Linking Dorgard X2
1. Ensure installed System X is not in an error state and the
CIE is not in a fire or fault state.
2. Ensure the Batteries are installed into the Dorgard X2unit.
3. On System X press and hold Button 1 LINK until the LCD
reads ‘LINK’. System X is now accepting Link data to the
Dorgard X2 unit.
4. Using the supplied plastic Screwdriver gently press the
Link Button on the front of the Dorgard X2 unit. Hold this
Button down until the LED located on top of the Dorgard
X2 unit lights red and the Dorgard X2beeps a long tone.
This resets the Dorgard X2and erases all associations with
other System X transmitters.
5. After the motor of the Dorgard X2has driven and the reset
beep has stopped, hold the Link Button on the front of the
Dorgard X2down again until the LED located on top of the
Dorgard X2 unit lights green. The Dorgard X2is now
searching for a TX to Link to.
6. When Dorgard X2has successfully Linked to the System X
transmitter its motor will drive, allowing the Plunger to be
held down. System X’s LCD will also display the Dorgard
X2’s Location Code, its signal strength, battery level and
software version. The Dorgard X2Location code should be
noted in the Installation Log at the rear of this Guide and
on the supplied sticker which should be attached to the
top of the Dorgard X2 and in this User Guide.
Note: the first Linked unit will be given the Location
code 000, the second Linked unit will be Location
code 001 etc.
7. If more Dorgard X2units are to be added to the system,
once powered up, press the Link Button on the front of the
Dorgard X2one at a time, waiting for confirmation on the
System X LCD between units.
8. When finished, press Button 1 LINK on the System X to
return to displaying the Clock.
Note. A maximum of 200 Dorgard X2units can be
linked to any one System X transmitter.