General Measure M04 Manuale utente

M04
User’s Manual
M 0 4 - 0 0 1 6 0 7 0 1

Table
1. General Description..................................................................................................... - 1 -
1.1 Features and Functions.......................................................................................... - 1 -
1.2 Front Panel Description......................................................................................... - 1 -
1.3Rear Panel Description........................................................................................... - 2 -
1.4 Specification...........................................................................................................- 3 -
1.4.1Total Specification....................................................................................... - 3 -
1.4.2Analog Specification:............................................................................... - 3 -
1.4.3Digital Specification:................................................................................ - 3 -
2. Installation....................................................................................................................- 3 -
2.1Method.................................................................................................................... - 3 -
2.2Load Cell Connection............................................................................................. - 4 -
2.3 I/O Connection.......................................................................................................- 5 -
2.4Power Supply Connection...................................................................................... - 5 -
2.5Serial Port Connection............................................................................................ - 6 -
3. User Permission........................................................................................................... - 7 -
4. M Menu........................................................................................................................- 7 -
4.1System information...............................................................................................- 10 -
4.2Calibration.............................................................................................................- 12 -
4.3 Working Parameter.............................................................................................. - 13 -
4.4 Recipe Parameter................................................................................................. - 16 -
4.5 Communication Setting................................................................................. - 20 -
4.6 I/O Module...........................................................................................................- 20 -
4.6.1 Output define and Input define.................................................................- 21 -
4.6.2 IO test........................................................................................................- 23 -
4.7 Total......................................................................................................................- 24 -
5. Function......................................................................................................................- 24 -
5.1 Batch.................................................................................................................... - 24 -
5.2 Filling Level Controlling..................................................................................... - 24 -
5.2.1Three levels................................................................................................- 25 -
5.2.2Dual levels................................................................................................. - 25 -
5.2.3Signal level.................................................................................................- 25 -
6. Automatic Bagging.................................................................................................... - 25 -
6.1 WithHopper Mode Packaging..............................................................................- 25 -
6.2 Without Hopper Mode Packaging....................................................................... - 27 -
6.3 Dual Hoppers Interlock Mode Packaging........................................................... - 28 -
7. Dimension...................................................................................................................... - 29 -
8. A tta c hm e nt (M O DB US ad dre ss ) ....................................................................... - 30 -

M04 User Manual
M04-02110701 - 1 -
1. General Description
M04 Bagging controller is specially designed for single hopper packaging
controller. It is easier to operate, working faster and more precise with new algorithm.
USB port and two serial communication ports of the indicator made it easier to connect
with system. So it is widely used in various bagging machines for rice, feed, seed and
chemical etc.
1.1 Features and Functions
Working mode: with or without a material hopper
20 On/Off data input and output(8 in and 12 out), which can be defined by user.
Function of I/O testing to make bagging machine adjusting easier.
Automatic three-way feeding speed control and optional ‘fine filling inching’
function.
20 recipes can be stored for different weighing capacity.
Input & output data easily with USB port.
Material filling control function to make indicator and equipment connection easier.
Free fall correction.
Multilevel of digital filter
Batching times setting
Bag-patting function for powdery material bagging.
Automatic Zero-Tracking function.
Date and time setting
Identity setting for secondary user.
Two serial communication ports to connect with printer, computer or a second
display.
1.2 Front Panel Description

M04 User Manual
- 2 - M04-02110701
Display Area: show weighing data, status and some recipe information
Digital Button: input data and select parameter
Function Button: 【ZERO1】Clear weighing data.
【ZERO2】Check and set parameter accordingly by shortcut button.(Need
admittance.)
【M】Set parameters
【ESC】Exit and return to main menu.
【ENTER】Confirm status.
1.3Rear Panel Description

M04 User Manual
M04-02110701 - 3 -
1.4 Specification
1.4.1Total Specification
Power Supply: AC100V-240V 50Hz/60Hz±2%
Power Supply Filter: Installed inside.
Working Temperatures : -10~40℃
Maximum Humidity: 90% R.H without dew
Power: 15W
Dimension: 225×100×120mm
1.4.2Analog Specification:
Power Source for load cells : DC5V 125mA(MAX)
Input Resistance: 10MΩ
Zero Point Adjustment range:
0.02~4mV (When the transducer is 1mV/V.)
0.02~8mV (When the transducer is 2mV/V.)
0.02~12mV (When the transducer is 3mV/V.)
Minimum Input sensitivity: 0.02uV/d
Input Range : 0.2~15mV
A/D Type: Sigma - Delta
A/D Rate: 120Times/Second,240Times/Second,480Times/Second,960Times/Second
Non-Linear:0.01% F.S
Gain Drifting:10PPM/℃
Maximum Accuracy of Display:1/100,000
1.4.3Digital Specification:
Display:5 inch TFT LCD Display (800*480)
Negative Display:“—”
Overload Display:“OFL”
Decimal Position:5 options
2. Installation
2.1Method
M04 packing controller uses AC100V-240V 50Hz/60Hz±2% power supply with
grounding to guarantee the safety of the controller and other equipment connected.
The cables connecting M04 to load cells should not bind with other cables,especially
power supply cables, and must use shielded cables, because the signals from the load cells

M04 User Manual
- 4 - M04-02110701
is low voltage analog signals.
Note:Please DON’T connect the Ground Wire of the controller directly to the GND of
other equipment.
To install the M04 into a control box, please refer to the last chapter of this manual first,
and make appropriate installation holes according to the position of screw holes on the
housing box, remove the fixing plates on both sides of M04, put the controller into the
housing box, fix it with the fixing plates and lock them with screws.
2.2Load Cell Connection
Please refer to the picture below to connect load cells to the M04 controller.
When you chose the six-wired load cells, you must bridge the SN+ with EX+ and
bridge the SN- with EX-.
Please keep the cables of load cells clear of other cables.
EX+: Excitation+ EX-: Excitation- SN+: Sense+ SN-: Sense- SIG+: Signal+ SIG-: Signal-

M04 User Manual
M04-02110701 - 5 -
2.3 I/O Connection
M04 Controller uses optoelectronic isolation technology to transfer the ON/OFF data.
This needs 24V DC power supply that is provided from outside, through the 24V+ and the
24V-. The I/O signal input is low level effective. The output is open-collector output. The
driving current can reach 500mA.
Figure: Input Schematics(Take IN1,IN3,IN5,IN7 for example)
Figure: Output Schematics(Take OU1, OUT9 for example)
User can define I/O signals. (See 4.6 for details.)
2.4Power Supply Connection
M04 packing controller uses AC100V-240V 50Hz/60Hz±2% power supply with

M04 User Manual
- 6 - M04-02110701
grounding. The Correct connections are depicted below.
Power Supply Connector: L-Live Wire G-Ground Wire N-Null Wire
2.5Serial Port Connection
M04 can provide two serial ports. It is depicted below. One for RS485, the other is for
optional RS232 or RS485. Serial ports support MODBUS mode, rEAd mode, Cont mode
and printing.
Connection between M04 and a Host Computer(RS-232)

M04 User Manual
M04-02110701 - 7 -
Connection between M04 and a Host Computer(RS-485)
3. User Permission
M04 provides different powers for operator, administrator and system administrator in
order to avoid wrong operation. Among them, system administrator holds all operation
rights. The permission of operator and administrator hold limited permission as below:
Permissi
on
Operation
Operator
Not allow to set calibration parameter or calibration.
Not allow to revise the working parameter.
Not allow to define I/O.
Not allow to delete or clear accumulated value.
Allow to enter System information check version.
Technici
an
Not allow to revise weigher structure parameter in Working parameter.
Not allow to or set shortcut define.
Operators log on when connect power.
User log in identity shifted by pressing Zero button. The initial password is
000000.
To set password of administrator in User administration of System Info.
4. M Menu
Checking and revising parameters through M menu list.

M04 User Manual
- 8 - M04-02110701
As figure showed above, the left side is parameter list; the right side is brief
description and parameter information.
【▲】&【▼】:Shift parameter option.
【ENTER】: Check and set parameter information.
【ESC】: Return to main menu.
List
Parameters
Parameter list
Description
M
Recipe
parameter
Result waiting
Result waiting setting
Result waiting
timer
Result waiting timer setting
Overlimit /
underlimit
Over/under weight and way
parameters setting
Free fall
correction
Free fall correction and other
parameters setting
Fine flow inching
Fine flow inching mode setting
Under-compensati
on
Compensation filling parameter
setting
Pat parameters
Pat time and method setting
Other parameters
Single hopper combination Nos
setting
Working
parameter
Basic parameter
Basic parameter setting
Advanced
parameter
Operation parameter setting
Indice