EMS SmartCell Manuale utente

©2020 EMS Ltd. All rights reserved MK349-0001-99 (Issue 1) 22/10/2020 AJM
Quick Start Guide
Intelligent Wireless Zone Monitor

©2020 EMS Ltd. All rights reserved Page 2 of 36 MK349-0001-99 (Issue 1) 22/10/2020 AJM
Contents
Introduction 3
Important notes 3
Additional documentation 4
Overview of system setup 5
What’s in the box 7
WZM features 8
Side cover removal 8
Open WZM 9
Optional door removal 9
Cable entry 10
Fix WZM to wall 10
Addressable fire system wiring
11
Conventional fire system wiring
12
Mains power connections 13
24 VDC power connections 13
Re-fit door 14
Connect backup battery 14
Remove 3V battery tab 15
Apply power 15
Engineer menu entry 16
Set time & date 17
Install devices 18
Add devices to system 19
Device attributes 20
Device location text 22
Text entry 23
Set the panel type 24
Sounder tones 25
Sounder duration 27
Sounder activation method 28
Pulsed output 29
Device indicator operation 31
Device signal levels 32
Test devices 33
Congratulations 36

©2020 EMS Ltd. All rights reserved Page 3 of 36 MK349-0001-99 (Issue 1) 22/10/2020 AJM
Introduction
This quick start guide will show you how to set up the SmartCell
Wireless Zone Monitor (WZM), for connection to either addressable or
conventional fire alarm systems. For advanced programming, refer to
the ‘SmartCell Wireless Zone Monitor Programming Guide’ (MK067).
Note: this quick start guide will cover the method of adding devices via
power-up. Refer to the programming guide for more information of
alternative methods.
Important notes
The installation must conform to applicable local
installation codes and should only be installed by a fully
trained competent person.
!
SmartCell devices contain electronics that may be
susceptible to damage from Electro Static Discharge (ESD).
Take appropriate precautions when handling electronic
boards.
The procedures outlined in this installation guide must be
carefully followed.
To ensure correct operation, products must be used within
the specified environmental operating conditions.
Always select an appropriate device type for the
application as per local codes of practice, or as advised by
a qualified professional.

©2020 EMS Ltd. All rights reserved Page 4 of 36 MK349-0001-99 (Issue 1) 22/10/2020 AJM
Additional documentation
The below QR codes provide links to the a wide range of WZM
information, including:
Wireless Zone Monitor Programming Guide (MK067)
Wireless Zone Monitor Installation Guide (TSD127)
Wireless Zone Monitor Datasheet
Wireless Zone Monitor certification
Note: Should you be unable to scan the QR code, visit the following
website addresses:
Wireless Zone Monitor (230 VAC version):
https://firesecurityproducts.com/en/product/fire/SC_13_1100_0001_99/83586
Wireless Zone Monitor (24 VDC version):
https://firesecurityproducts.com/en/product/fire/SC_13_2100_0001_99/83591
Wireless Zone Monitor
(230 VAC version):
Wireless Zone Monitor
(24 VDC version):

©2020 EMS Ltd. All rights reserved Page 5 of 36 MK349-0001-99 (Issue 1) 22/10/2020 AJM
Overview of system setup
Step 1
Install the SmartCell WZM.
Step 2
Log on devices required for the installation - Smoke detectors, heat
detectors, call points, sounders and input / output devices, etc.
Enter device location text.
Note: If devices and zones are not programmed with custom text
labelling, default text will be displayed. E.g.
Step 3
Change device default settings if required in accordance with local
codes of practice, or as professionally advised.
Step 4
Set the WZM to match the connected fire control panel type (either
conventional or addressable).
Step 5
Configure sounder tones, durations and activation methods.
Z01 A04 TAMPER
Sounder Detector
ID:001234
View>
Example device fault with
default device text:

©2020 EMS Ltd. All rights reserved Page 6 of 36 MK349-0001-99 (Issue 1) 22/10/2020 AJM
Step 6
Check all device signal levels are stated as ‘GOOD’.
Step 7
Test every device for correct operation, using appropriate test
equipment.
Note: sounders may activate upon activation of a wireless device if the
‘Sounder activation method’ is set to ‘Immediate’.
Step 8
Weekly test the system in accordance with local codes of practice.
Step 9
Maintain the system in accordance with local codes of practice and
manufacturers recommendations.


©2020 EMS Ltd. All rights reserved Page 8 of 36 MK349-0001-99 (Issue 1) 22/10/2020 AJM
FIRE
FAULT
POWER
FUNCTION 1
FUNCTION 2
1
2
3
4
Intelligent Wireless Zone Monitor
80 character
display
Status LEDs
Function
buttons
Le side cover
release clip
Navigation &
confirmation
buttons
Right side cover
release clip
WZM features
(A)(A)
(B)
Side cover removal
The following steps illustrate how to remove the side covers:
Slide the side cover
sideways, creating a
gap as shown.
Press the cover’s
releasing clip with
your thumb (A), and
simultaneously rotate
the side cover
anti-clockwise (B), as
viewed overhead to
remove the cover.
Position your fingers
behind the cover’s
protruding edge.
1. 2. 3.

©2020 EMS Ltd. All rights reserved Page 9 of 36 MK349-0001-99 (Issue 1) 22/10/2020 AJM
Optional door removal
1.
3.
Disconnect the ribbon cable, then turn and release the door hinges.
Open WZM
1. Unclip side cover. 2. Loosen screws.
230 VAC variant shown
3. Open door.
Refer to the ‘Side
cover removal’ section
(page 8) for details.
2.
4.
FAULT
NC C NO
FIRE
NC C NO
ACTIVE ACTIVE
FAULT FAULT
INPUT1 INPUT2
A B A B
EN54-4UNIVERSAL PSU
SC-60-1000
INPUT:220-240VAC, 50Hz, 0.3A
OUTPUT:5.0-8.5VDC, 0.8A MAX
STATUS
FAULT
MAINS/ CHARGER FAIL
BATTERYLOW
BATTERYFAIL
START
INPUT
Foradditional information refer to TSD042
0359-CPR-00267
15
0905
SLIDETO
REMOVE
EOL
(+) (-) (+)(+) (-) (+) (-) (+) (-) (+) (+) (-)
SOUNDERA
L1 L1 L2 EOL ALARM L1 L1 L2
IN OUT RES IN OUT
ZONE
A
B
C
D