Manual V1.2 Page 10 of 20
Quic reference I
A D ModeMinimum Rfield
ormula
Minimum field resistance
actory settings
Sensing voltage
Underspeed frequency
Underspeed slope
Droop
Sta ility P-action
Sta ility I-action
Max. out
Dipswitch 1
Dipswitch 2
Dipswitch 3
Dipswitch 4
Dipswitch 5
Dipswitch 6
Dipswitch 7
Dipswitch 8
: 400V
: 45Hz
: Trip slope
: 100%
: 50%
: 50 %
: 100 %
: On
: Off
: Off
: On
: Off
: Off
: Off
: Off
Link: 3- 4, EX-EX
AVR field current.
Max. rating: Intermitted 12A < 10s.
Max. rating: ield forcing 20A < 1s.
Max. out Droop Underspeed Stability Voltage
(Page 6)(Page 6)(Page 6)(Page 8)
Underspeed
Coarse
Fine
- +
- +
Range 230V sensing
+/- 185 .. 290V
Range 400V sensing
+/- 315 .. 505V
+ -0% 100%0% 100% - + - +
I-action
(Integral time)
P-action
( roportional gain)
Dipswitch
ON
1234
dip
5678
400V sensing voltage.
Phase loss protection disa led.
Remote adjust ena led.
DI Off On
S-T internally shorted.1
2
3
4
5
6
7
8
Underspeed trip disa led.
Underspeed F/V curve disa led.
Buildup speed 2 sec.
Normal Integral time.
Underspeed trip voltage +/- 27.5% of Unom.
Phase loss protection ena led.
230V sensing voltage.
Underspeed trip ena led.
Buildup speed 5 sec.
Increased Integral time.
Do not place or remove link!
Inputs are for EMRI AFD.
AFD is an option unit
for dual AVR applications.
For more information
see manual AFD.
Underspeed F/V curve ena led.
Underspeed trip voltage +/- 17.5% of Unom.
(Page 5..8)
Trip @
Higher – RPM - Lower
+/- 62Hz +/- 27Hz