one of the primary
device itself. If no message is received in the period an alarm message
issent onthe object “<General> PrimaryAlarm” and the secondary
device starts to surveil the plant.
Primary period - time unit seconds / minutes / hours
ThisparameterdenestheunitofmeasuresofthePrimaryHeartbeat
period.
Primary period - time value 1 ... 255
Thisparameter denes thetime interval forsending the “<General>
PrimaryHeartbeat”object.
Number of surveillances 16, 32, 48, 64, 80, 96, 112, 128
Thisparameterdenesthenumberofsurveillancemodules.
Logics conguration
Communication objects involved:
“<General>Enable/DisableAllLogics” 1 Bit CW
“<General>Enable/DisableLogicx” 1 Bit CW
KNX PARAMETER SETTINGS
Logic activation telegram telegram“0”/telegram“1”
Denesthetelegramsentontheobject“<General>Enable/DisableAll
Logics”toenablethelogicfunction.
Logic x enabled/disabled state
after download disabled / enabled
Thisparameter denes thevalue set for object ““<General>Enable/
DisableLogicx”afteradownload.
Logic x enable/disable object do not use / use
Withthisparameterit’spossibletousetheobject“<General>Enable/
DisableLogicx”.
Network conguration
This function allows the device to communicate with the DNS
(DomainNameSystem)andNTP(NetworkTimeProtocol)ser-
vices,tobeconsideredmandatoryfortheETSIPconguration.
To guarantee the correct functioning of the validation of the secu-
ritycerticatesandtheidentityofthebrokertowhichtoconnect
with the MQTT service, the device must reach the NTP and DNS
services.
In addition to the MQTT part, the NTP service is required to use
the object dedicated to sending the date and time via KNX.
Communication objects involved:
“<General>AlarmDHCP” 1 Bit CRT
“<General>AlarmPing” 1 Bit CRT
“<General>AlarmDNSResolution” 1 Bit CRT
“<General>AlarmNTP” 1 Bit CRT