© 1997 –2010 EIBMARKT GmbH
Page 9
Support of unparameterized interfaces:
An interface can be used with a physical address that does not fit into the line topology (e.g.
for putting the device into operation).
Parameters: disable, enable
Monitoring bus voltage failure:
If a KNX/EIB failure is detected, it is reported on the IP. Return of the bus voltage is also
reported.
Parameters: disable, enable
IP address assignment:
Automatic (DHCP): The IP address is automatically assigned on the DHCP, i.e.
additional settings are not required. To be able to use this
function, there must be a DHCP server in the LAN (many DSL
routers have an integrated DHCP server).
Manual: In this case, the IP address, the subnet and the gateway IP
address must be entered manually.
IP configuration:
IP Routing Multicast Address:
This address is used for routing telegrams on IP. The multicast IP address 224.0.23.12 was
reserved (KNXnet/IP) at the IANA (Internet Assigned Numbers Authority) for this purpose. If
adifferent multicast IP address is required, it must lie within the range of 239.0.0.0 to
239.255.255.255.