Elite Suite ELT-KLED Manuale utente

ELT-KLED
EliteSuite LED Keypad
Installation Manual
ELT-KLED EliteSuite Installation Manual

PUBLICATION INFORMATION
First Publication
Draft Document Release Only
Updated fire zone information
Second Publication
Option Menu Navigation Updated
Card Reader Interface Options Added
Third Publication
Slave Keypad Options Added
Slave mode Zone Wiring Diagrams Added
ELT-KLED EliteSuite Installation Manual

CONTENTS
INTRODUCTION ....................................................1
Hardware Compatibility ..................................................................................... 1
WIRING CONFIGURATION ....................................2
Introduction .................................................................................................... 2
Keypad Wire Loom Colour Coding ....................................................................... 2
Communication Connection ............................................................................... 3
Zone Input Wiring ............................................................................................ 4
Fire Zone Input Wiring ...................................................................................... 5
Slave Keypad Zone Wiring................................................................................. 6
PGM (Programmable Output) ............................................................................. 7
Slave Reader Network....................................................................................... 8
Slave Keypad Network ...................................................................................... 9
Indicator Lights................................................................................................ 10
Binary Number Display ..................................................................................... 10
DEVICE CONFIGURATION ...................................11
Device Configuration Mode Access ...................................................................... 11
Address Selection ([MENU] , [1])........................................................................ 11
Device Options ([MENU] , [2]) ........................................................................... 12
Device Default ([MENU] , [3]) ............................................................................ 12
LOCAL INSTALLER LOGIN ...................................12
Introduction .................................................................................................... 13
TIMING (MENU 1)...............................................14
Entry Delay Timer ([MENU] [1], [1]) ................................................................... 14
Exit Delay Timer (Menu 1, 2) ............................................................................. 14
Alarm/Siren (Menu 1, 3) ................................................................................... 15
Reader Pre-Alarm Timer (Menu 1, 4)................................................................... 16
Reader Left Open Timer (Menu 1, 5) ................................................................... 16
OPTIONS (MENU 2) ............................................17
General Options (Menu 2, 1).............................................................................. 17
Arming Options (Menu 2, 2)............................................................................... 19
Reporting Options (Menu 2, 3) ........................................................................... 20
Panic Options (Menu 2, 4) ................................................................................. 22
ZONES (MENU 3) ................................................24
Selecting a Zone .............................................................................................. 24
Zone Type....................................................................................................... 24
Zone Options................................................................................................... 25
CONTACT ............................................................27
Contact........................................................................................................... 27
ELT-KLED EliteSuite Installation Manual

INTRODUCTION
This document details the wiring configuration of the EliteSuite
condominium control keypad and installer programming functions.
Hardware Compatibility
This manual is written for hardware verison 208-4125-020 or
higher and covers firmware application 1.00. This firmware
communicates with a EliteSuite enabled Protégé System
Controller firmware version 1.06 or above.
1 ELT-KLED EliteSuite Installation Manual

WIRING CONFIGURATION
Introduction
The wiring structure of the EliteSuite keypad uses an encrypted
RS485 communication interface. Connections should be made in a
daisy chain configuration, avoiding star and stub connections.
Figure 1 - Condominium Keypad Communication
Keypad Wire Loom Colour Coding
The condominium keypads are supplied with a wire loom attachment
and are connected using a keyed 10 position snap lock connector.
The 10 way wiring loom connection uses the following colour coding.
Figure 2 - Wire Loom Colour Coding and Function
2
ELT-KLED EliteSuite Installation Manual

Communication Connection
Support for up to 250 keypads per condominium controller is
provided, connection to the system controller uses the network
communication RS-485 interface. This interface is an isolated
interface and requires power to be supplied to the N+ and N-
terminals.
Figure 3 - Wire Loom Colour Coding and Function
When using more than one PSU to supply multiple wiring runs
of condominium keypads only connect the +12 output of ONE
power supply unit to the N+ and N- terminals of the
controller. Each PSU unit should have the common (0V or -)
connected together to ensure a common 0V.
3 ELT-KLED EliteSuite Installation Manual

Zone Input Wiring
The EliteSuite LED Keypad is capable of connecting to 4 zone inputs,
each zone input can then be programmed to perform the required
function in the system.
The following diagrams show each of the zone wiring configuration
settings that are possible. The programmed zone configuration for
the EliteSuite LED Keypad is made in the option settings. Refer to the
General Options Section on Page 17 for the programming of the zone
configuration.
When using a tamper input on a device the tamper contacts
must be normally closed and wired in series.
All resistors required to wire the zone configurations are
provided with the EliteSuite LED Keypad in the accessory bag.
Figure 4 - 2 Zone Input (No Resistors)
Figure 5 - 2 Zone Input (1K and 1K)
4
ELT-KLED EliteSuite Installation Manual

Figure 6 - 4 Zone Input Duplex Mode (1K and 2K4)
Fire Zone Input Wiring
When wiring a zone to be a fire zone input the current programmed
zone options will determine what resistors and configuration is
required, refer to the General Options Section on Page 17 and the
zone configuration diagrams in the Zone Input Wiring Configuration
on Page 4.
Figure 7 - Fire/Smoke Detection Input
When a fire zone is connected to a zone input that is used in
the duplex zone configuration a fire zone fault will NOT BE
shown when the fire zone has a shorted condition as this is
shown as all zones closed. A Fire Loop trouble will be shown
when the zone is tampered.
Fire zones that are installed in duplex mode operation are not
recommended. Fire zones should ALWAYS be connected using
the EOL resistor method (2R) as this provides both open and
short circuit monitoring.
5 ELT-KLED EliteSuite Installation Manual

Slave Keypad Zone Wiring
With one or more slave keypads connected, extra zones beyond the
normal 4 are available on the suite system.
There are 2 options for wiring the zones:
-Duplex mode enabled, 8 zones in total available. This setup
is shown in Error! Reference source not found..
-Standard wiring mode, 6 zones in total available. This setup
is shown in Figure 9.
The choice between the two wiring options will be dependent on the
physical configuration of the sensors and wiring in each installation.
See General Options on page 17 for enabling duplex zones.
Figure 8 - Slave Keypad Duplex Zone Wiring
6
ELT-KLED EliteSuite Installation Manual

Figure 9 - Slave Keypad Standard Zone Wiring
PGM (Programmable Output)
The EliteSuite LED Keypad uses a programmable output (PGM) that
will activate during an alarm condition. This output can be
programmed to either:
-Follow the status of the alarm siren time or the fire alarm setting
-Follow the armed / disarmed status of the keypad.
Connect a relay or other interface device to this open collector output
for activation of ancillary devices. The behaviour of this output can
also be inverted in the programming, see the General Options section
0for details on PGM programming.
Figure 10 - LED Indicator Output
7 ELT-KLED EliteSuite Installation Manual