REV.03-(16.03.2015)
2 GENERAL
the followng wall-mounted condensng gas bolers:
The Wallcon 115-125B-160B s sutable for use as a sngle
boler or as part of a cascade system.
CE LABEL
The applance comples wth the basc
requrements of the relevant European
drectves.
Conformty has been substantated by the
proper documents whch, together wth
the declaraton of conformty, are filed
wth the manufacturer.
•Wallcon 115-125B-160B
The boler may only be used to heat up water for heatng
systems as standard and/or domestc hot water (DHW)
systems wth the connecton of DHW tank.
The boler can be nstalled ether as a sngle system or as
part of a multple system (cascade system). A cascade
system enables several bolers of ths type to be
connected together, where maxmum of 16 bolers wth
a total capacty of 1.840 kW can be connected together.
Specal cascade unts (accessores) have been
developed to enable ths boler to be nstalled n a
cascade system. Every cascade unt ncludes an
nstallaton frame, horzontal headers, connecton ppes
for the boler, man gas ppe and vertcal low loss header.
Also, cascade unts are avalable for nstallng the bolers
nlne or back-to-back. These cascade unts make
nstallng a cascade system easer and less labour
ntensve. Please contact your dealer or the
manufacturer for further nformaton about cascade
systems.
CAUTION:
Damage to the nstallaton due to frost.
Install the heatng system n a room
whch s free from frost.
WARNING:
Fre hazard due to flammable materals or
lquds.
Do not store any flammable materals or
lquds n the drect vcnty of the boler.
CAUTION:
Boler damage due to contamnated
combuston ar or contamnated ar n the
boler room.
Never use the boler n an envronment whch
contans lots of dust or aggressve chemcals.
Such as spray shops,hardresser's shops,
locatons where trcholorethylene or hydrogen
haldes (e.g. contaned n aerosols, certan
adhesves, solvents or detergents, pants)
and other aggressve chemcals are used or
stored.
2.1 DESIGNED TO USE
2.3 BOILER ROOM & VENTILATION
These nstallaton and mantenance nstructons apply to
General
5
The WALLCON s a wall-hung condensng boler, for
CH and DHW(wth DHW tank) purposes, wth pre-mx
burner, made up of stanless steel heat exchanger.
The WALLCON bolers can be combned n a cascade
configuraton wth other heat generators to create
modular heatng plants made up of bolers connected to
the same water cr cut and wth electr onc controllers
communcatng va bus. The heat output of each boler
o
unt reaches 116.1 kW (100%, 50
o
C / 30 C)
modulated from 30% to 100%. The ef ficency reaches
107% and the low flue gas outlet temperature 64 o C .
2.2 DESCRIPTION OF THE APPLIANCE
The ndvdual heatng unts n cascadng configuraton
can be actvated, as well as by smple rotaton, n such a
way that when a certan percentage of output s reached
by the first unt, the other unts start automatcally, all wth
the same load factor.
The man features of the WALLCON Bolers are:
- fiber coated premx burner
- output from 29.3 to 116.1 kW (models 115 M and 115 S)
- heat output up to 1.840 kW, by connectng up to 16
bolers n a cascadng configuraton.
- quck connecton of the water and gas headers (opto -
nal)
- mcroprocessor control wth self-dagnoss, shown on
LED and the dsplay
- frost protecton functon actvated accordng to the out-
sde temperature and/or the temperature of the boler
- fitted for room thermostat n the hgh and low tempera-
ture zones
- outsde probe to enable the clmate control functon
- post-crculaton functon for the central heatng and
DHW crcuts
- prorty settable on the DHW, hgh or low temperatur e
crcut
-
- low nvestment costs for cascade operatons ( slave
- chmney sweep functon
-
-solar system & swmmng pool control functons
models can be controlled by Master models, wthout
usng any dsplay modules n slave unts)