4 Description
Ventilation Controls TH PF(-U)
Status: 19.04.2016 • Technical Changes and Errors excepted.
1.1. Technical data
* Please note the information on measuring accuracy below.
The product conforms with the provisions of EU directives.
1.1.1. Measuring accuracy
Follow the instructions in chapter Installation position to avoid sources of interference
and to ensure the specified accuracy of the sensor.
When measuring temperature, the self-heating of the device is considered by the
electronics. The heating is compensated by reducing the measured temperture by the
self-heating of 0.7°C. The indicated indoor temperature measured value approches the
Housing Plastic (partially painted)
Colours • bright white (similar to RAL 9016 traffic white), no.
40100
• matt aluminium, no. 40101
• matt anthracite, no. 40102
• stainless steel, no. 40103
• special colours on request
Mounting Flush mounting
(wall mounting in junction box R60 mm, 42 mm depth)
Protection category IP 20
Dimensions Housing approx. 55 x 55 (W x H, mm),
Mounting depth approx. 15 mm
Base plate approx. 71 x 71 (W x H, mm),
Total weight approx. 65 g
Ambient temperature Operation -10…+50°C, storage -20…+60°C
Ambient humidity max. 95% RH, avoid condensation
Operating voltage 24 V DC ±20%
Power consumption max. 16 mA
Temperature measuring
range
-10…+50°C
Temperature resolution 0.1°C .
Temperature accuracy* ± 0.4°C at 25°C
Humidity measuring range 0…95%
Humidity resolution 0.1%
Humidity accuracy ± 5% rF
Ventilation outputs 2 semi-conductor outputs, open collector
max. 50 V AC/DC, 100 mA
Inputs 2 button inputs (with +24 V supply)
Measuring value outputs
(TH PF-U only)
Temperature 0...10 V (0 V = -10°C, 10 V = +50°C),
Humidity 0...10 V (0 V = 0%rF, 10 V = 100%rF).
100 Ωinternal, max. load 5 kΩ