Egress System HRX 5000 Manuale utente

HRX 5000
Technical Manual
Version 1.2

HRX5000 Technical Manual V1.2Page 1 of 18
Contents:
Specification.....................................................................................................2
Connectors ......................................................................................................5
RS-485 Network Connectors (J6 and J7).....................................................5
RS-232 to Printer (J19) ................................................................................6
RS-232 to PC (J8)........................................................................................7
TCP/IP..........................................................................................................8
Power (J21)..................................................................................................9
Fire Alarm Input (J20).................................................................................10
Relays (J12, J15) .......................................................................................11
Remote Readers (J13, J16).......................................................................12
Remote Door Inputs (J14, J17)..................................................................13
Modem (J3)................................................................................................14
Access Control...............................................................................................15
Fire Alarm Interaction.................................................................................16
Bells...............................................................................................................16
Fire Alarm Printer...........................................................................................16
Issue History..................................................................................................18

HRX5000 Technical Manual V1.2Page 2 of 18
Specification
The HRX 5000 is a Proximity card reading terminal with TCP/IP connection,
Fire Alarm printout, Access Control for 2 doors and optional internal Modem.

HRX5000 Technical Manual V1.2Page 3 of 18
Dimensions: 280mm (W) X 170mm (H) X 60mm (D)
Display: 16 X 2 Large character LCD with LED Backlight
Display area: 100mm X 25mm
Clockings: 15,000 in circular buffer
Employees:25 to 1,000, remotely upgradeable
Firmware: Flash memory upgradeable over TCP/IP
Configuration: 1 Master, up to 15 Slaves
Reader: Type: 125KHz HID type
Range: 80mm (ISO & Clamshell badges)
30mm (Keyfobs)
Battery Backup: Lithium battery for data and clock for 3 years
Enclosure: Material –Flame retardant ABS
IP rating –standard purchase is unsealed
Optionally sealed to IP66 (hosedown)
Weight: 1 KG.
UPS: Optional external

HRX5000 Technical Manual V1.2Page 4 of 18
Connections: Power 9-12v DC 350mA to 500mA
TCP/IP 10/100 Base-T
RS/232 Second, alternative, PC connection
RS485 Slave clocks. 2 connectors for buss
RS232 Fire Alarm printer
Digital IN Fire Alarm Panel
Remote Reader A8 core up to 50 metres
Relay ASPCO up to 250V 0.5A
Door Ajar AFrom magnetic contact
Egress AFrom egress button
Remote Reader B8 core up to 50 metres
Relay B SPCO up to 250V 0.5A
Door Ajar BFrom magnetic contact
Egress B From egress button
Modem Line connector
Modem Options: Internal PSTN type
Internal GSM type (data SIMM contract required)
Power Supply: Wall Mount
IN: 240V AC
OUT: 9V DC
95mm X 45mm X 25mm

HRX5000 Technical Manual V1.2Page 5 of 18
Connectors
RS-485 Network Connectors (J6 and J7)
J6, J7
A Master HRX5000 is able to communicate with up to 15 Slave HRX5000s (or
HRX3000s) over a twisted pair RS-485 bus. 2 connectors are fitted in each
clock to make wiring easier in the field.
End to end cable length can be up to 1Km. The cable required is single
twisted pair with shield.
A suitable cable is Belden 9501 which is 24 awg (7X32) stranded, single
twisted pair with shield, PVC insulation. The RS Part Number 382-576 is for 1
box of 304 metres at £75.
J6 and J7 are connected pin to pin on the PCB. I.e. J6 pin 1 connects to J7
pin 1 etc. To connect 2 units together, wire pin 1 to pin 1 and pin 2 to pin 2.
Keep the screen pigtail as short as possible.
Pin Signal Direction
1 -ve In/Out
2+ve In/Out
3
4Screen
J6
J7

HRX5000 Technical Manual V1.2Page 6 of 18
RS-232 to Printer (J19)
J19
The terminal uses an RS-232 output to a printer for the Fire Alarm evacuation
reports. The report is triggered by a contact closure on the Fire Alarm Input. It
can also be initiated from the PC.
The data format of the transmitted data to the printer is:
9600 baud, 8 Data bits, 1 Stop Bit, No Parity.
Using the Focus Software it is possible to command test printouts to be sent
from the Terminal to the printer. It is also possible to inspect the state of the
Printer's hardware handshake line. See menu option System | Fire Alarm.
Pin Signal Direction Printer DB-25 Notes
1Power Out 5-9 volts available to power an
external line driver. Current
limited to approx 50mA
2TXD Out RXD pin 3Transmit data. 9600 baud, 8
data, 1 stop, no parity
3RXD In RTS pin 20 Hardware handshake from
printer. Connect to Printer RTS
(Output) signal
4 0V 0V pin 7Signal Ground
J19

HRX5000 Technical Manual V1.2Page 7 of 18
RS-232 to PC (J8)
J8
The terminal can communicate with the PC either by TCP/IP, RS-232 or
Modem. The connection method is set up in the Focus System | Clock
Utilities | Connection Setup screen. Here you specify a terminal name and a
connection method.
Connections:
Pin Signal Direction Notes
1Power Out 5-9 volts available to power an
external line driver. Current
limited to approx 50mA
2TXD Out Transmit data. 19,200 baud, 8
data, 1 stop, no parity
3RXD In Receive data. 19,200 baud, 8
data, 1 stop, no parity
4 0V Signal Ground
Pin Signal Direction PC 9 Way PC 25 Way
1Power Out
2TXD Out RXD (pin 2) RXD (pin 3)
3RXD In TXD (pin 3) TXD (pin 2)
4 0V 0V (pin 5) 0V (pin 7)
J8

HRX5000 Technical Manual V1.2Page 8 of 18
TCP/IP
The TCP/IP connection supports Ethernet 10/100 Base-T.
The IP address of the unit is set up via the Focus software using the System
| Clock Utilities | TCP/IP Tab. A password is required to modify the TCP/IP
address of the unit as inadvertent changes will cause loss of communication.
You would normally modify the IP Address by communicating over the RS232
cable from the PC.
TCP/IP

HRX5000 Technical Manual V1.2Page 9 of 18
Power (J21)
J21
The unit requires 9 to 12 volts DC at up to 500mA depending on configuration.
The unit is protected internally against reverse polarity connection.
Pin Signal Direction Notes
1 0V Signal Ground connected to
pin 2
2 0V
3+ve In 9-12 volts DC at up to 500mA
4+ve In Connected to Pin 3
J21