Global Fire Equipment JUNIOR MINI-REP Manuale utente

OVERVIEW
The JUNIOR MINI-REP is a fully functional mini version of the JUNO NET Repeater which can be used with any
distributed or self contained JUNO NET or JUNIOR based Fire Alarm system. Its reduced dimensions make it
ideal for installation in reception areas or security booths where it would be impractical and unattractive to
install a full size control panel. Like its big brother, the J-NET-Repeater, the JUNIOR MINI-REP permits full
control of the system from multiple locations. Connection to the JUNO NET or JUNIOR is via an RS422/RS485,
Fibre Optic or TCP/IP interface. The JUNIOR MINI-REP is supplied complete with an RS422/RS485 interface as
standard. Depending on control panel loading, power for the JUNIOR MINI-REP can be supplied from the
control panel’s auxiliary power output or an external 24Volt power supply.
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL 1.0 - 12/2015
JUNIOR MINI-REP

IMPORTANT NOTES
!
competent person.
!A basic knowledge and training in the installation of Fire Detection systems is assumed.
!The Fire Detection system should be designed by a suitably qualified person with reference to the
Local Regulations and Guidance from the fire Officer where applicable.
!All wiring should be carried out with no power present in any part of the fire detection system.
NOTE: This unit should not be used to program the JUNO NET panel as it does not provide total
control over certain programming functions, namely all the functions that involve selecting loops in
the range 2-96 as no switches for loop change are provided.
This document provides detailed information on how to install and operate the JUNIOR MINI-REP when used
in conjuction with any of GFE’s Analogue Addressable Fire Detection panels using GFE’s RS-422/485 data loop
interface (J-NET-INT-RS485-NEW).
Detailed information on how to install these units in a network using either Fiber Optics orTCP/IP interfaces is
available in the appropriate interface installation manual and in the panel’s installation manual.
This unit is compatible with all models of the following panels:
JUNIOR V2, JUNIORV3, JUNIORV4, JUNO NET and JUNO NET EN54
Please note that for JUNIOR V2 and JUNO NET (Classic) panels, certain functions associated with key-switch
presses on the panel’s front display are different than those represented on the JUNIOR MINI-REP. If the JUNIOR
MINI-REP is going to be networked with either of these panel models, a modified overlay can optionally be
provided in these occasions. Please contact GFE for details.
Optionally the JUNIOR MINI-REP can be provided with a key-switch in order to gain access to Aceess Level 2
(Authorised User). Please contact GFE for details.
This equipment must only be installed and maintained by a suitably qualified and technically
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL 1.0 - 12/2015
JUNIOR MINI-REP

INSTALLATION
In order to correctly install a JUNIOR MINI-REP the following steps should be taken:
a) Remove the 4 screws fixing display to the unit’s back box.
b) Disconnect flat cable interconnecting Main Board to Data Loop Interface. SeeFigure3
c) Remove 3 fixing screws that hold the Data Loop Interface to back box. See Figure1
d) Fix unit’s back box in required mounting position using the mounting holes provided. SeeFigure1
e) Re-mount Data Loop Interface on back box using the 3 screws previously removed.
f) Reconnect flat cable connecting Main Board to Data Loop Interface board.
g) Finally connect Power Supply. are supplied by an external 24V DC, normally derived from
the control panel’s auxiliary supply outputs. Do not apply supply voltage until installation is complete.
h) Connect Data Loop Cables to interface following instructions provided in this manual and on appropriate
data loop interface data sheet.
Please also refer to the panel’s installation manual (JUNO NET and JUNIOR) for further details, in particular on
how to integrate the on a networked system. All connections should be performed with all
elements of the fire detection system unpowered.
This unit should be located where access to the internal components is not restricted and where the unit is not
exposed to high levels of moisture, vibration and shock.
Any metal swarf could damage the PCBs if it is still present when the Repeater is powered up so it is
recommended that all PCBs are removed from the box whilst the box is being installed. Make a note of the
positions of the PCBs before removal.
WARNING:
All cables should be screened.
Data loop cable should be RS422/485 grade data cable, eg:
Signal cables for RS485 Communication Links (twisted pair) to Repeater panels
12 AWG Signal 88202 Belden 9583WPW999
14 AWG Signal 88402 Belden 9581WPW995
16 AWG Signal 88602 Belden 9575WPW991
18 AWG Signal 88802 Belden 9574WPW975
FIRETUF FDZ1000 by Draka 2 core
PIRELLI type FP200 Gold 2 core
PIRELLI type FP-PLUS
Fibre Optic:
JUNIOR MINI-REP
JUNIOR MINI-REP
JUNIOR MINI-REP
JUNIOR MINI-REP
JUNIOR MINI-REP
JUNIOR MINI-REP
JUNIOR MINI-REP
Network cable U/UTP, F/UTP or SF/UTP (fireproof versions available) CAT5 or CAT6.
OBSERVE ESD PRECAUTIONSWHEN HANDLINGTHE PCBS.
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL 1.0 - 12/2015
JUNIOR MINI-REP

Figure 1: JUNIOR MINI-REP - Mechanical information
Top Cable Entry
256 mm
246 mm
75 mm
194 mm
187 mm
Rear Cable Entry
Data Loop
Interface PCB - Stand-offs
Back Box - Mounting Holes
MECHANICAL DETAILS
STATUS QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/ SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
DISABLED
TEST
FAULT
FIRE
ZONES
1 2 3456 7 8
9 10 11 12 13 14 15 16
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL 1.0 - 12/2015
JUNIOR MINI-REP

J-NET-INT-FO
FIBRE OPTIC INTERFACE
J-NET-INT-485-NEW
INTERFACE FOR RS485
COMMUNICATION
J-NET-INT-TCP/IP
INTERFACE FOR TCP/IP
COMMUNICATION
Typical cable form (one end)
VIEW FROM TOP
NOTE:
THROUGHOUT THE MANUAL,
THE PIN ON THE 5 WAY MOLEX
INDICATES WHICH PIN IS
RED
Nº1
VIEW FROM FRONT
MALE FEMALE
Figure 2: JUNIOR MINI-REP - Network Interfaces
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL 1.0 - 12/2015
JUNIOR MINI-REP

Connect JUNIOR MINI-REP CON3 (Data Loop)
to corresponding interface using the
5-way flat cable provided with each interface.
+24 V DC
Ground ( 0V )
Earth
Figure 3: JUNIOR MINI-REP - General Hardware and Connections Layout for RS-422/485 connection
J-NET-INT-RS-485
CN3
5 way flat cable
CON3
DATA LOOP
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL 1.0 - 12/2015
JUNIOR MINI-REP

CON3
CON3
JUNIOR MINI-REP
JUNIOR MINI-REP
CON3
JUNIOR Panel
2
2
2
2
2
2
2
2
2
2
2
2
Optional
Connections
Figure 4: JUNIOR MINI-REP - RS-485 Data Loop Connections
NOTES:
On JUNIOR Panel interface DIL
Switches 1 & 2 should be removed.
On JUNIOR MINI-REP interface DIL
Switches 1 & 2 should be ON.
Interface CON3 should be
connected to DATA CON
on JUNIOR version 3 panel, to MINI-
REP on JUNIOR V4 and to CON3 or
JUNIOR version 2 main board.
RS-485 OUT RS-485 IN
Tx1 a
Tx1 b
Rx2 a
Rx2 b
Rx1 a
Rx1 b
Tx2 a
Tx2 b
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL 1.0 - 12/2015
JUNIOR MINI-REP

JUNIOR Panel
CON3
CON3
2
2
2
2
2
2
2
2
Optional
Connections
NOTES:
On JUNIOR Panel interface DIL Switches 1 & 2 should be removed.
On JUNIOR MINI-REP interface DIL Switches 1 & 2 should be ON.
Interface CON3 should be connected to DATA CON
on JUNIOR version 3 panel, to MINI-REP on JUNIOR V4 and to CON3
or JUNIOR version 2 main board.
Figure 5: JUNIOR Panel JUNIOR MINI-REP (Single) - RS-485 Data Loop Connections
JUNIOR MINI-REP
RS-485 OUT RS-485 IN
Tx1 a
Tx1 b
Rx2 a
Rx2 b
Rx1 a
Rx1 b
Tx2 a
Tx2 b
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL 1.0 - 12/2015
JUNIOR MINI-REP

Figure 6:
SUB-PANEL - RS-485 Data Loop Connections
JUNO NET Panel - JUNIOR MINI-REP
NOTES:
On Main Panel DIL Switches 1 & 2
should be removed.
On Repeaters and sub-panels DIL
Switches 1 & 2 should be ON
CON3 on interface connect to CON
5 on J-NET-CON on Main Panel
or JUNO NET Repeater.
CON3 on interface connects to
DATA LOOP (CON 3) on JUNIOR
MINI-REP.
CON3
CON3
CON3
2
2
2
2
2
2
2
2
2
2
2
2
JUNIOR MINI-REP
SUB-PANEL
JUNO-NET
RS-485 OUT RS-485 IN
Tx1 a
Tx1 b
Rx2 a
Rx2 b
Rx1 a
Rx1 b
Tx2 a
Tx2 b
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL 1.0 - 12/2015
JUNIOR MINI-REP
Indice
Altri manuali Global Fire Equipment Pannello di controllo

Global Fire Equipment
Global Fire Equipment Junior V4 Manuale

Global Fire Equipment
Global Fire Equipment ORION PLUS Manuale utente

Global Fire Equipment
Global Fire Equipment NODE+ Manuale utente

Global Fire Equipment
Global Fire Equipment ORION PLUS Guida

Global Fire Equipment
Global Fire Equipment JUNO NET Manuale di istruzioni