Assembly Instructions
Ceiling mounted air handling unit
and automatic control system
INSTALLATION
INSTRUCTIONS

2
This appliance may be used by children of 8 years or
above or by persons with reduced sensory capacity
or reduced physical or mental capacity, or by persons
with lacking experience or knowledge, provided they
have received instructions in the safe use of the
appliance or are supervised to ensure safe use and
providing they are aware of the risks. The product is
not suitable for use by children.
Children must not be allowed to play with the
appliance. Children must not carry out cleaning or
maintenance without supervision.
Our products are subject to continuous development
and we therefore reserve the right to make changes.
We disclaim all liability for printing errors.
See the following documents for more
information on the product:
114531 Spare parts list
114537 Wiring diagram without electric battery
114536 Wiring diagram with electric battery
110827 CI60
110828 CI600
SAFETY INSTRUCTIONS
• It is the installer's responsibility to
carry out a full safety and function
assessment of the appliance.
• To reduce the risk of fire, electric
shock or injury, read all the safety
instructions and warning texts before
using the unit.
• This unit is only designed for
ventilation air in homes and
commercial buildings.
• It must not be used to extract
combustible or flammable gases.
• Remove the power plug before
commencing any service and
maintenance work.
• Before opening the door: switch off
the heat, let the fans continue for
3 minutes to remove hot air, unplug
the unit and wait 2 minutes before
opening the doors.
• If the power cable is damaged, it must
be replaced by the manufacturer,
the manufacturer's service agent or
a similarly qualified person.
• The unit contains heating elements
that must not be touched when they
are hot.
• The unit must not be operated
without the filters being in place.
• Do not heat any combustible
substances under the cooker hood if
one is installed.
• Do not leave a saucepan or frying
pan containing oil or fat unsupervised
when using a cooker hood.
• Warranty claims will only be valid if
the instructions in the manuals have
been followed.
• To maintain a good indoor climate,
comply with regulations and avoid
condensation damage, the unit
must never be stopped except
during service/maintenance or in
connection with an accident.
• All electrical connections must be
carried out by qualified electricians.
• All plumbing work must be carried out
by an authorised plumber.
• The water battery must be located in
a room with a drain.
When servicing ceiling-mounted units, be aware of the
danger of components falling down.

3
Innhold
1 How to read the document....................................................................................................................................... 4
2 Planning and preparation work....................................................................................................................5
2.1 Joiner / fitter ...........................................................................................................................................................................................5
2.2 Plumber (if the unit has a water battery)................................................................................................5
2.3 Electrician...................................................................................................................................................................................................5
3 Installation........................................................................................................................................................................................................ 6
3.1 Mounting the safety strap................................................................................................................................................ 6
3.2 What is supplied?........................................................................................................................................................................... 6
3.3 Ceiling mounting..............................................................................................................................................................................7
3.4 Wall mounting...................................................................................................................................................................................13
3.5 Floor (attic) mounting.........................................................................................................................................................15
4 Duct connection.............................................................................................................................................................................. 16
4.1 Connection to the unit ...................................................................................................................................................... 16
5 Installation of the CI60/600 control panel.................................................................17
5.1 Contents......................................................................................................................................................................................................17
5.2 Installation of the CI60/600...................................................................................................................................17
5.3 Installation with a flush-mounted wall box.......................................................................................18
5.4 Surface mounting..................................................................................................................................................................... 18
5.5 Finishing off – C160................................................................................................................................................................ 18
5.6 Finishing off – C1600.......................................................................................................................................................... 18
6 Electrical work...................................................................................................................................................................................... 19
6.1 Supply air sensor for heating (B1) .................................................................................................................. 19
6.2 Frost sensor for water battery (B5) (if the unit has a water battery).... 19
6.3 Outdoor air damper (if the unit has a water battery)...................................................... 19
7 Plumbing work*.................................................................................................................................................................................. 19
8 Adjustment................................................................................................................................................................................................. 20
8.1 Adjustment with CI60......................................................................................................................................................... 20
8.2 Adjustment......................................................................................................................................................................................... 20
8.3 Adjusting the temperature....................................................................................................................................... 20
8.4 Adjustment with CI600 ................................................................................................................................................... 21
9 Installing the cooker hood...................................................................................................................................22
9.1 Installation of external cooker hood..........................................................................................................23
9.2 Adjusting the cooker hood.......................................................................................................................................23
10 General and system drawings.................................................................................................................24
10.1 System drawing (electric battery)................................................................................................................24
10.2 System drawing (electric battery)..............................................................................................................25
10.3 Nipple location...........................................................................................................................................................................26
11 Technical data...................................................................................................................................................................................27
11.1 Dimensioned drawing......................................................................................................................................................... 28
11.2 Capacity and sound data...........................................................................................................................................29
12 Final checks / Startup..................................................................................................................................................32
12.1 Final checks....................................................................................................................................................................................... 32
12.2 Startup....................................................................................................................................................................................................32
13 CE Declaration of Conformity................................................................................................................... 33

4
1 How to read the document
DANGER! DO NOT TOUCH
Symbols used
These products have a number of symbols that are used
to label the product itself and in the installation and user
documentation.
Extract air Extract
air from
kitchen
Outdoor air
Supply air
Exhaust air
CAUTION! When a text bears this
symbol, it means that personal
injury or serious damage to the equip-
ment may result if the instructions are
not followed.
NB! When a text bears this sym-
bol, damage to equipment or
poor efficiency may be the consequen-
ce of not following the instructions.
DANGER!
ELECTRICITY

5
2 Planning and preparation work
2.1 Joiner / fitter
Airflow
Check that the air moves from rooms with supply air
valves to rooms with extract air valves.
Kitchen
If a kitchen fan with a motor is included, sufficient
supply air must be ensured. See Chap. 9.1 Installation
of external cooker hood and Chap. 9.2 Adjusting
the cooker hood for more information.
Fireplace
When using a fireplace, sufficient air supply from
a separate supply air point must be ensured.
Location in the building
Location of the unit on an internal wall requires
insulation of the wall, interrupted studs and boards,
and double plasterboard or a wall structure of similar
quality (see Chap. 3.4.1 Positioning requirements).
Suspension of unit
See kap. 3 Installation på side 6.
Access
The unit must have good access for service/
maintenance. See kap. 3 Installation på side 6
for details.
Fire requirements
Any fire safety requirements must be clarified.
Location of heat sources must be coordinated with
extraction valves, so that heat is not sucked straight
out through the valves or door gaps.
2.2 Plumber (if the unit has a water battery)
Water pipe layout and location of the water battery
(duct battery) must be planned. These must be kept
warm to avoid frost damage. A closing damper with
spring must be used. See separate instructions that
accompany the water battery.
2.3 Electrician
Power supply
The units have an approx. 2 m cable with plug and
require a single-phase earthed socket nearby. Plug
requirements: 10 A. We recommend a separate circuit
for the unit. It is important that the plug is accessible
for servicing when the unit is fully installed.
If a cooker hood is to be connected to the ventilation
unit, a minimum Ø16 conduit must be installed for the
two-core signal cable.
NB!
The PG nipple for the power cable must be tightened
with a torque of 2.0 Nm if the cable is replaced.
For exact positioning of the electrical bushings,
see 11.1 Dimensioned drawing.
The assembly instructions for the
product must be followed.
Wiring for control switches.
Ø20 conduit for running the trailing cable for
controlling the unit should be laid between the
unit and an easily accessible place in the home
(e.g. outside the bathroom) and terminated with
a flush-mounted single wall box. The control switch
is located here. The control cable must be located
min. 30 cm away from any power cables. The control
cable must be max. 24 m to ensure a signal.
Control panel
The control panel is designed for flush mounting over
a single wall box or surface mounting on the wall.
figure 1
Positioning of bushings for
electrical conductors.
The water battery must be
located in a room with a drain.
Positioning must accord with
individual countries' electrical
safety legislation. Check which
rules apply in your country.

6
3 Installation
The unit can be installed in the following ways:
• On the ceiling.
• Horizontally on a wall.
Mounting devices for this can be purchased as
an accessory.
• On the floor (lying on its back).
In this case absorption feet are recommended
(available as an accessory).
The unit comes in both a left-hand and a right-hand
version, depending on what is best with regard to duct
positioning.
figure 2
Location options
1
2
3
3.1 Mounting the safety strap
Mount the safety strap as shown on figure 3.
figure 3
Fixed safety strap
When the unit is located on the
floor, this strap must always be
mounted.
We also recommend its use for
ceiling mounting.
5x
4x 1x 1x16x
1x
A
BCDE
Ffigure 4
What is supplied?
3.2 What is supplied?

7
3.3 Ceiling mounting
3.3.1
Positioning requirements
The unit is designed to be installed in boiler rooms,
laundry rooms, stores, lofts or other suitable areas.
The unit should be positioned in such a way that there
is no danger of noise nuisance in nearby rooms.
If the unit is located in a warm room where a lot of
moisture is generated, condensation may form on the
outside of the unit during periods when the outside
temperature is low.
The base should be stable and level.
3.3.2
Space requirements
The unit must be installed with suitable space for
servicing and maintenance such as filter replacement
and cleaning of fans and recovery system.
See figure 5. The control cable with plug for
automatic control must be easily accessible when the
unit is fully installed.
These are minimum requirements and only take
service needs into account.
figure 5
Space requirements for ceiling mounting
figure 6
Opening the door in case of ceiling mounting
530mm
400mm
400mm
200mm
*
In the case of mounting in an
enclosure or a suspended ceiling,
remember that the door must be
able to open by 120°.
Ensure there is servicing access
to electrical bushings. See the
dimensioned drawing for exact
location.
Positioning must accord with
individual countries' electrical
safety legislation. Check which
rules apply in your country.
* required
for access to
electrical bushings

8
Fixing brackets to be mounted in the same way regardless of top or side mounting
1 2
43
The air handling unit can be mounted in the ceiling in several different ways.
Alternative 1 - Top mounting Alternative 2 - Side mounting
To facilitate access to the fixing bracket,
the polystyrene rings round the bosses
may be removed.
3.3.3
Mounting of fixing bracket
1
2

9
Alternative 1 - Top mounting
3mm
The unit must always
be mounted at
min. 3mm distance
from the mounting
substrate, as shown in
figure 12. This is to
prevent structural
sound.

10
Alternative 1 - Top mounting
If it is necessary to pre-drill your mounting substrate,
the drilling pattern is given here:
Select a suitable fixing device which matches your mounting
substrate.
Remember that the unit weighs 46 kg and the fixing device
must be able to support this.
40 mm
40 mm
Ø8 mm
472mm
947mm
26mm
24mm
figure 7