6 Part Number HA026270 Issue 5.0 Aug 07
3.2 To View The Display Units
Press and release quickly the or button. The
display units will be flashed for 0.5 sec.
If you get lost, pressing and together will
always return you to the HOME display.
If, at any time, no key is pressed within 45 seconds,
the display will always return to the HOME display.
3.3 To Acknowledge a New Alarm
Press and together. This will also reset any
latched alarms that are no longer true.
3.4 Alarm Messages
If an alarm occurs a message will be flashed in the
display. This alternates with the measured temperature
as shown below:
Possible messages
-fsH Alarm - Full Scale High
-FSL Alarm - Full Scale Low
-deV Alarm - Deviation
-dHi Alarm - Deviation High
-dLo Alarm - Deviation Low
Sbr Sensor Break
Lbr Loop Break
Ldf Load Fail
End End of Timing
In place of the dash the alarm number is shown -
Alarm 1 or 2 or 3.
Display Units
*CDeg Centigrade
*FDeg Fahrenheit
*KDeg Kelvin
Linear inputs - no
units displayed
0.5 sec
or
oC
20
Alarm 1
Full Scale
Low
Actual
temperature
1fsL
20