
6
• Fire detectors
Gas Alarm Systems recommends the use of twisted-pair
cable, screened with an overall protective sheath that
is reproof, for example, Pirelli FP200 or similar. A 1K8
end-of-line resistor must be tted to the last detector
on each conventional smoke or heat detector loop.
Alternative cabling techniques, such as steel conduit,
may be acceptable provided that appropriate
standards are met. The minimum acceptable supply
voltage measured at the detector and the maximum
current drawn by that detector is dierent for each
device. Please refer to the relevant Installation,
Operating and Maintenance Instructions provided
with each detector to calculate the maximum cable
distances allowed for dierent cable types.
The maximum cable distance allowed is dependent
upon the installation, for example, whether Zener
Barriers or Galvanic Isolators are required (for I.S.
devices) or not.
When calculating maximum cable distances for
detectors, assume a minimum supply of 19 V and
a sense resistance of 98 Ω (39 Ω for convential re
channels).
Table 1: Typical cable characteristics
c.s.a (mm2)* Resistance (Ω per km)
Cable Loop
0.5 (20) 39.0 78.0
1.0 (17) 18.1 36.2
1.5 (15) 12.1 24.2
2.5 (13) 8.0 16.0
*Approximate c.s.a. in awg given in brackets.
Cable lengths should be calculated according to the
equations dened in the detector instructions sheet
and the cable and Gasmaster characteristics specied
above.
There are a number of suitable ways of terminating
cables and glands to Gasmaster dependant on the
cable and gland type:
– Steel wire-armoured (SWA) cable and glands with
electrical termination of the armour to the enclosure
via the gland.
– Screened cable with the screen terminated inside the
enclosure via a metal tag attached to the gland.
– Screened cable using an EMC gland where the screen
is terminated to the enclosure via the gland.
– For detectors, 4-20 mA outputs and RS- 485
terminations: screened cable where the screen is
connected to the SCR terminal on the appropriate
terminal strip.
2.5 Installing gas and re detectors
Install gas and re detectors as per instrument
installation manuals, paying attention to location and
cabling requirements. For ESU devices please refer to
installation manual provided.
2.6 Installing output devices
Gasmaster can drive 12 V dc or 24 V dc audible visual
alarms directly via the Audible Visual drive terminals
on the terminal PCB. Relays are provided for switching
additional outputs, and 12 V dc or 24 V dc 200 mA
auxiliary supplies are available adjacent to each
block of relay terminals for switching low power
devices. Section 2.9 provides detailed information on
connections to output devices.
2.7 Connecting mains power
Connect the external power supply using the two part
screw terminals, refer to Figures 2.4 and 2.5.
Gasmaster must be earthed either at the power
connector earth terminal (see Figure 2.4) or using the
stud on top of the enclosure.
Figure 2.4 Mains connection terminals on terminal PCB
2. Installation