Mounting (Figure 2)
- PS-722 can be mounted on DIN rails which comply with EN50022 standards.
- Mount the device vertically. When mounting the device, it is recommended that the DC output side stays
on top side.
- Mind the device’s ventilation when mounting the device. After the mounting, it is recommended to leave a
1 cm space between PS-722 and devices next to it.
4- Technical Properties:
Input
Nominal input voltage 100-240 VAC / 130-320 VDC
Input voltage range 85-265V AC / 110-350V DC
Frequency 45-65 Hz / 0 Hz
Current consumption (@72W) 0.8 -1.7A AC (±10%)
Inrush current <20A
Internal fuse 3.15A
Estimated opening time after
Nominal Voltage <2 s (@220V AC - 72W)
Mains butering >20 ms (@220V AC - 72W)
Transient surge
Voltage protection Varistor
Line ragulation <1% (@24V DC)
Output
Nominal output voltage 24V DC (± 1% )
Output voltage range 21.6 - 27.6V DC
Nominal output current 3A DC (<55°C)
Maximum output current 4A DC
Eciency >83% @85V AC
>86% @265V AC
Residual uctuation <30 mV @220V AC
Overload protection max. 4.4A (@25°C, @220 VAC)
Short circuit protection Hysteresis turn o
Thermal protection >55°C
Series connection Yes
Parallel connection Yes (by connecting ORing diode)
Load regulation < 1%
Indicators
Output OK LED
General Information
Operating Temperature -20°C...+55°C ** (Reduce load by 2.5% / °C over 50°C)
Humidity <95% (@25°C)
Mounting Type Rail mount (EN 50022)
Rail mounting spaces 1 cm horizontally, 5 cm vertically
(spacing between other devices)
Connection Terminals with xed screws
compatible with Phillips screw drives
Connection wire max. 12 AWG (4mm2) solid wire,
14 AWG(2.5mm2) stranded wire
Protection class IP20
Pollution Degree Class 2
Overvoltage protection class 3
Dimensions DIN4 (72*95*60) mm
Casing Nylon 6
Weight 300 gr
Product Standards
Product standard EN61204-1, EN61204-3,
EN61204-4, EN61204-7
SMPS transformer standard EN61558-1
Electric safety EN60950, EN61558-2-17
Insulation voltage (input/output) 4 kV
Insulation resistance >5 MW (between input-output)
Surge voltage 3 kV Criterion A EN61000-4-5
Burst voltage 4 kV Criterion B EN61000-4-4
ESD
Air discharge 8 kV Criterion A EN61000-4-2
Contact discharge 4 kV Criterion A EN61000-4-2
Sag in input voltage (@220 VAC)
0% 20ms Criterion A EN61000-4-11
70% 500ms Criterion A EN61000-4-11
Other EN61000 3-2, EN61000 6-2, EN55011, EN55022
24V 72W Power Supply
PS-722
! ATTENTION
This user manual contains information necessary for the safe and correct operation of the device. Before
mounting the device, please read this user manual carefully and pay attention to warnings.
Safety and Warnings
! ATTENTION
Do not open the device under any circumstances. An opened device’s warranty will become void.
! ATTENTION The device must be mounted only by qualied personnel with necessary precautions against
electric shock in place. Incorrect connection may create dangerous result for people and environment.
Incorrect connection may result in permanent damage to the performance of the device.
- Before you energize the device or remove the device from mains, make sure that the supply cable isn’t
connected to mains.
- Supply input of the device must be connected according to EN60950 standards.
! A supply voltage greater than 265V AC may result in an explosion in the device or in damages to the user.
- Device supply must be at a sucient power capacity and must comply with security standards.
-
Cables connected to the outputs of PS-722 must be suitable for the maximum current that PS-722 can provide.
- After device connection is nished, connection points must be protected against accidental contacts.
- Mounting of the device must be done vertically as shown in Figure-1.
1- Introduction
1.1 Applications : PS-722 is a 72W high eciency SMPS which was designed according to DIN case
standards for easy installation in panels. It can be safely used in industrial and building automation
applications.
1.2 General Features :
- Wide input voltage range 85-265V AC (50-60 Hz) / 110-350V DC
- Adjustable DC output voltage 21.6 ...27.6V DC
- 72W output power (3A DC @24V DC)
- Status notication LED
- High eciency operation >86%
- Low input voltage protection
- Short circuit, overload protection
- Thermal protection
- Class 2 device, no earth connection is necessary
- DIN4 case
- IP20 Protection class
- CE, EN 60950,EN 61204
3
2
4
1
1- Input Voltage
2- DC Output
3- Setting Range of the Output Voltage
4- Output OK LED
1.3 Operation : The part of the device which is numbered as 1 in Figure-1 is the input voltage connection
point of PS-722 and it is shown with L (Line) and N (Neutral) on the device body. Connect the supply voltage
to these points. The part of the device which is numbered as 2 in Figure-1 is the DC output connection point
of PS-722 and its polarity is shown with + and - on the device body. PS-722 supplies adjustable DC voltage
from these connection points. When supply voltage is applied to PS-722, the LED which is numbered as 4
in Figure-1 will light up. When this is LED is lit, it indicates that PS-722 is working and it generates an output
voltage. The part of the device which is numbered as 3 in Figure-1 is the DC voltage adjustment trimpot of
the device. After the device has been energized, the output voltage is increased by turning the adjustment
trimpot clockwise and is decreased by turning the adjustment trimpot is turned counterclockwise. This way,
the output voltage can be adjusted in the specied range.The device will turn itself o to protect itself during
cases of overload, overheating and shortcircuit at the output contacts. When the error state is resolved, it will
activate itself automatically. (In case of thermal protection power on reset is needed).
2- Block Diagram
2.1 Input (1)
- The part which is numbered as 1 in Figure-2 is the Line and Neutral supply inputs of PS-722.
- 100-240V AC input voltage can be connected by using the L and N terminals.
- 110-350V DC input voltage can be connected by using the L and N terminals.
- The device will turn itself o to protect itself during cases of overload, overheating and shortcircuit at the
output contacts. When the error state is resolved, it will activate itself automatically.
2.2 Output (2)
- The part which is numbered as 1 in Figure-2 is the DC voltage output of PS-722.
- Positive and negative parts of the output voltage are shown with (+) and (-).
- Output voltage is 24V DC.
- Output voltage can be adjusted between 21.6-27.6V DC values by using the adjustment trimpot on the
device.
- Device output is protected against short circuit.
- When the output is shorted circuited, device turns o completely and turns on again after the short circuit
condition is resolved.
- The device can operate up to an ambient temperature of +55⁰C.*
PS-722 has LED indicator (Parts 4 in Figure-1).
- When there’s no energy : Output OK LED is o.
- Normal operation mode : Output OK LED is on.
- Short circuit : Output OK LED is o. If short circuit situation is resolved, the device starts to work again.
- Overload : If overload is drawn from device at normal temperature, Output OK LED turn o. The device
makes blinks. When the load condition returns to normal, the device starts to opening again.
- Overheating + Overload : Device cuts the supply, doesn’t generate voltage.
- Overvoltage on Output : Output OK LED blinks.
3- Connection and Mounting
3.1 Wire Connection
- AC Input (1): Under nominal load, PS-722 draws maximum 1.7A AC and minimum 0.8A AC. Wire thickness
must be selected according to these values. Maximum 14 AWG stranded wire (2.5 mm2) or 12 AWG solid wire
(4 mm2) can be connected to the input terminal.
- DC output (2): Output current is 3A DC. Wire thickness must be selected according to this value. Maximum
14 AWG stranded wire (2.5 mm2) or 12 AWG solid wire (4 mm2) can be connected to the output terminal.
- In terms of complying with standards, use copper wires that can operate at 75oC.
ENTES Elektronik Cihazlar Imalat ve Ticaret A.S.
Adr: Dudullu OSB; 1. Cadde; No:23 34776
Ümraniye - İSTANBUL / TÜRKİYE
Tel: +90 216 313 01 10 Fax: +90 216 314 16 15
Web: www.entes.com.tr - www.entes.eu
Call Center Technical Support: 0850 888 84 25 A7202/Rev.4
Figure-5