Elotech R2000-N4 Series Manuale

R 2000 - N4 . .
Temperature Controller
4 - Zones „heat-only”
4 - Zones „heating-off-cooling“
Installation depth: 122 mm
DIN-Format: 96 x 96 mm
escription and operating manual
ELOTECH Ind strieelektronik GmbH
Verbind ngsstraße 27
D - 40723 HILDEN
FON +49 2103 / 255 97 0 FAX +49 2103 / 255 97 29
www.elotech.de Email: [email protected]
Man al: R2000-N4XX-X-000-X-X_EN Release: 2.02 © Elotech GmbH Page1/28

1 Contents
1 Contents..........................................................................................................2
2 General Information ........................................................................................3
3 Installation Instr ctions....................................................................................3
4 Type Code.......................................................................................................4
5 Connection Diagram.........................................................................................5
5.1 Power S pply and O tp ts..........................................................................5
5.2 Sensor Inp ts.............................................................................................7
6 Display and Keyboard........................................................................................8
6.1 Tendency Display........................................................................................9
6.2 Operating Levels.......................................................................................10
7 Parameter descriptions:...................................................................................12
7.1 Config ration Parameters, Valid for the Complete Device.............................12
7.2 Zone Config ration....................................................................................16
7.3 Control Parameters, Zone Dependent ........................................................20
7.4 Operating Level........................................................................................24
8 Error Messages................................................................................................25
9 Technical Data.................................................................................................26
10 Notes............................................................................................................27
Man al: R2000-N4XX-X-000-X-X_EN Release: 2.02 © Elotech GmbH Page2/28

2 General Information
Messages shown by the controller display
<§> Symbolizes the val e of the factory adj stment of the respective
parameters.
>3< This parameter is available in 3-point controllers only.
3 Installation Instructions
Make certain that the device is sed for the intended p rpose only.
R2400 controllers are designed for installation in control panels.
Protect the device against impermissible h midity and contamination.
Ambient temperat re may not exceed 50 °C (122 °F).
Electrical connections m st be made according to valid reg lations and by properly q alified
personnel.
If sing thermoco ple sensors, compensation lines have to be connected directly to the controller
terminals. Sensors may be connected only in compliance with the programmed range.
Sensor cables and signal lines (e.g. logic or linear voltage o tp ts) m st be laid separately from
control lines and mains voltage s pply cables (power cables).
It is not permitted to connect the gro nds of the sensor-inp ts and Logic-o tp ts with each other.
Separate installation of controller and ind ctive loads is recommended.
Interference from contactor coils m st be s ppressed by connecting adapted RC-combinations parallel
to the coils.
Control circ its (e.g. for contactors) sho ld not be connected to the mains power s pply terminals of
the controller.
The config ration parameters are generally to be selected first.
isclaimer of Liability
We have checked the contents of this doc ment for conformity with the hardware and software
described. Nevertheless, we are nable to precl de the possibility of deviations so that we are nable
to ass me warranty for f ll compliance. However, the information given in the p blication is reviewed
reg larly. Necessary amendments are incorporated in the following editions.
We wo ld be pleased to receive any improvement proposals which yo may have.
The information contained herein is s bject to change witho t notice.
Electronic scrap and components are s bject to special treatment and m st be disposed of by
a thorized companies.
Man al: R2000-N4XX-X-000-X-X_EN Release: 2.02 © Elotech GmbH Page3/28

4 Type Code
Man al: R2000-N4XX-X-000-X-X_EN Release: 2.02 © Elotech GmbH Page4/28
R2000 - y - 000N4xx- d- - z
230 VAC
115 VAC
1
224 VAC3 24 VDC5
No0 RS 2322 RS 4854 0/20mA TTY5
No0
Power Supply
Fieldbus-Interface
Heater Current Monitoring
Yes
(Logic outputs only)
5
4-zonesN421 Zones 2-point
Type
4-zonesN426 2-point
4-zonesN431 2/3-point
4-zonesN436 2/3-point
4-zonesN437 2/3-point
Control Outputs
heating / cooling
Relay
Logic
Relay Relay
Logic Logic
Logic Relay

5 Connection iagram
5.1
Power Supply and Outputs
Man al: R2000-N4XX-X-000-X-X_EN Release: 2.02 © Elotech GmbH Page5/28
1
2
3
4
5
6
7
8
9
Out 4-1
Out 4-1
10
11
Out 3-1
Out 3-1
12
13
Out 2-1
Out 2-1
14
15
Out 1-1
Out 1-1
21
22
Out 4-2
Out 4-2
23
24
Out 3-2
Out 3-2
25
26
Out 2-2
Out 2-2
27
28
Out 1-2
Out 1-2
17
18
19
20
L / DC
N / DC
A1
A1
A2
A2
Power Supply
Type: N421, N431
2-point Configuration
Out 1-1 – Out 4-1
heating or cooling according
to configuration
Out 1-2 – Out 4-2
not used
3-point Configuration
Out x-1 heating
Out x-2 cooling
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
21
22
23
24
25
26
27
28
17
18
19
20
L / DC
N / DC
A1
A1
A2
A2
Out 4-1
Out 3-1
Out 2-1
Out 1-1
Com.
Out 4-2
Out 3-2
Out 2-2
Out 1-2
Com.
+Uout +Uout
Type: N426, N436
Power Supply 2-point Configuration
Out 1-1 – Out 4-1
heating or cooling according
to configuration
Out 1-2 – Out 4-2
not used
3-point Configuration
Out x-1 heating
Out x-2 cooling

Man al: R2000-N4XX-X-000-X-X_EN Release: 2.02 © Elotech GmbH Page6/28
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
L / DC
N / DC
A1
A1
A2
A2
Out 4-1
Out 3-1
Out 2-1
Out 1-1
Com.
+Uout
Type: N437
Power Supply
21
22
Out 4-2
Out 4-2
23
24
Out 3-2
Out 3-2
25
26
Out 2-2
Out 2-2
27
Out 1-2
17
18
19
20
28
Out 1-2
2-point Configuration
Out 1-1 – Out 4-1
heating or cooling according
to configuration
Out 1-2 – Out 4-2
not used
3-point Configuration
Out x-1 heating
Out x-2 cooling

5.2
Sensor Inputs
It is not permitted to connect the gro nds of the sensor-inp ts and Logic-o tp ts with each other.
External Contacts:
Man al: R2000-N4XX-X-000-X-X_EN Release: 2.02 © Elotech GmbH Page7/28
70
71
72
73
74
75
76
77
78
79
80
+
−
ϑ
ϑ
+
−
ϑ
+
−
+
−
+
−
+
−
81
82
83
ϑ
ϑ
ϑ
ϑϑ
TC PT100
3-wire
PT100
2-wire
Sensor
Zone
4
3
2
1
Ι
L1
RxD in
RxD out
TxD out
0/20mA
TxD in
GND
RxD out
TxD in
TxD out
RS 232
RxD in
A
RS 485
B
83
90
91
92
93
94
95
8396
Heater Current Monitoring
K3
K2
K1
Fieldbus
Sensor Inputs
K1 Open
Closed Setpoint 1 (SP1) valid for all zones
Setpoint 2 (SP2) valid for all zones
K2 Open
Closed Adjustment lock off
Adjustment lock on
(see parameter „Adjustment lock”)
K3 Open
Closed Individual setpoint 1 adjustment for each zone
Setpoint 1 will be overtaken for all other zones automatically
Setpoint Switch:
Adjustment Lock:
Setpoint Changing:

6 isplay and Keyboard
LE 1: Control o tp t „heating“ of the
choosen zone active
LE 2: Control o tp t „cooling“ of the choosen zone
active
LE A1: Alarm o tp t A1, indication LE Setpoint ramp of the choosen zone active
LE A2: Alarm o tp t A2, indication LE SP2: Setpoint 2 valid (for all zones)
Key functions:
Zone preselection
Parameter key (parameter preselection)
Adj stment of chosen parameter (e.g. setpoint) to higher or lower val es.
Short operation: single-step adj stment
Longer operation: q ick-scanning
When the parameter adj stments have been altered b t not entered,
the display will flash bright/dark.
Confirmation and storage of the preselected val es.
The display will show a light chain as a control of this f nction.
Sets the parameter back to the originally stored val e.
Any alterations made to the parameters, that are not confirmed (E-key) within
30 seconds, will not be accepted and the parameter will ret rn to its originally
stored val e. The act al process val e and the setpoint val e will be indicated.
F nction key, E. g. all zones are displayed cyclic (zone scanning on/off).
Zones, which are not in action (OFF), are not displayed.
The f nction of this key can be programmed into the config ration level of zone 0.
See parameter „Co.F1“.
Man al: R2000-N4XX-X-000-X-X_EN Release: 2.02 © Elotech GmbH Page8/28

6.1
Tendency isplay
After switching the instr ment „on“ a temperat re tendency display will be shown, to give an overview
abo t the temperat res deviations relating to the setpoints in the individ al controller zones.
Zone:
1 2 3 4
Display examples:
Zone 1: Controller o tp t active
temperat re OK
(Bar central)
Zone 2: Controller o tp t not active
Process val e is higher than setpoint
>0,5 % of meas ring range (Bar top)
Zone 3: Controller o tp t not active
temperat re OK
(Bar central)
Zone 4: Controller o tp t active
Process val e is lower than setpoint
<0,5 % of meas ring range (Bar bottom)
Zone:
1 2 3 4
Zone 1: Top range end has been reached (sensor
break)
Zone 2: Bottom range end has been reached
(sensor error, open)
Zone 3: Selft ning algorithm is active
Zone 4: Man al mode
The displayed decimal points show the act al sit ation of the controller o tp t.
Flashing digit: Alarm indication in the matching zone
Man al: R2000-N4XX-X-000-X-X_EN Release: 2.02 © Elotech GmbH Page9/28

6.2
Operating Levels
The operation of the controller is divided into 3 levels.
After power p of the device, it will be a tomatically in the operating level.
Operating level (valid for each zone separately):
Process- and Setpoint val e will be displayed sim ltaneo sly. Within the operating level the setpoint
can be adj sted by pressing the„UP" / „ OWN" - keys.
Every adj stment has to be confirmed by pressing the „ E “ - key.
All parameters within the operating level ( incl ding the alarm val es ) can , in s ccession, be
displayed by pressing the „ P “ - key and adj sted by pressing the „UP" / „ OWN" - keys.
Confirm by pressing the „ E “ - key.
Parameter level: (valid for each zone separately)
Within the parameter level the val es are adj sted to s it each individ al process.
This level is reached by sim ltaneo sly pressing the „ P" - and „ E " -keys.
The display of each single parameter within the parameter level and their adj stment are made in
the same fashion as within the operating level.
After either pressing the „ E “ - key for approx. 1 second, or waiting for a period of approx. 30
seconds, the nit will a tomatically ret rn to the operating level
Configuration level: (valid for the complete device)
Select zone “0”. Then press sim ltaneo sly the „ P " - and "„ E " - keys for a period of approx. 5
seconds.
This general settings have to be made first.
Configuration level: (valid for each zone separately)
Select zone 1...4. Then press sim ltaneo sly the „ P " - and "„ E " - keys for a period of approx. 5
seconds.
There is a copy f nction available. So it is possible to copy the programmed parameters of one zone
to other zones.
Man al: R2000-N4XX-X-000-X-X_EN Release: 2.02 © Elotech GmbH Page10/28
PP
EE
Parameter level
P
Y (output ratio)
xxxx
xxxx P
Operating level
P
setpoint (set)
xxxx
xxxx P
Configuration-
level
P
Zone : on / OFF
xxxx
xxxx P
and and
press press appr. 5 sec.
Back into operation level:
-Press
E
1 sec. or automatically after appr. 30 sec.
Indice
Altri manuali Elotech Regolatori di temperatura

Elotech
Elotech R 1140 Manuale utente

Elotech
Elotech R 2000 - 431 Manuale utente

Elotech
Elotech R2400 Manuale utente

Elotech
Elotech R 1120 Manuale utente

Elotech
Elotech R 1140 Manuale utente

Elotech
Elotech R 1100 Manuale

Elotech
Elotech R2000 Manuale utente

Elotech
Elotech R4000 Manuale

Elotech
Elotech R4000 Manuale