environmental potentials EP-HPF Manuale

www.OMResources.net •281.456.3568
Power Quality For e Digital Age
Installation and Maintenance Manual
EP-HPF
EP-HPF
Wall Mounted Waveform Corrector
Represented By:

EP-HPF Series INSTALLATION GUIDE 2
Mailing Address: 4220W 2100S, Suit N&O, Salt Lake City, UT 84120
FIVE YEAR WARRANTY
•Environmental Potentials will replace or repair any product from the EP-HPF product
line as long as it was not damaged during installation or damaged
from faulty installation.
•EP warranty registration card must be filled out and received by Environmental
Potentials within 15 days of installation.
•This warranty is for the repair or replacement of damaged EP products only.
Environmental Potentials accepts no liability, written or expressed, for the damage
that may have occurred to any other equipment; nor does Environmental Potentials
warranty cover any labor cost associated with replacement of such product.
Contact Us: info@ep2000.com •844.500.7436
Table of Contents
3 – Safety First
3 – Pre-Installation Preparations
4 – Voltage Ratings & Power Source Configurations
5– Mounting
6– Wiring
6– Maintenance
6– Servicing
EP-HPF Series Wall Mounted Waveform Corrector
Installation and Maintenance Manual

Safety First
Pre-Installation Preparations
3
EP-HPF Series INSTALLATION GUIDE

EP-HPF Series INSTALLATION GUIDE 4
Voltage Ratings & Power Source Configurations
Single Leg 1 Wire, 1 Neutral + Ground Installation
1. Connect white neutral to neutral bus bar.
2. Next connect black phase A to phase A of the 15 A breaker.
3. Last connect green ground to ground bus bar or panel. Ground is case ground only
and should NOT be connected to neutral bus bar.
Single Phase Installation
1. Connect white neutral to neutral bus bar.
2. Next connect black phase A to phase A of the 15 A breaker.
3. Then connect black phase B to phase B of 15 A breaker.
4. Last connect green ground to ground bus bar or panel. Ground is case ground only
and should NOT be connected to neutral bus bar.
L
N
Single Phase 1 Wire + Neutral
L1
N
L2
Split Phase 2 Wire + Neutral
single leg 1 wire + 1 neutral
single phase, 2 wire + 1 neutral

EP-HPF Series INSTALLATION GUIDE 5
Mounting
For optimal performance, mount EP product as close to
electrical panel as possible. Longer wire increases inductance
in the system and the EP unit may not function properly.
Make sure the EP product is mounted in a dry and clean
environment. e EP unit can be mounted in any secure area
above, below, beside or inside the electrical panel.
For optimal performance:
•EP-HPF should be connected no more than 6
inchesfrom electrical panel.
Although internal mounting can be preferred mounting for
shorter lead lengths and optimal performance, it poses two
problems:
1. IEEE does not recommend internal mounting of
Waveform Corrector in the event of end of life
termination of the unit that may cause damage to the
internal distribution panel.
2. On internal installation the panel must be opened for
visual verification of units’ functional status.
Ensure you have considered all of these options before
attempting internal installation.
WARNING
•ALWAYS have a professional
electrician with proper safety
equipment perform installation.
•Any attempt to open unit voids
warranty.
!!
SIDE MOUNTING
EP units are designed for installation to ½ inch
panel knockout on side, top or bottom of panel.
Unit may also be secured with #8 self tapping or
wood screws.
INTERNAL MOUNTING
Ensure a minimum of 1 inch clearance to all
electrical surfaces before attempting an internal
mounting.

6
Wiring
1. Requires a dedicated 15 A circuit breaker to connect Waveform Corrector to the electrical system.
2. Wire should be connected straight to the power source. Avoid sharp bends and refrain from splicing the
wires as this will reduce the effectiveness of the unit.
3. Do not twist wires.
NOTE: It is good electrical practice to tighten all of the bolts in the electrical panel. Electrical leads should be
connected securely to prevent fire or electrical damage.
Maintenance
EP products do NOT require periodic maintenance. The units have LED lights to provide visual indication of the
unit’s functional status. It is also good practice to inspect the connections of the power supply wiring to the EP unit
monthly.
Servicing
EP units contain no serviceable parts and require no adjustments. All EP products are designed to provide many
years of electrical protection without any need for servicing.
If the EP unit does malfunction, have a professional electrician inspect the wire connections. If the problem
persists, contact your EP sales representative to discuss obtaining a replacement unit.