7
2. SETUP AND OPERATION
2.5. FIRST START AND RUNNING
Our vibration motors are manufactured as standard only for direct starting. For this reason, our
vibration motors have 3 pole outputs in the terminal boxes.
The suitability of the network that will feed the vibration motor to the vibration motor plate
information must be checked and the supply cables should be selected according to these values. If the voltage
difference is greater than ± 5%, the vibration motor windings may be damaged.
Check the tightness of the nuts at the terminals. Loosely nuts cause the vibration motor to
malfunction.
The user has the responsibility to protect the vibration motor against overload. The vibration
motor must be connected to the mains via a thermal-magnetic switch which is capable of
protection against overcurrents. The current setting of the switch must not be more than 1.05
times the rated current of the vibration motor. Otherwise, the vibration motor is not covered by
the warranty.
Overload protection will only be possible by sensing excessive heat caused by overload and other
reasons (two phases, excessive ambient temperature or altitude, excessive starting stop, etc.). Install a
thermistor in the winding and to connect the terminals coming from the thermistor to the thermistor relay is
necessary for overload protection.
PTC thermistors are mounted as standard on 132, 160, 180 and 200 types of vibration motors and
Phase Protection Relay is given as free of charge. On request, our smaller vibration motors are supplied with
a thermistor and are supplied with a relay.
Vibration motors of type 132, 160, 180 and 200 should be used with thermistors. Otherwise, the
warranty terms will be invalid.
2.6. ROTATION DIRECTION
Our vibration motors are designed to operate in both directions. The rotation direction of the vibration
motor can be changed by replacing any two of the mains phases in the connection diagram L1, L2 and L3.