Note: Tank Shower frame is not Cyclone Rated when
mounted on FRP Grid Base.
Tank Shower frame with privacy panels is Category B Cyclone
Rated when bolted to the specied concrete slab and when
tank is at least half full of water.
MOUNTING ANCHORS
The frame is to be anchored to the reinforced concrete
foong specied below, using the 6 mounng plates on the
frame (SEE FIGURE 1).
Each mounng plate has provision for 4 or 2 anchor bolts/rods
(NOT SUPPLIED), for a total of 20 to fully anchor the frame.
The 20 anchors must be of an M12 Stainless Steel Epoxy type
with 150mm embedment into the reinforced concrete foong
to meet Cercaon Requirements.
FOUNDATION: The foong is to be founded upon a minimum
150kPa material.
CONCRETE SPECIFICATIONS
ELEMENT SLUMP AGGREGATE
SIZE
CEMENT
TYPE F’C - MPA
FOOTING
SLAB
80mm 20mm max. GP 32
REINFORCED CONCRETE FOOTING SPECIFICATIONS
Reinforced concrete foong is to be a minimum
2000 x 2000 x 200mm (SEE FIGURE 2) with 16mm Diameter
Bars (with a Tensile Stress Capacity of 500 MPa) running at
200mm each way both top and boom (SEE FIGURE 3).
Foong must have a 50mm top and edge cover
and a 65mm boom cover.
CONCRETE NOTES
1. All workmanship and materials shall be in accordance
with AS3600-2001 concrete structures code.
2. Concrete quality and clear concrete cover are to be as
specied.
3. Concrete element sizes do not include thickness of any
applied nishes.
4. All concrete shall be mechanically vibrated. The vibrator
shall not be used to spread concrete.
5. Reinforcement is shown diagramacally, not necessarily
shown in true projecon.
6. All reinforcement shall be rmly supported on plasc
or MS plasc pped or galvanised chairs placed at not
greater than 800mm centres both ways.
cyclone wind catergory B requirements
200
2000
2000
FIGURE 2
FIGURE 1
FIGURE 3
Cross Secon showing reinforcement bars in one direcon
200